3. Outdoor unit failure mode table
The left lamp of
OPERATION IN-
DICATOR lamp
(Indoor unit)
Abnormal point
(Failure mode/protection)
LED indication
(Outdoor P.C.
board)
Condition
Remedy
Indoor/
outdoor unit
failure mode
recall function
LED1
LED2
OFF
None (Normal)
Lighted Lighted
2-time
fl
ash
Outdoor power system
Lighted Lighted Overcurrent protection cut-out operates 3 con-
secutive times within 1 minute after the com-
pressor gets started, or converter protection
cut-out or bus-bar voltage protection cut-out
operates 3 consecutive times within 3 minutes
after start-up.
• Check the connection of the com-
pressor connecting wire.
• Refer to 11-6.
"How to check inverter/compres-
sor".
• Check the stop valve.
○
3-time
fl
ash
Discharge temperature thermistor
Lighted
Once
A thermistor shorts or opens during
compressor running.
• Refer to 11-6. "Check of outdoor
thermistors".
○
Defrost thermistor
Lighted
Once
Ambient temperature thermistor
Lighted
Twice
Fin temperature thermistor
Lighted 3 times
P.C. board temperature thermis-
tor
Lighted 4 times
• Replace the outdoor control P.C.
board.
Outdoor heat exchanger tem-
perature thermistor
Lighted 9 times
• Refer to 11-6. "Check of outdoor
thermistors".
4-time
fl
ash
Overcurrent
Once
Not
lighted
21 A current
fl
ows into power module.
• Reconnect compressor connector.
• Refer to 11-6. "How to check in-
verter/compressor".
• Check the stop valve.
—
5-time
fl
ash
Discharge temperature
Lighted Lighted The discharge temperature exceeds 115°C
(
MXZ-3E54/3E68/4E72VA
)/ 106°C(
MXZ-
4E83/5E102VA, MXZ-2E52VAHZ
)/ 116°C
(
MXZ-4E83VAHZ
) during operation.
Compressor can restart if discharge tem-
perature thermistor reads 80°C (
MXZ-
3 E 5 4 / 3 E 6 8 / 4 E 7 2 V A
) / 9 5 ° C (
M X Z -
4E83/5E102VA, MXZ-2E52VAHZ
)/100°C
(
MXZ-4E83VAHZ
) or less 3 minutes later.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6. "Check of LEV".
—
6-time
fl
ash
High pressure
Lighted Lighted The outdoor heat exchanger temperature ex-
ceeds 70°C during cooling or the indoor gas pipe
temperature exceeds 70°C during heating.
• Check refrigerant circuit and refrig-
erant amount.
• Check the stop valve.
—
7-time
fl
ash
Fin temperature
3 times
Not
lighted
The fin temperature exceeds 88°C (
MXZ-
3E54/3E68/4E72/4E83/5E102VA, MXZ-
2E52VAHZ
)/89°C (
MXZ-4E83VAHZ
) during
operation.
• Check around outdoor unit.
• Check outdoor unit air passage.
• Refer to 11-6. "Check of outdoor
fan motor".
—
P.C. board temperature
4 times
Not
lighted
The P.C. board temperature exceeds 67°C
(
MXZ-3E54/3E68/4E72/4E83/5E102VA, MXZ-
2E52VAHZ
)/87°C (
MXZ-4E83VAHZ
) during
operation.
8-time
fl
ash
Outdoor fan motor
Lighted Lighted A failure occurs 3 consecutive times within 30
seconds after the fan gets started.
• Refer to 11-6. "Check of outdoor
fan motor".
—
9-time
fl
ash
Outdoor control system
Lighted 5 times Nonvolatile memory data cannot be read prop-
erly.
• Replace the outdoor control P.C. board.
○
10-time
fl
ash
Low discharge temperature
protection
Lighted Lighted The frequency of the compressor is kept 80 Hz
or more and the discharge temperature is kept
under 39°C for more than 20 minutes.
• Check refrigerant circuit and refrig-
erant amount.
• Refer to 11-6. "Check of LEV".
—
11-time
fl
ash
Communication error
between P.C. boards
Lighted 6 times Communication error occurs between the out-
door control P.C. board and outdoor power P.C.
board for more than 10 seconds.
• Check the connecting wire between
outdoor control P.C. board and out-
door power P.C. board.
—
The communication between boards protec-
tion cut-out operates 2 consecutive times.
○
Current sensor
Lighted 7 times A short or open circuit is detected in the cur-
rent sensor during compressor operating.
—
—
Current sensor protection cut-out operates 2
consecutive times.
○
Zero cross detecting circuit
5 times
Not
lighted
Zero cross signal cannot be detected while the
compressor is operating.
• Check the connecting wire among
outdoor control P.C. board and out-
door power P.C. board.
—
The protection cut-out of the zero cross
detecting circuit operates 10 consecutive
times.
○
Converter
5 times
Not
lighted
A failure is detected in the operation of the
converter during operation.
• Check the voltage of power supply.
• Replace the outdoor power P.C.
board.
—
Bus-bar voltage
5 times
Not
lighted
The bus-bar voltage exceeds 400 V or falls to
low level during compressor operating.
• Check the voltage of power supply.
• Replace the outdoor control P.C.
board.
15-time
fl
ash
LEV and drain pump
Lighted Lighted The indoor unit detects an abnormality in
the LEV and drain pump.
• Refer to 11-6. "Check of LEV".
• Check the drain pump of the indoor
unit.
—
NOTE
: Blinking patterns of this mode differ from the ones of Troubleshooting check table (11-4.).
OBH723C
Summary of Contents for MXZ-2E53VAHZ
Page 16: ...16 MXZ 4E83VA Unit mm Air in Air in Air in Air out OBH723C ...
Page 17: ...17 MXZ 5E102VA Unit mm Air in Air in Air in Air out OBH723C ...
Page 18: ...18 Unit mm MXZ 2E53VAHZ OBH723C ...
Page 19: ...19 MXZ 4E83VAHZ Unit mm OBH723C ...
Page 22: ...22 MXZ 4E83VA E1 OBH723C ...
Page 23: ...23 MXZ 4E83VA E2 OBH723C ...
Page 24: ...24 MXZ 4E83VA ET1 OBH723C ...
Page 25: ...25 MXZ 4E83VA ET2 OBH723C ...
Page 26: ...26 MXZ 4E83VA ER1 OBH723C ...
Page 27: ...27 MXZ 5E102VA E1 OBH723C ...
Page 28: ...28 MXZ 5E102VA E2 OBH723C ...
Page 29: ...29 MXZ 5E102VA ET1 OBH723C ...
Page 30: ...30 MXZ 5E102VA ET2 OBH723C ...
Page 31: ...31 MXZ 5E102VA ER1 OBH723C ...
Page 32: ...32 MXZ 2E53VAHZ E1 OBH723C ...
Page 33: ...33 MXZ 2E53VAHZ ER1 OBH723C ...
Page 34: ...34 MXZ 4E83VAHZ E1 OBH723C ...
Page 35: ...35 MXZ 4E83VAHZ ER1 OBH723C ...