46
Heat pump type(2)
Rating Conditions (ISO T1)
Electrical circuit
Total
Refrigerant circuit
Indoor side
Outdoor
side
Capacity
Input
Indoor unit Service Ref.
Phase, Hz
Volts
Amperes
Outdoor unit Service Ref.
Phase, Hz
Volts
Amperes
Discharge pressure
Suction pressure
Discharge temperature
Condensing temperature
Suction temperature
Ref. pipe length
Intake air temperature
Discharge air temperature
Intake air temperature
Mode
Service Ref.
SHF
BF
W
KW
V
A
V
A
°
C
°
C
°
C
m
°
C
°
C
°
C
°
C
°
C
°
C
Cooling
5350
2.35
0.41
10.82/3.32
2.30
0.48
86
41
3.5
5
27
19
12.6
35
24
0.72
0.09
Heating
6200
2.36
0.41
10.87 / 3.34
2.23
0.43
88
50
0.3
5
20
15
46.4
7
6
—
—
1, 50
230
1/3, 50
230/400
Cooling
6600
2.62
0.53
11.99 / 3.63
2.08
0.50
78
49
6.0
5
27
19
13.6
35
24
0.75
0.08
Heating
7250
2.66
0.53
12.18 / 3.69
2.14
0.42
82
48
0.7
5
20
15
41.9
7
6
—
—
1, 50
230
1/3, 50
230/400
Cooling
7450
3.37
0.53
15.57 / 4.82
2.28
0.44
86
52
3.5
5
27
19
12.3
35
24
0.73
0.08
Heating
9150
3.48
0.53
16.10 / 5.00
2.51
0.40
88
52
-0.5
5
20
15
48.2
7
6
—
—
1, 50
230
1/3, 50
230/400
Cooling
9600
3.62
0.69
16.61 / 5.06
1.94
0.50
75
47
10.0
5
27
19
12.8
35
24
0.76
0.06
Heating
10600
3.81
0.69
17.51 / 5.36
2.04
0.40
67
46
0.2
5
20
15
43.1
7
6
—
—
1, 50
230
1/3, 50
230/400
Cooling
12300
4.91
1.01
6.79
2.17
0.44
76
51
4.2
5
27
19
13.5
35
24
0.77
0.07
Heating
14800
5.11
1.01
7.10
2.26
0.41
78
46
0.5
5
20
15
44.0
7
6
—
—
1, 50
230
3, 50
400
Cooling
14200
5.89
1.01
8.34
2.30
0.46
79
51
4.0
5
27
19
12.1
35
24
0.74
0.07
Heating
17000
6.24
1.01
8.90
2.22
0.42
74
48
-0.5
5
20
15
47.7
7
6
—
—
1, 50
230
3, 50
400
MPa
MPa
D.B.
W.B.
D.B.
D.B.
W.B.
PCA-RP2GA
PCA-RP2GA
PCA-RP2.5GA
PCA-RP2.5GA
PCA-RP3GA
PCA-RP3GA
PCA-RP4GA
PCA-RP4GA
PCA-RP5GA
PCA-RP5GA
PCA-RP6GA
PCA-RP6GA
PUH-P3VGAA
PUH-P3VGAA.UK
PUH-P3VGAA
1
.UK
PUH-P3YGAA
PUH-P3YGAA.UK
PUH-P3YGAA
1
.UK
PUH-P2.5VGAA
PUH-P2.5VGAA.UK
PUH-P2.5VGAA
1
.UK
PUH-P2.5YGAA.UK
PUH-P2.5YGAA
1
.UK
PUH-P2VGAA
PUH-P2VGAA.UK
PUH-P2VGAA
1
.UK
PUH-P2YGAA.UK
PUH-P2YGAA
1
.UK
PUH-P4VGAA.UK
PUH-P4VGAA
1
.UK
PUH-P4YGAA
PUH-P4YGAA.UK
PUH-P4YGAA
1
.UK
PUH-P5YGAA
PUH-P5YGAA.UK
PUH-P5YGAA
1
.UK
PUH-P6YGAA
PUH-P6YGAA.UK
PUH-P6YGAA
1
.UK
The unit of pressure has been changed to MPa on the international system of unit (SI unit system).
The converted score against the traditional unit system can be gotten according to the formula below.
1(MPa)=10.2(
O
O
f/
F
F
)