background image

En-5

3-2. PIPE CONNECTION

1) Apply a thin coat of refrigeration oil (G) to the flared ends of the pipes and the 

pipe connections of the outdoor unit.

2) Align  the  center  of  the  pipe  with  that  of  the  pipe  connections  of  the  outdoor 

unit, then hand tighten the flare nut 3 to 4 turns.

3) Tighten the flare nut with a torque wrench as specified in the table.

•  Over-tightening may cause damage to the flare nut, resulting in refrigerant 

leakage.

•  Be  sure  to  wrap  insulation  around  the  piping.  Direct  contact  with  the  bare 

piping may result in burns or frostbite.

3-3. INSULATION AND TAPING

1) Cover piping joints with pipe cover.

2) For outdoor unit side, surely insulate every piping including valves.

3) Using piping tape (E), apply taping starting from the entry of outdoor unit.

•  Stop the end of piping tape (E) with tape (with adhesive agent attached).

•  When piping have to be arranged through above ceiling, closet or where the 

temperature and humidity are high, wind additional commercially sold insula-

tion to prevent condensation.

 

WARNING

When installing  the  unit,  securely 

connect the refrigerant pipes before 

starting the compressor.

 

CAUTION

When  there  are  the  ports  which are 

not  used,  make  sure  their  nuts  are 

tightened securely.

Fig. 

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Fig. 6

Tilted Uneven Burred

Good

No good

Burr Copper pipe

Spare reamer

Pipe cutter

Smooth all 

around

Even length 

all around

Inside is shin-

ing without any 

scratches.

B

Flare nut

Die

Copper pipe

Clutch type

Flaring tool

Wing nut type

Copper 

pipe

Pipe diameter  

[inch (mm)]

[inch (mm)]

A [inch (mm)]

Tightening torque

Clutch type tool for R40A Clutch type tool for R22

Wing nut type tool for R22

ft-Ib

N•m

kgf•cm

/4 (ø6.35)

2/32 (7)

0 to 0.02

(0 to 0.5)

0.04 to 0.06

(.0 to .5)

0.06 to 0.08

(.5 to 2.0)

0 to 3

3.7 to 7.7

40 to 80

3/8 (ø9.52)

7/8 (22)

25 to 30

34.3 to 4.2

350 to 420

/2 (ø2.7)

-/32 (26)

0.08 to .0

(2.0 to 2.5)

36 to 42

49.0 to 56.4

500 to 575

5/8 (ø5.88)

-5/32 (29)

54 to 58

73.5 to 78.4

750 to 800

3.  FLARING WORK AND PIPE CONNECTION

3-1. FLARING WORK

) Cut the copper pipe correctly with pipe cutter. (Fig. , 2)

2) Completely remove all burrs from the cut cross section 

of pipe. (Fig. 3)

•  Aim the copper pipe downward while removing burrs 

to prevent burrs from dropping in the pipe.

3) Remove flare nuts attached to indoor and outdoor units, 

then put them on pipe having completed burr removal. 

(Not possible to put them on after flaring work.) 

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the 

dimension shown in the table. Select A inch (mm) from 

the table according to the tool selected.

5) Check 

•  Compare the flared work with Fig. 6.

•  If flare is noted to be defective, cut off the flared sec

-

tion and do flaring work again.

4-1. PURGING PROCEDURES AND LEAK TEST

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

1) Remove service port cap of stop valve on the side of the outdoor unit gas pipe. (The 

stop valves are fully closed and covered in caps in their initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of stop valve on 

the gas pipe side of the outdoor unit.

3) Run the vacuum pump. (Vacuumize for more than 15 minutes.)

4) Check the vacuum with gauge manifold valve, then close gauge manifold valve, 

and stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure the pointer of gauge manifold 

valve remains in the same position. Confirm that pressure gauge shows -14.7 psi 

[Gauge] (-0.0 MPa).

6) Remove gauge manifold valve quickly from service port of stop valve.

7) Fully open all stop valves on the gas pipe and the liquid pipe. Operating without 

fully opening lowers the performance and this causes trouble.

8) Refer to -2., and charge the prescribed amount of refrigerant if needed. Be sure 

to charge slowly with liquid refrigerant. Otherwise, composition of the refrigerant 

in the system may be changed and affect performance of the air conditioner.

9) Tighten cap of service port to obtain the initial status.

0) Leak test

Gauge manifold 

valve 

(for R40A)

Compound pressure 

gauge (for R40A)

Handle High

Charge hose 

(for R40A)

Pressure gauge

(for R40A)

-4.7 psi 

(-0.0 MPa)

Handle Low

Vacuum pump

(for R40A)

Stop valve cap

(Torque 5 to 

22 ft-lb, 9.6 to 

29.4 N•m, 200 

to 300 kgf•cm)

Pull the handle toward you 

and rotate /4 turn in a counter 

clockwise direction to open.

