44
6.4
Wiring
6.4.1
Wiring with a terminal block for module power supply and FG
(1) Tightening torque
Tighten the terminal block screws within the following specified torque range.
Overtightening can damage the module case.
(2) Wire to be used
The following table lists the wire to be connected to the terminal block for module power supply and FG.
For applicable solderless terminals, refer to the following.
• Performance Specifications (
(3) Installing and removing the terminal block
To remove the terminal block, loosen the terminal block mounting screw with a slotted screwdriver.
To install the terminal block, tighten the terminal block mounting screw.
Failure to secure the terminal block may cause drop, short-circuit, or malfunction.
Screw type
Tightening torque range
Terminal block mounting screw (M2.5 screw)
0.2 to 0.3N
m
Terminal screw (M2.5 screw)
0.5 to 0.6N
m
Diameter
Type
Material
Temperature rating
20 to 16 AWG
Stranded
Copper
75
or more