Mitsubishi Electric MXZ-3D54VA Installation Manual Download Page 6

En-5

4-1. PURGING PROCEDURES AND LEAK TEST

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

4-2. GAS CHARGE

Perform gas charge to unit.

) Connect gas cylinder to the service port of stop valve.

2) Perform air purge of the pipe (or hose) coming from refrigerant gas cylinder.

3) Replenish specified amount of the refrigerant, while operating the air condi

-

tioner for cooling.

Note:

In case of adding refrigerant, comply with the quantity specified for the refrigerat

-

ing cycle.

CAUTION:

When charging the refrigerant system with additional refrigerant, be sure to use 

liquid  refrigerant. Adding  gas  refrigerant  may  change  the  composition  of  the 

refrigerant in the system and affect normal operation of the air conditioner. Also, 

charge the liquid refrigerant slowly, otherwise the compressor will be locked.

To  maintain  the  high  pressure  of  the  gas  cylinder,  warm  the  gas  cylinder  with 

warm water (under 40°C) during cold season. But never use naked fire or steam.

) Remove service port cap of stop valve on the side of the outdoor unit 

gas pipe. (The stop valves are fully closed and covered in caps in 

their initial state.)

2) Connect gauge manifold valve and vacuum pump to service port of 

stop valve on the gas pipe side of the outdoor unit.

3) Run the vacuum pump. (Vacuumize for more than 5 minutes.)

4) Check the vacuum with gauge manifold valve, then close gauge 

manifold valve, and stop the vacuum pump.

5) Leave as it is for one or two minutes. Make sure the pointer of gauge 

manifold valve remains in the same position. Confirm that pressure 

gauge shows -0.0 MPa [Gauge] (-760 mmHg).

6) Remove gauge manifold valve quickly from service port of stop valve.

7) Fully open all stop valves on the gas pipe and the liquid pipe. Operat-

ing without fully opening lowers the performance and this causes 

trouble.

8) Refer to -2., and charge the prescribed amount of refrigerant if 

needed. Be sure to charge slowly with liquid refrigerant. Otherwise, 

composition of the refrigerant in the system may be changed and 

affect performance of the air conditioner.

9) Tighten cap of service port to obtain the initial status.

0) Leak test

Union

Stop valve

Liquid 

pipe

Indoor 

unit

Stop valve with 

service port

Gas 

pipe

Refrigerant gas            

cylinder  

operating valve

(for R40A)

Gauge manifold 

valve (for R40A)

Charge hose 

(for R40A)

Refrigerant gas cylinder for R40A with siphon

Electronic scale for refrigerant charging

Refrigerant (liquid)

Outdoor 

unit

* D unit is for 

4D72VA only.

Union

Union
Union

Stop valve 

for GAS

Stop valve cap

(Torque 9.6 to 

29.4 N•m, 200 

to 300 kgf•cm)

Gauge manifold 

valve (for R40A)

Compound pressure 

gauge (for R40A)

–0.0MPa  

(–760 mmHg)

Handle 

Low

Handle High

Vacuum pump

(for R40A)

*Close

*Open

Hexagonal wrench

*4 to 5 turns

Stop valve 

for LIQUID

Pressure gauge

(for R40A)

Precautions when using 

the control valve

When attaching the control valve to 

the service port, valve core may de-

form or loosen if excess pressure is 

applied. This may cause gas leak.

Service port

Charge hose 

(for R40A)

Body

Close

Open

Control 

valve

A

When attaching the control valve to 

the service port, make sure that the 

valve core is in closed position, and 

then  tighten  part A.  Do  not  tighten 

part A or turn the body when valve 

core is in open position.

Service port cap

(Torque 3.7 to 

7.7 N•m, 40 to 

80 kgf•cm)

Charge hose 

(for R40A)

4-3. REMOVING THE MAINTENANCE PANEL

The setting of Dip Switch on the outdoor controller board can be changed 

without removing the front panel.

Follow the procedures below to remove the maintenance panel and set 

the Dip Switch.

1) Remove screw(s) which fix the maintenance panel.

2) Remove the maintenance panel, and perform necessary settings.

3) Install the maintenance panel.

Note:

Make sure to fix the maintenance panel securely. Incomplete installation 

could cause malfunction.

Maintenance panel

JG79A627H01_en.indd   5

2012/09/07   11:32:17

Summary of Contents for MXZ-3D54VA

Page 1: ...relativo manuale di instal lazione Εγχειρίδιο εγκατάστασης Για τον ΤΕΧΝΙΚΟ Στο παρόν εγχειρίδιο περιγράφεται μόνο η εγκατάσταση της μονάδας εξωτερικού χώρου Για την εγκατάσταση της μονάδας εσωτερικού χώρου ανατρέξτε στο εγχειρίδιο εγκατάστασης της μονάδας εσωτερικού χώρου Manual de Instalação Para o INSTALADOR Este manual descreve apenas a instalação da unidade exterior Quando proceder à instalaçã...

Page 2: ...suffocation Provide ventilation in accord ance with EN378 1 n Check that the refrigerant gas does not leak after installation has been completed If refrigerant gas leaks indoors and comes into contact with the flame of a fan heater space heater stove etc harmful substances will be generated n Use appropriate tools and piping materials for installation The pressure of R410A is 1 6 times more than R...

Page 3: ...n operating the air conditioner in low outside temperature be sure to follow the instructions described below Never install the outdoor unit in a place where its air inlet outlet side may be exposed directly to wind To prevent exposure to wind install the outdoor unit with its air inlet side facing the wall To prevent exposure to wind it is recommended to install a baffle board on the air outlet s...

Page 4: ...frigeration oil Little amount H Putty 1 I Pipe fixing band 2 to 7 J Fixing screw for I 2 to 7 K Wall hole sleeve 1 L Soft PVC hose 15 mm inner di ameter or hard PVC pipe VP16 for drain socket 1 1 Note Place indoor outdoor unit connecting wire B and power supply cord A at least 1 m away from the TV antenna wire The Q ty for B to K in the above table is quan tity to be used per indoor unit Units sho...

Page 5: ...pper pipe Spare reamer Pipe cutter Smooth all around Even length all around Inside is shin ing without any scratches Flare nut Die Copper pipe Clutch type Flaring tool Wing nut type 3 2 PIPE CONNECTION 1 Apply a thin coat of refrigeration oil G to the flared ends of the pipes and the pipe connections of the outdoor unit Do not apply refrigeration oil on screw threads Excessive tightening torque wi...

Page 6: ...r to 1 2 and charge the prescribed amount of refrigerant if needed Be sure to charge slowly with liquid refrigerant Otherwise composition of the refrigerant in the system may be changed and affect performance of the air conditioner 9 Tighten cap of service port to obtain the initial status 10 Leak test Union Stop valve Liquid pipe Indoor unit Stop valve with service port Gas pipe Refrigerant gas c...

Page 7: ... refrigerant is released into the atmosphere 1 Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit 2 Fully close the stop valve on the liquid pipe side of the outdoor unit 3 Close the stop valve on the gas pipe side of the outdoor unit almost completely so that it can be easily closed fully when the pressure gauge shows 0 MPa Gauge 0 kgf ...

Page 8: ...omschlägen kommen n Achten Sie beim Installieren Umsetzen oder Warten der Anlage darauf dass keine andere Substanz als das vorgeschriebene Kältemittel R410A in den Kältemittelkreislauf gelangt Das Vorhandensein irgendeiner anderen Substanz wie z B Luft kann einen abnormalen Druckanstieg verursachen und zu einer Explosion oder zu Ver letzungen führen Die Verwendung eines anderen als des vorgeschrie...

Page 9: ...r heiße Luft gestört werden Wählen Sie einen Ort an dem eine feste Wand oder eine feste Ab stützung vorhanden ist um eine Verstärkung von Betriebsgeräuschen und Vibrationen zu vermeiden Wählen Sie einen Ort an dem nicht die Gefahr des Austritts brennba rer Gase besteht Wenn Sie das Gerät anbringen befestigen Sie die Füße des Gerätes Wählen Sie einen Ort an dem mindestens 3 m Abstand zu einer Fern ...

Page 10: ...BLAUFROHRE FÜR AUSSENGERÄT Arbeiten an der Ablaufverrohrung nur vornehmen wenn der Ablauf von einer Stelle aus erfolgt 1 Ein Loch für den Ablauf wählen und den Ablaufstutzen 1 an diesem Loch anbringen 2 Die anderen Löcher mit Ablaufkappen verschließen 2 3 Den im Fachhandel erhältlichen Schlauch aus Weich PVC L mit 15 mm Innendurchmesser an dem Ablaufstutzen 1 und der Ablaufleitung anschlie ßen Hin...

Page 11: ...anschlüsse des Außengerätes auf Tragen Sie kein Kältemaschinenöl auf die Schraubengewinde auf Zu starkes Anziehen der Schrauben kann diese beschädigen 2 Richten Sie die Rohrmitte auf die Rohranschlüsse des Außengerätes aus und ziehen Sie die Konusmutter 3 bis 4 Umdrehungen von Hand an 3 Ziehen Sie die Konusmutter mit einem Drehmomentschlüssel gemäß den An gaben in der Tabelle fest Durch ein zu fes...

Page 12: ...ßiger Druck ausgeübt wird Dadurch kann ein Gasleck verursacht werden Vergewissern Sie sich beim An bringen des Steuerventils an der Wartungsöffnung dass sich der Ven tileinsatz in der geschlossenen Po sition befindet und ziehen Sie dann den Teil A fest Ziehen Sie den Teil A nicht fest und drehen Sie den Körper nicht wenn sich der Ventileinsatz in der geöffneten Position befindet Wartungsan schluss...

Page 13: ...dem Benutzer unter Verwendung der BEDIENUNGSANLEITUNG wie das Klimagerät verwendet wird wie die Fernbedienung verwendet wird wie die Luftfilter entfernt werden wie die Fernbedienung aus dem Fernbedienungshalter entnommen und wieder eingesetzt wird wie das Gerät ge reinigt wird welche Vorsichtsmaßregeln zu beachten sind usw Empfehlen Sie dem Benutzer die BEDIENUNGSANLEITUNG sorgfältig zu lesen 4 6 ...

Page 14: ...я труб с хладагентом Если трубы с хладагентом отсоединить при работающем компрессоре и от крытом стопорном клапане возможно засасывание воздуха и чрезмерное по вышение давления в контуре охлаждения Это может привести к разрыву труб или нанесению увечий n При установке прибора надежно подсоедините трубы с хладагентом до запуска компрессора Если компрессор запускается до подсоединения труб с хладаге...

Page 15: ...ега В районах с сильным снегопадом уста новите навес опору и или несколько отражательных перегородок Примечание Рекомендуется сделать трубную петлю рядом с наружным прибором для уменьшения передаваемой оттуда вибрации Примечание При эксплуатации кондиционера при низкой температуре наружно го воздуха обязательно следуйте приведенным ниже инструкциям Запрещается устанавливать наружный прибор в места...

Page 16: ...го прибора Воздухозаборное отверстие Воздуховыпускное отверстие 1 6 ТРУБОПРОВОДЫ ДРЕНАЖНОЙ СИСТЕМЫ НАРУЖНОГО БЛОКА Воздухозаборное отверстие 4 10 21 Овальные отверстия После проверки на отсутствие утечек плотно нанесите изо ляционный материал чтобы обеспечить отсутствие зазоров В случае крепления трубопро водов к стене содержащей ме таллы обшитые белой жестью или металлическую сетку уста новите хи...

Page 17: ...му приборам затем насадите их на трубу после полного удаления заусен цев После развальцовки насадка гаек невозможна 4 Развальцовка Рис 4 5 Полностью соблюдайте размеры медной тру бы указанные в таблице Выберите A мм из таблицы в соответствии с используемым инструментом 5 Проверьте Сравните развальцовку с Рис 6 При обнаружении дефекта на развальцовке обрежьте развальцован ный участок и выполните ра...

Page 18: ...ольного клапана к сервисному порту убедитесь что сердечник кла пана находится в закрытом положении затем затяните часть A Не затягивайте часть A или не поворачивайте кор пус если сердечник клапана находится в открытом поло жении Колпачок сервис ного порта Крутящий момент от 13 7 17 7 Н м 140 180 кгс см 4 5 оборотов Стопорный клапан для ЖИДКОСТИ Манометр давления для R410A 4 2 ЗАПРАВКА ГАЗА Заправь...

Page 19: ...05 0 МПа маном ок 0 5 0 кгс см2 6 Остановите аварийное управление в режиме ОХЛАЖДЕНИЕ COOL Нажмите кнопку E O SW несколько раз пока все светодиодные лампы не погаснут Подробнее см инструкции по эксплуатации ПРЕДУПРЕЖДЕНИЕ При сливании хладагента останавливайте компрессор до отключения труб с хла дагентом Попадание внутрь компрессора воздуха и т п может привести к взрыву 4 6 ПРОБНЫЙ ПРОГОН Тестовый...

Page 20: ......

Page 21: ......

Page 22: ...r ved bruk i boliger samt kommersielle og lettindustrielle miljøer vakuuttaa täten yksinomaisella vastuullaan että jäljempänä kuvatut asuinrakennuksiin pienteollisuuskäyttöön ja kaupalliseen käyttöön tarkoitetut ilmastointilaitteet ja lämpöpumput Note Its serial number is on the nameplate of the product Hinweis Die Seriennummer befindet sich auf dem Kennschild des Produkts Remarque Le numéro de sé...

Reviews: