7. Troubleshooting

State of Machine

Cause

Chec

k point

1.

 The fun does not r

un.

Content of confir

mation

3) 

The tr

ansf

or

mer (T01) is def

ectiv

e

4) 

The th

yr

istor module (SCRM) is def

ectiv

e

.  

5) 

The control pr

inting wir

ing board is

    def

ectiv

e

6) 

The f

an motor and unit side control bo

x

    are def

ectiv

e

.  

2) Connected mistak

e

1) 

The po

w

er-supply v

oltage is abnor

mal.

The v

alue of po

w

er-supply v

oltage is

confir

med

. (TB IN)

F

an po

w

er supply wir

ing is connected

with f

an controller po

w

er supply taking

out par

t, and confir

m oper

ation.

 

The b

linking of LED01 is confir

med.

The resistance is confir

med.

(Betw

een the lines of pr

imar

y side

, and

 lines of secondar

y side

.)

The content of P15 is chec

k

ed.

 (SCRM)

The content of P15 is judgment.

 (SCRM)

Whether the v

oltage is input to f

an motor is

confir

med.

Whether the f

an motor oper

ation is 

confir

med.

 

The f

an controller connection is confir

med.

The unit side connection is confir

med.

Is the po

w

er-supply v

oltage 342-457V?

T

roub

leshooting

Replace the tr

ansf

or

mer in case of abnor

mal 

resistance

.

When the v

oltage impression and f

an motor does

not w

or

k, f

an motor is def

ectiv

e

.

When the v

oltage is not impressed to the f

an, 

the

unit side control bo

x is def

ectiv

e

When there is no wrong abo

v

e-mentioned,

it is assumed f

an controller connection state

if abnor

mality relapses

, the control pr

inting board

is def

ectiv

e and e

xchange

Replace SCRM when abnor

mality is f

ound.

At the time of tur

ning on light.

 (alw

a

ys)

The CN01 connector is remo

v

ed, and measures

resistance

.  

When the resistance is 1 kilo-ohm or

less

, repair the control pr

inting board due to the

ther

mistor shor

t-circuit breakdo

wn.

  

In case of ther

mistor is correct, the control

pr

inting board is def

ectiv

e and e

xchange

.

At the time of tur

ning off light.

The CN01 connector is remo

v

ed, and measures

resistance

.  

When the resistance is 25 kilo-ohm or

more

, repair the control pr

inting board due to the

ther

mistor open breakdo

wn.

  

In case of ther

mistor is correct, the control

pr

inting board is def

ectiv

e and e

xchange

.

The wir

ing mistak

e is corrected.

  

The po

w

er supply wir

ing is confir

med,

and corrected.

 

TB OUT - f

an motor 

Resistance betw

een the lines of pr

imar

y side

(red and white)   about 310 ohm.

Resistance betw

een the lines of secondar

y

side (CN02 the connector is remo

v

ed from

the pr

inting wir

ing board.)

Betw

een 1-3 pin   about 0.9 ohm

CN02- ther

mistor

NF-SCRM-TB OUT

CNU

, CNV

, CNW

-SCRM 

(The connection is noted.)

TB IN-NF wir

ing

TB IN-T01-CN02.

11

After chec

king item 1)-4), when the po

w

er

supply is tur

ned on, the b

linking of LED01 is

confir

med.

 

Please intercept the power supply without fail, and secure safety when you execute detaching wiring, the connector,

and the measurement machine to the following work. 

Summary of Contents for PAC-205FC

Page 1: ... the correct safe install before installation 2 The customer must not install and not transfer the unit by themselves Safety and the function cannot be secured PAC 205FC CONTENTS CONTENTS 1 Safety precautions 2 Outline 3 Caution 4 Parts 5 Installation 6 Before starting the trial run 7 Troubleshooting PAGE 1 2 2 2 3 10 11 ...

Page 2: ...erformed improperly electric shock or fire may result If you need to have the unit repaired or moved consult your dealer 2 Before constructing the installation or transfer Do not touch the metal edges inside the unit without wearing glove on your hands Touching directly it may injure your hands Do not touch the compressor or refrigerant piping without wearing glove on your hands Touching directly ...

Page 3: ...ease consider the soundproofing wall equipment etc when using the fan controller in the place where the noise becomes a problem There is no worry which interferes to the unit though an electromagnetic sound might be generated from fan motor 3 When shipping the fan controller the dip switch on the control circuit board is set as follows Do not change factory set of all dip switches Accessory assy 1...

Page 4: ...trol box cover Earth sticker Fan controller Fan controller 1 The wiring from the printed circuit board CN04 is pulled out In case of PU 7 8 10 only CN04 Fan controller inside 2 Disconnect connector C11 C11 and C21 C21 The connector C11 and C21 remove to the motor side and the control box side F C N Control box MF2 MF3 Terminal block C11 C11 C21 C21 3 Cover the connector C11 control box side is cap...

Page 5: ...x side Control box MF2 MF3 Terminal block C11 C11 C21 C21 3 When the fan controller is installed the connector is connected in the control box The wiring from CN04 connect to the terminal block F C N in the control box In case of PUH 15 20 Please be careful do not damage wires by the sheet metal edges or the fin etc pull out 6 Please use the pipe cover 2x1 pieces and fix with the band 2x2 pieces 5...

Page 6: ...n controller is installed the connector is connected in the control box The wiring from CN04 connect to the terminal block F C N in the control box Please be careful do not damage wires by the sheet metal edges or the fin etc 5 Please use the pipe cover 1 piece and fix with the band 2 pieces 5 1 2 Wiring 3 After connect wiring to prevent wiring being damaged with the pipe header the pipe cover 2 p...

Page 7: ...nd band 4 pieces are used In that time never bundle the thermistor wiring with other wiring 5 After wiring ends the wiring is bundled with a remaining band Never bundle the thermistor and other wiring together 6 Ensure there is not wiring mistake found then only install the controller box cover and service panel Fan controller Earth sticker Unit wiring sticker Fan controller 2 Disconnect connector...

Page 8: ...ends the wiring is bundled with a remaining band Never bundle the thermistor and other wiring together 6 Ensure there is not wiring mistake found then only install the controller box cover and service panel Earth sticker 3 When the fan controller is installed the connector is connected in the control box Please be careful do not damage wires by the sheet metal edges or the fin etc Pipe cover Band ...

Page 9: ...re used In that time never bundle the thermistor wiring with other wiring 4 After wiring ends the wiring is bundled with a remaining band Never bundle the thermistor and other wiring together 5 Ensure there is not wiring mistake found then only install the controller box cover and service panel Fan controller Earth sticker Unit wiring sticker Fan controller 1 Disconnect connector C11 C11 The conne...

Page 10: ...ring is bundled with a remaining band Never bundle the thermistor and other wiring together 5 Ensure there is not wiring mistake found then only install the controller box cover and service panel 2 When the fan controller is installed the connector is connected in the control box The wiring from CN04 connect to the terminal block F C N in the control box Earth sticker Please be careful do not dama...

Page 11: ...essure switch off Whether LED01 has blinked is confirmed When the unit is in operation the fan controller output voltage measured in TB OUT and checked whether the output of about 200V There is a problem when it is an output of about 300V Step 2 3 The thermistor for the condensing temperature detection is surely connected with CN01 as before Step 2 4 Step 1 5 Is the thermistor for the condensing t...

Page 12: ... controller connection state if abnormality relapses the control printing board is defective and exchange Replace SCRM when abnormality is found At the time of turning on light always The CN01 connector is removed and measures resistance When the resistance is 1 kilo ohm or less repair the control printing board due to the thermistor short circuit breakdown In case of thermistor is correct the con...

Page 13: ...ted 12 2 The fan rotates oppositely 3 The rotation speed of fans cannot control Something wrong occurs by step2 2 drive confirmation of installed confirmation matter It becomes high pressure abnormal pressure 1 During heating drive During heating drive there is an input in CN04 and the fan becomes full load drive Normality CN04 the wiring for full load input in heating CN04 input is AC198 264V in ...

Page 14: ...e and exchange After checking item 1 5 when the power supply is turned on the blinking of LED01 is confirmed 3 The control printing wiring board is defective Item 1 is checked again After checking item 1 there is a possibility of a defective printed circuit board if a normal drive is not done After checking item 1 if there is no problem the control printing board is defective and exchange 13 4 The...

Page 15: ...ues 1 Check between G and K Use the smallest resistance range on the tester Judgment Value 1 5 ohm 80 ohm 14 Judgment Values 2 External View Internal Circuit Diagrams Check between AK1 and AK2 Use the greatest resistance range on the tester Judgment Value 60 kilo ohm ohm K AK1 AK1 AK1 AK1 AK2 AK2 AK2 AK2 G K G K G G K G K G K K K AK1 AK2 G G K K AK1 AK2 G G G K G K ...

Page 16: ...00 0005 TELEX J24532 CABLE MELCO TOKYO Specifications subject to change without notice WT03134X01 This product is designed and intended for use in the residential commercial and light industrial environment Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC The product at hand is based on the following EU regulations Printed in Malaysia ...

Reviews: