91
The other cases
• When the operation frequency does not go up from the lowest frequency.
Check of bus-bar voltage
•Check the voltage of power supply.
•Con
fi
rm outdoor unit failure mode
recall function. (Refer to 11-2.2.)
Blink 5 times
Con
fi
rm LED1 indication lamp on the
outdoor control P.C. board.
Replace the outdoor power
P.C. board.
Blink 9 times
Replace the outdoor control
P.C. board.
Turn OFF power supply before removing P.C. board.
Con
fi
rm LED1 indication lamp
on the outdoor control P.C.
board.
Turn ON power supply. Start
operation.
Lighting
Replace the outdoor control
P.C. board.
Blink 9 times
Replace the outdoor power
P.C. board.
Con
fi
rm LED1 indication lamp
on the outdoor control P.C.
board.
Turn ON power supply. Start
operation.
Normal
Lighting
Lighting
Check of HPS
Infinity
No
Yes
1. Disconnect the connector CN63H in the outdoor control P.C. board.
2. Check the resistance of HPS after 1 minute has passed since the outdoor unit power supply was turned OFF.
Check the resistance between each terminal.
Reconnect CN63H.
Turn ON the power supply to the indoor and outdoor unit.
3 minutes later, start EMERGENCY OPERATION.
Is HPS protection displayed immediately
after compressor starts?
Replace HPS.
Replace the outdoor control P.C. board.
Normal
CN63H
Outdoor control
P.C. board
Indoor unit does not operate. (different operating models in multi system)
• When you try to run 2 indoor units simultaneously, one for cooling and the other for heating, the unit which transmits signal to
the outdoor units
fi
rst decides the operation mode.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and then turn them back
ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that the refrigerant gas
continuously
fl
ows into the indoor unit even while it is not operating.
OBH723C
Summary of Contents for MXZ-2E53VAHZ
Page 16: ...16 MXZ 4E83VA Unit mm Air in Air in Air in Air out OBH723C ...
Page 17: ...17 MXZ 5E102VA Unit mm Air in Air in Air in Air out OBH723C ...
Page 18: ...18 Unit mm MXZ 2E53VAHZ OBH723C ...
Page 19: ...19 MXZ 4E83VAHZ Unit mm OBH723C ...
Page 22: ...22 MXZ 4E83VA E1 OBH723C ...
Page 23: ...23 MXZ 4E83VA E2 OBH723C ...
Page 24: ...24 MXZ 4E83VA ET1 OBH723C ...
Page 25: ...25 MXZ 4E83VA ET2 OBH723C ...
Page 26: ...26 MXZ 4E83VA ER1 OBH723C ...
Page 27: ...27 MXZ 5E102VA E1 OBH723C ...
Page 28: ...28 MXZ 5E102VA E2 OBH723C ...
Page 29: ...29 MXZ 5E102VA ET1 OBH723C ...
Page 30: ...30 MXZ 5E102VA ET2 OBH723C ...
Page 31: ...31 MXZ 5E102VA ER1 OBH723C ...
Page 32: ...32 MXZ 2E53VAHZ E1 OBH723C ...
Page 33: ...33 MXZ 2E53VAHZ ER1 OBH723C ...
Page 34: ...34 MXZ 4E83VAHZ E1 OBH723C ...
Page 35: ...35 MXZ 4E83VAHZ ER1 OBH723C ...