48
No.
Symptom
LED indication
Abnormal point/ Con-
dition
Condition
Remedy
21
Outdoor unit
operates.
7-time blink
2.5 seconds OFF
Low discharge tem-
perature protection
Temperature of discharge temperature thermistor has been
50°C or less for 20 minutes.
• Refer to 12-5. "Check of LEV".
• Check refrigerant circuit and refrig-
erant amount.
22
8-time blink
2.5 seconds OFF
MUZ-
AP25/35/42/50/60
PAM protection
PAM: Pulse Ampli-
tude Modulation
The overcurrent flows into PFC (Power factor correction:
IC820) or the bus-bar voltage reaches 394 V or more, PAM
stops and restarts.
This is not malfunction. PAM pro-
tection will be activated in the fol-
lowing cases:
1 Instantaneous power voltage
drop. (Short time power failure)
2 When the power supply voltage
is high.
MUZ-AP71
Zero cross detecting
circuit
Zero cross signal cannot be detected.
• It occurs with following cases.
1 Instantaneous power voltage
drop. (Short time power failure)
2 Distortion of primary voltage
• Refer to 12-5. "Check of power
supply".
23
9-time blink
2.5 seconds OFF
Inverter check mode The connector of compressor is disconnected, inverter check
mode starts.
• Check if the connector of the com-
pressor is correctly connected.
Refer to 12-5. "How to check
inverter/compressor".
NOTE:
1. The location of LED is illustrated at the right figure. Refer to 12-6.1.
2. LED is lighted during normal operation.
The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the blinking frequency is “2”.
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
LED
Blinking →
MUZ-AP25/35/42/50/60VG
MUZ-AP25/35/42/50VGH
Inverter P.C. board
MUZ-AP71VG
LED
→
Blinking
OBH789A
Summary of Contents for MUZ-AP25VG
Page 12: ...12 Unit mm MUZ AP50VG MUZ AP60VG MUZ AP50VGH MUZ AP50VG H MUZ AP60VG OBH789A ...
Page 15: ...15 MUZ AP42VG E1 ET1 E2 ET2 ER2 MUZ AP42VGH E1 E2 OBH789A ...
Page 16: ...16 MUZ AP50VG E1 ET1 MUZ AP50VGH E1 OBH789A ...
Page 17: ...17 MUZ AP60VG E1 ET1 MUZ AP71VG E1 ET1 OBH789A ...
Page 76: ......