background image

En-

1-2. SPECIFICATIONS

1.  BEFORE INSTALLATION

1-1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY

•  Be sure to read “THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY” before installing the air conditioner.

•  Be sure to observe the warnings and cautions specified here as they include important items related to safety.

•  After reading this manual, be sure to keep it together with the OPERATING INSTRUCTIONS for future reference.

Required Tools for Installation

Phillips screwdriver

Level

Scale

Utility knife or scissors

Torque wrench

Wrench (or spanner)

5/32 in. (4 mm) hexagonal 

wrench

Flare tool for R40A

Gauge manifold for R40A

Vacuum pump for R40A

Charge hose for R40A

Pipe cutter with reamer

 ENGLISH

CONTENTS

. BEFORE INSTALLATION ............................................................

2. OUTDOOR UNIT INSTALLATION ...............................................3

3. FLARING WORK AND PIPE CONNECTION ...............................5

4. PURGING PROCEDURES, LEAK TEST, AND TEST RUN ......... 5

5. PUMPING DOWN ........................................................................7

Model

Power supply

Pipe length and height difference *, *2, *3, *4, *5, *6

Rated Voltage

Frequency Max. pipe length per indoor 

unit / for multi-system

Max. height difference *7

Max. no. of bends per 

indoor unit / for multi system Refrigerant adjustment A *8

MXZ-5B42NA

208 / 230 V

60 Hz

82 ft (25 m) / 262 ft (80 m)

49 ft (5 m)

25 / 80

.08 oz each 5 ft (20 g/m)

*1 Never  use  pipes  with  thickness  less  than  specified.  The  pressure  resist

-

ance will be insufficient.

*2 Use a copper pipe or a copper-alloy seamless pipe.

*3 Be careful not to crush or bend the pipe during pipe bending.

*4 Refrigerant pipe bending radius must be 4 in. (00 mm) or more.

*5 Insulation material : Heat resisting foam plastic 0.045 specific gravity

*6 Be sure to use the insulation of specified thickness. Excessive thickness 

may cause incorrect installation of the indoor unit and insufficient thickness 

may cause dew drippage.

*7 If the outdoor unit is installed higher than the indoor unit, max. height differ-

ence is reduced to 33 ft (0 m).

*8 If pipe length exceeds 97 ft (60 m), additional refrigerant (R40A) charge 

is  required.  (No  additional  charge  is  required  for  pipe  length  less  than  

97 ft (60 m).)

  Additional refrigerant (ft) = A ×  (pipe length (ft) - 97)

5

  Additional refrigerant (m) = A × (pipe length (m) - 60)

n

  Do not install the unit by yourself (user).

  Incomplete installation could cause fire or electric shock, injury due to the unit 

falling, or leakage of water. Consult the dealer from whom you purchased the 

unit or a qualified installer.

n

  Follow the instructions detailed in the installation manual.

  Incomplete installation could cause fire or electric shock, injury due to the unit 

falling, or leakage of water. 

n

  When installing the unit, use appropriate protective equipment and tools 

for safety.

  Failure to do so could cause injury.

n

  Install the unit securely in a place that can bear the weight of the unit.

  If the installation location cannot bear the weight of the unit, the unit could fall 

causing injury.

Perform electrical work according to the installation manual and be sure 

to use an exclusive circuit. Do not connect other electrical appliances to 

the circuit.

  If the capacity of the power circuit is insufficient or there is incomplete electrical 

work, it could result in a fire or an electric shock.

n

  Ground the unit correctly.

  Do not connect the ground wire to a gas pipe, water pipe, lightning rod or 

telephone ground. Defective grounding could cause electric shock.

Do not damage the wires.

  Damaged wires could cause fire.

Be sure to shut off the main power when setting up the indoor P.C. board 

or wiring.

  Failure to do so could cause electric shock.

n

  Use the specified wires to securely connect the indoor and outdoor units. 

Attach the wires firmly to avoid applying stress to the terminal block.

  Improper connection could cause fire.

Do not install the unit in a place where flammable gas may leak.

  If gas leaks and accumulates around the unit, it could cause an explosion.

n

  Do not use intermediate connection of the power cord or the extension 

cord.Do not connect many devices to one AC outlet.

  It could cause a fire or an electric shock.

Use the parts provided or specified parts for the installation work.

  The use of defective parts could cause an injury or leakage of water due to a 

fire, an electric shock, the unit falling, etc.

When plugging the power supply plug into the outlet, make sure that there 

is no dust, blockage, or loose parts both in the outlet and on the plug. 

Verify that the power supply plug is completely in the outlet. 

  If there is dust, blockage, or loose parts on the power supply plug or the outlet, 

it could cause electric shock or fire. If loose parts are found on the power supply 

plug, replace it.

Securely attach the electrical cover to the indoor unit and the service 

panel to the outdoor unit.

  If the electrical cover of the indoor unit and/or the service panel of the outdoor 

unit are not attached securely, dust, water, etc. could collect in the unit and 

could cause a fire or an electric shock.

When installing, relocating, or servicing the unit, make sure that no sub-

stance other than the specified refrigerant (R410A) enters the refrigerant 

circuit.

  Any presence of foreign substance such as air can cause abnormal pressure 

rise and may result in explosion or injury. The use of any refrigerant other than 

that specified for the system will cause mechanical failure, system malfunction, 

or unit breakdown. In the worst case, this could lead to a serious impediment 

to securing product safety.

Do  not  discharge  the  refrigerant  into  the  atmosphere.  Check  that  the 

refrigerant gas does not leak after installation has been completed. If 

refrigerant leaks during installation, ventilate the room.

  If refrigerant comes in contact with a fire, harmful gas could be generated. 

  If refrigerant gas leaks indoors, and comes into contact with the flame of a fan 

heater, space heater, stove, etc., harmful gases will be generated.

Use appropriate tools and piping materials for installation. 

  The pressure of R40A is .6 times higher than R22. Not using the appropri-

ate tools and materials, or improper installation could cause the pipes to burst 

causing an injury. 

When pumping down the refrigerant, stop the compressor before discon-

necting the refrigerant pipes.

  If the refrigerant pipes are disconnected while the compressor is running and 

the stop valve is open, air could be drawn in and the pressure in the refrigera

-

tion cycle could become abnormally high, causing the pipes to burst. 

When installing the unit, securely connect the refrigerant pipes before 

starting the compressor.

  If the compressor is started before the refrigerant pipes are connected and the 

stop valve is open, air could be drawn in and the pressure in the refrigeration 

cycle could become abnormally high, causing the pipes to burst.

Fasten a flare nut with a torque wrench as specified in this manual.

  If fastened too tight, a flare nut could break and cause refrigerant leakage.

Install the unit  according to national wiring regulations.

n

  Depending on the installation area, install a Ground Fault Interrupt (GFI) 

circuit breaker.

  If the Ground Fault Interrupt (GFI) circuit breaker is not installed, an electric 

shock could occur.

n

  Perform the drainage/piping work securely according to the installation 

manual.

  If there is defect in the drainage/piping work, water could drip from the unit, 

and damage household items.

n

  Do not touch the air inlet or the aluminum fins of the outdoor unit.

  This could cause injury. 

n

  Do not install the outdoor unit where small animals may live.

  If small animals enter the unit and damage its electrical parts, it could cause a 

malfunction, smoke emission, or fire. Keep the area around the unit clean. 

 

CAUTION

(Could lead to serious injury when operated incorrectly.)

 

WARNING

(Could lead to death or serious injury, etc.)

JG79A337H02_en.indd   1

2013/04/23 (火)   午後 2:55:52

Summary of Contents for MXZ-5B42NA

Page 1: ... l appareil extérieur Lors de l installation de l appareil intérieur consultez la notice d installation de cet appareil Toute altération structurelle requise pour l installation doit être conforme aux exi gences du code du bâtiment local Manual de instalación Para el INSTALADOR En este manual sólo se describe la instalación de la unidad exterior Para instalar la unidad interior consulte el manual ...

Page 2: ... and accumulates around the unit it could cause an explosion n Do not use intermediate connection of the power cord or the extension cord Do not connect many devices to one AC outlet It could cause a fire or an electric shock n Use the parts provided or specified parts for the installation work The use of defective parts could cause an injury or leakage of water due to a fire an electric shock the...

Page 3: ...t blowing only When there is an obstacle in front of the unit as shown in the figure open space above behind and on the sides of the unit is required 2 Front blowing side open As long as space indicated in the figure is provided it is allowed to install the unit where obstacles are behind and on the sides of the unit No obstacle above the unit FREE SPACE REQUIRED AROUND OUTDOOR UNIT Service space ...

Page 4: ...a wire The Q ty for B to K in the above table is quan tity to be used per indoor unit More than 3 15 16 in 100 mm Open as a rule More than 19 11 16 in 500 mm if the front and both sides are open More than 3 15 16 in 100 mm More than 7 7 8 in 200 mm if there are obstacles to both sides Open as a rule More than 19 11 16 in 500 mm if the back both sides and top are open More than 13 25 32 in 350 mm O...

Page 5: ...ix both cable and wire with cable clamps Connecting order Connect the terminal block in following order A B C D E P A B C D E P A B C D E P A B C E P A B C D E D P Power supply Terminal block for indoor outdoor unit Service panel Screws Lock nut Conduit cover Conduit connector CONNECTING WIRES AND CONNECTING GROUND WIRE Use solid conductor AWG14 or stranded conductor AWG14 Use double insulated cop...

Page 6: ...on of pipe Fig 3 Aim the copper pipe downward while removing burrs to prevent burrs from dropping in the pipe 3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A inch mm from the table according to the to...

Page 7: ... or steam Union Stop valve Liquid pipe Indoor unit Stop valve with service port Gas pipe Refrigerant gas cylinder operating valve for R410A Gauge manifold valve for R410A Charge hose for R410A Refrigerant gas cylinder for R410A with siphon Electronic scale for refrigerant charging Refrigerant liquid Outdoor unit Union Union Union Procedure Press the piping wiring correction switch SW871 1 minute o...

Page 8: ...Refer to the indoor unit installation manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 1 to 0 psi Gauge 0 05 to 0 MPa or the protection function may operate due to the pressure increase in the high pressure refrigerant circuit If this occurs use a refrigerant collecting device to collect all of th...

Page 9: ...ement Un raccordement incorrect peut provoquer un incendie n N installez pas l unité dans un endroit exposé à des fuites de gaz inflam mable La fuite ou l accumulation de gaz autour de l unité peut entraîner une explo sion n N utilisez pas de raccord intermédiaire ou de rallonge pour brancher le cordon d alimentation Ne branchez pas plusieurs appareils à une prise secteur Cela peut provoquer un in...

Page 10: ... vibrations transmises par l unité Remarque Si vous utilisez le climatiseur alors que la température extérieure est basse veillez à observer les instructions ci dessous N installez jamais l unité externe dans un endroit où le côté présentant l entrée la sortie d air risque d être directement exposé au vent Pour protéger l unité externe du vent installez la de façon à ce que l entrée d air soit fac...

Page 11: ...reillis métallique utiliser un morceau de bois traité d une épais seur de 25 32 po 20 mm minimum entre le mur et la tuyauterie ou isoler la tuyauterie en lui appliquant 7 à 8 couches de ruban isolant en vinyle Pour utiliser la tuyauterie existante effectuer un cycle COOL REFROI DISSEMENT de 30 minutes et lancer l aspiration avant de procéder à la dépose de l ancien climatiseur Reformer l écrou éva...

Page 12: ...local CÂBLE D ALIMENTATION Utiliser un conducteur massif ou toronné AWG8 Utiliser des conducteurs en cuivre uniquement Respecter le code électrique local CÂBLE DE TERRE Utiliser un conducteur massif ou toronné AWG8 Utiliser des conducteurs en cuivre uniquement Respecter le code électrique local AVERTISSEMENT Utiliser le câble de connexion conforme aux normes techniques pour raccorder les unités in...

Page 13: ...é de réfrigérant recom mandée si nécessaire Veillez à charger lentement le liquide réfrigérant Sinon la composition de réfrigérant dans le système peut changer et affecter les performances du climatiseur 9 Serrez le bouchon de l ouverture de service pour recréer les conditions d origine 10 Test de contrôle des fuites 3 2 RACCORDEMENT DES TUYAUX 1 Appliquez une fine couche d huile réfrigérante G su...

Page 14: ...our annuler cette fonction Vérifier ensuite les raccordements de câblage et tuyauterie de manière conventionnelle en faisant fonctionner les appareils intérieurs l un après l autre Pour utiliser cette fonction l appareil doit être alimenté Veiller à ne pas toucher des éléments autres que le commutateur notamment le panneau de commande Cela peut entraîner un choc électrique ou des brûlures par des ...

Page 15: ...ous au manuel d installation de l appareil intérieur pour la méthode d arrêt du système Si trop de réfrigérant a été ajouté au système de climatisation il se peut que la pression ne parvienne pas à baisser jusqu à 0 1 à 0 psi jauge 0 05 à 0 MPa ou la fonction de protection pourrait se déclencher en raison de la montée de pression dans le circuit de réfrigérant à haute pression Dans ce cas utilisez...

Page 16: ...la mable Si hay fugas de gas y se acumula alrededor de la unidad podría producirse una explosión n No emplee conexiones intermedias del cable de alimentación ni tampoco un cable de extensión Evite también conectar demasiados aparatos a una sola toma de CA Esto podría provocar un incendio o una descarga eléctrica n Utilice las piezas suministradas o indicadas para efectuar la instala ción El empleo...

Page 17: ...vibración que pudiera transmitirse desde ese punto Nota Si utiliza el acondicionador de aire cuando la temperatura exterior sea baja observe las instrucciones siguientes No instale nunca la unidad exterior en un lugar en el que el lado de entra da salida de aire quede expuesto directamente al viento Para evitar la exposición al viento instale la unidad exterior con el lado de entrada de aire hacia...

Page 18: ...ed con contenido metálico placas de latón o rejillas metálicas ponga un trozo de madera tratada químicamente de 25 32 pulg 20 mm o más de grosor entre la pared y los tubos o envuelva los tubos con 7 u 8 vueltas de cinta aislante de vinilo Para utilizar tuberías ya existentes active el modo COOL REFRIGERA CIÓN durante 30 minutos y realice el bombeo de vaciado antes de retirar el acondicionador de a...

Page 19: ...normativa eléctrica local CABLE DE ALIMENTACIÓN Utilice un conductor sólido o trenzado AWG8 Use únicamente conductores de cobre Siga la normativa eléctrica local CABLE DE TIERRA Utilice un conductor sólido o trenzado AWG8 Use únicamente conductores de cobre Siga la normativa eléctrica local ATENCIÓN Conecte las unidades interior y exterior con el cable de conexión normalizado destinado a este fin ...

Page 20: ...ulg mm en la tabla de acuerdo con la herramienta seleccionada 5 Compruebe Compare el abocardado con la Fig 6 Si el abocardado se ve defectuoso corte la sección abocardada y repita el proceso de abocardado 1 Retire la tapa de la abertura de servicio de la válvula de retención situada en el lado de la tubería de gas de la unidad exterior Inicialmente las válvulas de retención están completamente cer...

Page 21: ...ón para detectarla y corregirla siguiendo estos procedimientos Asegúrese de lo siguiente La unidad recibe corriente Las válvulas de retención están abiertas 4 4 EXPLICACIÓN PARA EL USUARIO Basándose en el MANUAL DE INSTRUCCIONES explique al usuario cómo utilizar el equipo de aire acondicionado cómo utilizar el controlador remoto cómo retirar los filtros de aire cómo retirar o colocar el control re...

Page 22: ...ga la operación Consulte el manual de instalación de la unidad interior para más detalles acerca del método de detención de la operación Si se ha añadido demasiado refrigerante al sistema con acondicionador de aire puede que la presión no baje de 0 1 a 0 psi manómetro de 0 05 a 0 MPa o que la función de protección se ponga en funcionamiento debido a la subida de presión en el circuito de refrigera...

Page 23: ......

Page 24: ...JG79A337H02 HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: