background image

En-2

1-4. SELECTING THE INSTALLATION LOCATION

•  Where it is not exposed to strong wind.

•  Where airflow is good and dustless.

•  Where rain or direct sunshine can be avoided as much as possible.

•  Where neighbours are not annoyed by operation sound or hot air.

•  Where rigid wall or support is available to prevent the increase of operation 

sound or vibration.

•  Where there is no risk of combustible gas leakage.

•  When installing the unit, be sure to secure the unit legs.

•  Where it is at least 0 ft. (3 m) away from the antenna of TV set or radio. 

Operation of the air conditioner may interfere with radio or TV reception in 

areas where reception is weak. An amplifier may be required for the affected 

device.

•  Install the unit horizontally.

•  Please  install  it  in  an  area  not  affected  by  snowfall  or  blowing  snow.  In 

areas with heavy snow, please install a canopy, a pedestal and/or some 

baffle boards.

Note:

It is advisable to make a piping loop near outdoor unit so as to reduce vibra

-

tion transmitted from there.

Note: 

When operating the air conditioner in low outside temperature, be sure to 

follow the instructions described below.

•  Never install the outdoor unit in a place where its air inlet/outlet side may 

be exposed directly to wind.

•  To prevent exposure to wind, install the outdoor unit with its air inlet side 

facing the wall.

• 

To prevent exposure to wind, it is recommended to install a baffle board on 

the air outlet side of the outdoor unit.

Avoid the following places for installation where air conditioner trouble is li

-

able to occur.

•  Where flammable gas could leak.

•  Where there is much machine oil.

•  Salty places such as the seaside.

•  Where sulfide gas is generated such as a hot spring.

•  Where there is high-frequency or wireless equipment.

•  Where there is emission of high levels of VOCs, including phthalate com

-

pounds, formaldehyde, etc., which may cause chemical cracking.

3. 

Obstacles in front (blowing) only

When there is an obstacle in front of the unit as shown in the figure, open 

space above, behind, and on the sides of the unit is required.

2. 

Front (blowing) side open

As long as space indicated in the 

figure is provided, it is allowed to 

install  the  unit  where  obstacles 

are  behind  and  on  the  sides  of 

the  unit.  (No  obstacle  above  the 

unit)

FREE SPACE REQUIRED AROUND OUTDOOR UNIT

Service space

•  When installing the unit in an area that is enclosed with walls such as a 

verandah, be sure to have enough space as shown below. 

  In this case, the air conditioning capacity and power consumption might 

deteriorate.

•  When installing two or more units, do not install the units in front or be-

hind each other.

1. 

Obstacles above

When  there  is  no  obstacle  in  front 

and on the sides of the unit, it is al-

lowed  to  install  the  unit  where  an 

obstacle is above the unit only if the 

space shown in the figure is provided.

5. 

Service space

Provide space for service and maintenance as shown in the figure.

9-/6 (500) 

or more

3-5/6 (00) 

or more

4. 

Obstacles in front, behind and on side(s)

(Unit: inch (mm))

Height of the obstacle is 47-/4 (200) or less

9-/6 (500) or more

3-5/6 (00) or more

9-/6 (500) 

or more

3-25/32 (350) or more

3-5/6 (00) or more

3-25/32 (350) or more

3-5/6 (00) or more

7-7/8 (200) or more

3-25/32 (350) 

or more

3-5/6 (00) 

or more

7-7/8 (200) or more

3-25/32 (350) 

or more

9-/6 (500) 

or more

9-/6 (500) 

or more

1-3. SELECTING OPTIONAL DIFFERENT-DIAMETER JOINTS

If the diameter of connection pipe does not match the port size of outdoor unit, use optional different-diameter joints according to the following table.

Port size of outdoor unit

Optional different-diameter joints (port size of outdoor unit 

 diameter of connection pipe)

MXZ-5B

Liquid / Gas

/4 (6.35) 

 3/8 (9.52) : PAC-493PI

3/8 (9.52) 

 /2 (2.7) : MAC-A454JP

3/8 (9.52) 

 5/8 (5.88) : PAC-SG76RJ

/2 (2.7) 

 3/8 (9.52) : MAC-A455JP

/2 (2.7) 

 5/8 (5.88) : MAC-A456JP

Refer to the installation manual of indoor unit for the diameter of connection pipe of indoor unit.

A UNIT

/4 (6.35) / /2 (2.7)

B - E UNIT

/4 (6.35) / 3/8 (9.52)

(Unit: inch (mm))

JG79A337H02_en.indd   2

2013/04/23 (火)   午後 2:55:52

Summary of Contents for MXZ-5B42NA

Page 1: ... l appareil extérieur Lors de l installation de l appareil intérieur consultez la notice d installation de cet appareil Toute altération structurelle requise pour l installation doit être conforme aux exi gences du code du bâtiment local Manual de instalación Para el INSTALADOR En este manual sólo se describe la instalación de la unidad exterior Para instalar la unidad interior consulte el manual ...

Page 2: ... and accumulates around the unit it could cause an explosion n Do not use intermediate connection of the power cord or the extension cord Do not connect many devices to one AC outlet It could cause a fire or an electric shock n Use the parts provided or specified parts for the installation work The use of defective parts could cause an injury or leakage of water due to a fire an electric shock the...

Page 3: ...t blowing only When there is an obstacle in front of the unit as shown in the figure open space above behind and on the sides of the unit is required 2 Front blowing side open As long as space indicated in the figure is provided it is allowed to install the unit where obstacles are behind and on the sides of the unit No obstacle above the unit FREE SPACE REQUIRED AROUND OUTDOOR UNIT Service space ...

Page 4: ...a wire The Q ty for B to K in the above table is quan tity to be used per indoor unit More than 3 15 16 in 100 mm Open as a rule More than 19 11 16 in 500 mm if the front and both sides are open More than 3 15 16 in 100 mm More than 7 7 8 in 200 mm if there are obstacles to both sides Open as a rule More than 19 11 16 in 500 mm if the back both sides and top are open More than 13 25 32 in 350 mm O...

Page 5: ...ix both cable and wire with cable clamps Connecting order Connect the terminal block in following order A B C D E P A B C D E P A B C D E P A B C E P A B C D E D P Power supply Terminal block for indoor outdoor unit Service panel Screws Lock nut Conduit cover Conduit connector CONNECTING WIRES AND CONNECTING GROUND WIRE Use solid conductor AWG14 or stranded conductor AWG14 Use double insulated cop...

Page 6: ...on of pipe Fig 3 Aim the copper pipe downward while removing burrs to prevent burrs from dropping in the pipe 3 Remove flare nuts attached to indoor and outdoor units then put them on pipe having completed burr removal Not possible to put them on after flaring work 4 Flaring work Fig 4 5 Firmly hold copper pipe in the dimension shown in the table Select A inch mm from the table according to the to...

Page 7: ... or steam Union Stop valve Liquid pipe Indoor unit Stop valve with service port Gas pipe Refrigerant gas cylinder operating valve for R410A Gauge manifold valve for R410A Charge hose for R410A Refrigerant gas cylinder for R410A with siphon Electronic scale for refrigerant charging Refrigerant liquid Outdoor unit Union Union Union Procedure Press the piping wiring correction switch SW871 1 minute o...

Page 8: ...Refer to the indoor unit installation manual about the method for stopping the operation If too much refrigerant has been added to the air conditioner system the pressure may not drop to 0 1 to 0 psi Gauge 0 05 to 0 MPa or the protection function may operate due to the pressure increase in the high pressure refrigerant circuit If this occurs use a refrigerant collecting device to collect all of th...

Page 9: ...ement Un raccordement incorrect peut provoquer un incendie n N installez pas l unité dans un endroit exposé à des fuites de gaz inflam mable La fuite ou l accumulation de gaz autour de l unité peut entraîner une explo sion n N utilisez pas de raccord intermédiaire ou de rallonge pour brancher le cordon d alimentation Ne branchez pas plusieurs appareils à une prise secteur Cela peut provoquer un in...

Page 10: ... vibrations transmises par l unité Remarque Si vous utilisez le climatiseur alors que la température extérieure est basse veillez à observer les instructions ci dessous N installez jamais l unité externe dans un endroit où le côté présentant l entrée la sortie d air risque d être directement exposé au vent Pour protéger l unité externe du vent installez la de façon à ce que l entrée d air soit fac...

Page 11: ...reillis métallique utiliser un morceau de bois traité d une épais seur de 25 32 po 20 mm minimum entre le mur et la tuyauterie ou isoler la tuyauterie en lui appliquant 7 à 8 couches de ruban isolant en vinyle Pour utiliser la tuyauterie existante effectuer un cycle COOL REFROI DISSEMENT de 30 minutes et lancer l aspiration avant de procéder à la dépose de l ancien climatiseur Reformer l écrou éva...

Page 12: ...local CÂBLE D ALIMENTATION Utiliser un conducteur massif ou toronné AWG8 Utiliser des conducteurs en cuivre uniquement Respecter le code électrique local CÂBLE DE TERRE Utiliser un conducteur massif ou toronné AWG8 Utiliser des conducteurs en cuivre uniquement Respecter le code électrique local AVERTISSEMENT Utiliser le câble de connexion conforme aux normes techniques pour raccorder les unités in...

Page 13: ...é de réfrigérant recom mandée si nécessaire Veillez à charger lentement le liquide réfrigérant Sinon la composition de réfrigérant dans le système peut changer et affecter les performances du climatiseur 9 Serrez le bouchon de l ouverture de service pour recréer les conditions d origine 10 Test de contrôle des fuites 3 2 RACCORDEMENT DES TUYAUX 1 Appliquez une fine couche d huile réfrigérante G su...

Page 14: ...our annuler cette fonction Vérifier ensuite les raccordements de câblage et tuyauterie de manière conventionnelle en faisant fonctionner les appareils intérieurs l un après l autre Pour utiliser cette fonction l appareil doit être alimenté Veiller à ne pas toucher des éléments autres que le commutateur notamment le panneau de commande Cela peut entraîner un choc électrique ou des brûlures par des ...

Page 15: ...ous au manuel d installation de l appareil intérieur pour la méthode d arrêt du système Si trop de réfrigérant a été ajouté au système de climatisation il se peut que la pression ne parvienne pas à baisser jusqu à 0 1 à 0 psi jauge 0 05 à 0 MPa ou la fonction de protection pourrait se déclencher en raison de la montée de pression dans le circuit de réfrigérant à haute pression Dans ce cas utilisez...

Page 16: ...la mable Si hay fugas de gas y se acumula alrededor de la unidad podría producirse una explosión n No emplee conexiones intermedias del cable de alimentación ni tampoco un cable de extensión Evite también conectar demasiados aparatos a una sola toma de CA Esto podría provocar un incendio o una descarga eléctrica n Utilice las piezas suministradas o indicadas para efectuar la instala ción El empleo...

Page 17: ...vibración que pudiera transmitirse desde ese punto Nota Si utiliza el acondicionador de aire cuando la temperatura exterior sea baja observe las instrucciones siguientes No instale nunca la unidad exterior en un lugar en el que el lado de entra da salida de aire quede expuesto directamente al viento Para evitar la exposición al viento instale la unidad exterior con el lado de entrada de aire hacia...

Page 18: ...ed con contenido metálico placas de latón o rejillas metálicas ponga un trozo de madera tratada químicamente de 25 32 pulg 20 mm o más de grosor entre la pared y los tubos o envuelva los tubos con 7 u 8 vueltas de cinta aislante de vinilo Para utilizar tuberías ya existentes active el modo COOL REFRIGERA CIÓN durante 30 minutos y realice el bombeo de vaciado antes de retirar el acondicionador de a...

Page 19: ...normativa eléctrica local CABLE DE ALIMENTACIÓN Utilice un conductor sólido o trenzado AWG8 Use únicamente conductores de cobre Siga la normativa eléctrica local CABLE DE TIERRA Utilice un conductor sólido o trenzado AWG8 Use únicamente conductores de cobre Siga la normativa eléctrica local ATENCIÓN Conecte las unidades interior y exterior con el cable de conexión normalizado destinado a este fin ...

Page 20: ...ulg mm en la tabla de acuerdo con la herramienta seleccionada 5 Compruebe Compare el abocardado con la Fig 6 Si el abocardado se ve defectuoso corte la sección abocardada y repita el proceso de abocardado 1 Retire la tapa de la abertura de servicio de la válvula de retención situada en el lado de la tubería de gas de la unidad exterior Inicialmente las válvulas de retención están completamente cer...

Page 21: ...ón para detectarla y corregirla siguiendo estos procedimientos Asegúrese de lo siguiente La unidad recibe corriente Las válvulas de retención están abiertas 4 4 EXPLICACIÓN PARA EL USUARIO Basándose en el MANUAL DE INSTRUCCIONES explique al usuario cómo utilizar el equipo de aire acondicionado cómo utilizar el controlador remoto cómo retirar los filtros de aire cómo retirar o colocar el control re...

Page 22: ...ga la operación Consulte el manual de instalación de la unidad interior para más detalles acerca del método de detención de la operación Si se ha añadido demasiado refrigerante al sistema con acondicionador de aire puede que la presión no baje de 0 1 a 0 psi manómetro de 0 05 a 0 MPa o que la función de protección se ponga en funcionamiento debido a la subida de presión en el circuito de refrigera...

Page 23: ......

Page 24: ...JG79A337H02 HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN ...

Reviews: