9.5.3
Errors that occur in CC-Link
Error code
(hexadecimal)
Error
description
Error cause (detailed)
Action
B115
H
Link error
A line error has occurred.
Check the line.
B116
H
Packet error
A line error has occurred.
Check the line.
B301
H
Processing
request error
during link stop
A line test request was issued during link stop.
Execute a line test while data link is being
performed.
B302
H
Specified station
number setting
error
The destination station number of the temporary
error invalid request or temporary error invalid
canceling request has exceeded the maximum
station number that can communicate.
Specify a station number smaller than or equal to
the maximum station number.
B303
H
No station
number setting
error
Although the temporary error invalid request or
temporary error invalid canceling request was
issued, the target station number has not been
set.
Set the station number.
(Address: 603
H
and 604
H
to 607
H
)
B304
H
Detection of a
faulty station in a
line test
When a line test was executed, an error has
been detected in a CC-Link remote station.
Check that the CC-Link remote station has been
started, and that the cables are not
disconnected.
B306
H
Specified station
number setting
error
A station number other than the start station
number has been specified in the temporary
error invalid request or temporary error invalid
canceling request.
Specify the start station number.
B307
H
Data link error in
all stations
When one of the following requests is issued, a
data link error has occurred in all stations.
• Data link restart (address: 5E0
H
.b0)
• Data link stop (address: 5E0
H
.b2)
Make sure that the data link returns to normal
then issue the request again.
B308
H
Station number
setting error
(installation
status)
A slave station number is outside of 1 to 64.
Set the number within 1 to 64.
B309
H
Station number
already in use
error
The station number of the connected module is
already in use (including the station numbers of
occupied stations and excluding the start station
number).
Check the station number of the corresponding
modules.
B30A
H
Mismatch
between the
connected
module status
and parameter
setting
The station type differs between the connected
modules and parameter settings.
(Example)
Start CC-Link with the automatic CC-Link startup
and save the parameters again.
B30B
H
Mismatch
between the
connected
module status
and parameter
setting
The network parameter setting does not match
with the connected module status.
Match them.
Connected
module
Remote
device
Intelligent
device
Parameter
setting
Remote I/O
Remote I/O
Remote
device