121
APPENDICES
A
Appendix
2 Det
a
ils of
Rem
o
te
Buf
fer Me
mory
69C
H
69D
H
69E
H
69F
H
Actual
installation/parame
ter consistency
status
Whether the connected module status matches with parameter settings is stored.
A mismatch error will occur in the following cases.
• The station types do not match.
• The number of occupied stations do not match.
• The expanded cyclic settings do not match.
• The CC-Link compatible versions do not match.
*1
When the number of connected modules is smaller than or equal to the number of
modules set using the parameter, a mismatch error will not occur. (When a remote
I/O station is actually connected and a remote device station has been set using
the parameter, for example, a mismatch error will not occur.)
0: Normal
1: Mismatch error
Example of a mismatch error
Installation
Parameter
Remote device station
Remote I/O station
Intelligent device station
Remote I/O station
Intelligent device station
Remote device station
• Reserved stations, station with the last station number, and stations later than that are excepted.
• Only the bit corresponding to the start station number turns on. This item is checked, and the result is
stored only upon data link start and the update of a parameter.
6B4
H
6B5
H
6B6
H
6B7
H
Line test 1 result
The result of the line test 1 is stored.
0: Normal
1: Error
The bits for the station number of the start station and the number of occupied stations are turned on.
6B8
H
Line test result
The result of a line test is stored.
0: Normal
Values other than 0: Error code (
783
H
Transmission
speed test result
The result of a transmission speed test is stored.
0: Normal
Values other than 0: Error code (
Address
Name
Description
to
to
to
to
to
The numbers 1 to 64 in the table are station numbers.
b15
16
32
48
64
15
31
47
63
14
30
46
62
13
29
45
61
4
20
36
52
3
19
35
51
2
18
34
50
1
17
33
49
b14
b13
b12
b3
b2
b1
b0
69C
H
69D
H
69E
H
69F
H
to
to
to
to
to
The numbers 1 to 64 in the table are station numbers.
b15
16
32
48
64
15
31
47
63
14
30
46
62
13
29
45
61
4
20
36
52
3
19
35
51
2
18
34
50
1
17
33
49
b14
b13
b12
b3
b2
b1
b0
6B4
H
6B5
H
6B6
H
6B7
H