Push in the handle and rotate the 

cap back to its original position.

Cap

*Close

*Open

Hexagonal 

wrench

*4 to 5 turns

Service port cap

(Torque 0 to 3 ft-lb, 

3.7 to 7.7 N•m, 40 

to 80 kgf•cm)

Open

Close

JG79A337H02_en.indd   5

2013/04/23 (火)   午後 2:55:53

Summary of Contents for MXZ-5B42NA

Page 1: ... l appareil extérieur Lors de l installation de l appareil intérieur consultez la notice d installation de cet appareil Toute altération structurelle requise pour l installation doit être conforme aux exi gences du code du bâtiment local Manual de instalación Para el INSTALADOR En este manual sólo se describe la instalación de la unidad exterior Para instalar la unidad interior consulte el manual ...

Page 2: ... and accumulates around the unit it could cause an explosion n Do not use intermediate connection of the power cord or the extension cord Do not connect many devices to one AC outlet It could cause a fire or an electric shock n Use the parts provided or specified parts for the installation work The use of defective parts could cause an injury or leakage of water due to a fire an electric shock the...

Page 3: ...t blowing only When there is an obstacle in front of the unit as shown in the figure open space above behind and on the sides of the unit is required 2 Front blowing side open As long as space indicated in the figure is provided it is allowed to install the unit where obstacles are behind and on the sides of the unit No obstacle above the unit FREE SPACE REQUIRED AROUND OUTDOOR UNIT Service space ...

Page 4: ...a wire The Q ty for B to K in the above table is quan tity to be used per indoor unit More than 3 15 16 in 100 mm Open as a rule More than 19 11 16 in 500 mm if the front and both sides are open More than 3 15 16 in 100 mm More than 7 7 8 in 200 mm if there are obstacles to both sides Open as a rule More than 19 11 16 in 500 mm if the back both sides and top are open More than 13 25 32 in 350 mm O...

Page 5: ...ix both cable and wire with cable clamps Connecting order Connect the terminal block in following order A B C D E P A B C D E P A B C D E P A B C E P A B C D E D P Power supply Terminal block for indoor outdoor unit Service panel Screws Lock nut Conduit cover Conduit connector CONNECTING WIRES AND CONNECTING GROUND WIRE Use solid conductor AWG14 or stranded conductor AWG14 Use double insulated cop...

Page 6: ...on of pipe Fig 3 Aim the copper pipe downward while removing burrs to prevent burrs from dropping in the pipe 3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A inch mm from the table according to the to...

Page 7: ... or steam Union Stop valve Liquid pipe Indoor unit Stop valve with service port Gas pipe Refrigerant gas cylinder operating valve for R410A Gauge manifold valve for R410A Charge hose for R410A Refrigerant gas cylinder for R410A with siphon Electronic scale for refrigerant charging Refrigerant liquid Outdoor unit Union Union Union Procedure Press the piping wiring correction switch SW871 1 minute o...

Page 8: ...Refer to the indoor unit installation manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 1 to 0 psi Gauge 0 05 to 0 MPa or the protection function may operate due to the pressure increase in the high pressure refrigerant circuit If this occurs use a refrigerant collecting device to collect all of th...

Page 9: ...ement Un raccordement incorrect peut provoquer un incendie n N installez pas l unité dans un endroit exposé à des fuites de gaz inflam mable La fuite ou l accumulation de gaz autour de l unité peut entraîner une explo sion n N utilisez pas de raccord intermédiaire ou de rallonge pour brancher le cordon d alimentation Ne branchez pas plusieurs appareils à une prise secteur Cela peut provoquer un in...

Page 10: ... vibrations transmises par l unité Remarque Si vous utilisez le climatiseur alors que la température extérieure est basse veillez à observer les instructions ci dessous N installez jamais l unité externe dans un endroit où le côté présentant l entrée la sortie d air risque d être directement exposé au vent Pour protéger l unité externe du vent installez la de façon à ce que l entrée d air soit fac...

Page 11: ...reillis métallique utiliser un morceau de bois traité d une épais seur de 25 32 po 20 mm minimum entre le mur et la tuyauterie ou isoler la tuyauterie en lui appliquant 7 à 8 couches de ruban isolant en vinyle Pour utiliser la tuyauterie existante effectuer un cycle COOL REFROI DISSEMENT de 30 minutes et lancer l aspiration avant de procéder à la dépose de l ancien climatiseur Reformer l écrou éva...

Page 12: ...local CÂBLE D ALIMENTATION Utiliser un conducteur massif ou toronné AWG8 Utiliser des conducteurs en cuivre uniquement Respecter le code électrique local CÂBLE DE TERRE Utiliser un conducteur massif ou toronné AWG8 Utiliser des conducteurs en cuivre uniquement Respecter le code électrique local AVERTISSEMENT Utiliser le câble de connexion conforme aux normes techniques pour raccorder les unités in...

Page 13: ...é de réfrigérant recom mandée si nécessaire Veillez à charger lentement le liquide réfrigérant Sinon la composition de réfrigérant dans le système peut changer et affecter les performances du climatiseur 9 Serrez le bouchon de l ouverture de service pour recréer les conditions d origine 10 Test de contrôle des fuites 3 2 RACCORDEMENT DES TUYAUX 1 Appliquez une fine couche d huile réfrigérante G su...

Page 14: ...our annuler cette fonction Vérifier ensuite les raccordements de câblage et tuyauterie de manière conventionnelle en faisant fonctionner les appareils intérieurs l un après l autre Pour utiliser cette fonction l appareil doit être alimenté Veiller à ne pas toucher des éléments autres que le commutateur notamment le panneau de commande Cela peut entraîner un choc électrique ou des brûlures par des ...

Page 15: ...ous au manuel d installation de l appareil intérieur pour la méthode d arrêt du système Si trop de réfrigérant a été ajouté au système de climatisation il se peut que la pression ne parvienne pas à baisser jusqu à 0 1 à 0 psi jauge 0 05 à 0 MPa ou la fonction de protection pourrait se déclencher en raison de la montée de pression dans le circuit de réfrigérant à haute pression Dans ce cas utilisez...

Page 16: ...la mable Si hay fugas de gas y se acumula alrededor de la unidad podría producirse una explosión n No emplee conexiones intermedias del cable de alimentación ni tampoco un cable de extensión Evite también conectar demasiados aparatos a una sola toma de CA Esto podría provocar un incendio o una descarga eléctrica n Utilice las piezas suministradas o indicadas para efectuar la instala ción El empleo...

Page 17: ...vibración que pudiera transmitirse desde ese punto Nota Si utiliza el acondicionador de aire cuando la temperatura exterior sea baja observe las instrucciones siguientes No instale nunca la unidad exterior en un lugar en el que el lado de entra da salida de aire quede expuesto directamente al viento Para evitar la exposición al viento instale la unidad exterior con el lado de entrada de aire hacia...

Page 18: ...ed con contenido metálico placas de latón o rejillas metálicas ponga un trozo de madera tratada químicamente de 25 32 pulg 20 mm o más de grosor entre la pared y los tubos o envuelva los tubos con 7 u 8 vueltas de cinta aislante de vinilo Para utilizar tuberías ya existentes active el modo COOL REFRIGERA CIÓN durante 30 minutos y realice el bombeo de vaciado antes de retirar el acondicionador de a...

Page 19: ...normativa eléctrica local CABLE DE ALIMENTACIÓN Utilice un conductor sólido o trenzado AWG8 Use únicamente conductores de cobre Siga la normativa eléctrica local CABLE DE TIERRA Utilice un conductor sólido o trenzado AWG8 Use únicamente conductores de cobre Siga la normativa eléctrica local ATENCIÓN Conecte las unidades interior y exterior con el cable de conexión normalizado destinado a este fin ...

Page 20: ...ulg mm en la tabla de acuerdo con la herramienta seleccionada 5 Compruebe Compare el abocardado con la Fig 6 Si el abocardado se ve defectuoso corte la sección abocardada y repita el proceso de abocardado 1 Retire la tapa de la abertura de servicio de la válvula de retención situada en el lado de la tubería de gas de la unidad exterior Inicialmente las válvulas de retención están completamente cer...

Page 21: ...ón para detectarla y corregirla siguiendo estos procedimientos Asegúrese de lo siguiente La unidad recibe corriente Las válvulas de retención están abiertas 4 4 EXPLICACIÓN PARA EL USUARIO Basándose en el MANUAL DE INSTRUCCIONES explique al usuario cómo utilizar el equipo de aire acondicionado cómo utilizar el controlador remoto cómo retirar los filtros de aire cómo retirar o colocar el control re...

Page 22: ...ga la operación Consulte el manual de instalación de la unidad interior para más detalles acerca del método de detención de la operación Si se ha añadido demasiado refrigerante al sistema con acondicionador de aire puede que la presión no baje de 0 1 a 0 psi manómetro de 0 05 a 0 MPa o que la función de protección se ponga en funcionamiento debido a la subida de presión en el circuito de refrigera...

Page 23: ......

Page 24: ...JG79A337H02 HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: