36
OPERATION INDICATOR
Lit
Blinking
Not lit
No.
Abnormal
point
Operation indicator lamp
Symptom
Condition
Remedy
1
MXZ type
Operation
mode
setting
Upper lamp lights and lower lamp blinks.
2.5-second OFF
Outdoor unit
operates but
indoor unit does
not operate.
The operation mode of the each indoor unit is
differently set to COOL (includes DRY) and
HEAT at the same time, the operation mode of
the indoor unit that has operated at first has
the priority.
• Unify the operation mode.
Refer to outdoor unit service
manual.
10-5. TROUBLESHOOTING CRITERION OF MAIN PARTS
Part name
Check method and criterion
Figure
Room temperature
thermistor (RT11)
Indoor coil thermistor
(RT12, RT13)
Measure the resistance with a multimeter.
Refer to 10-7. “Test point diagram and voltage”, “Indoor electronic control
P.C. board”, for the chart of thermistor.
Indoor fan motor (MF)
Check 10-6. “Check of indoor fan motor”.
Vane motor (MV1)
(Horizontal Upper)
Measure the resistance between the terminals with a multimeter.
(Temperature: 10 to 30°C)
Color of the lead wire
Normal
RED - SKY*
262 - 328 Ω
SKY
SKY
RED
SKY
SKY
Vane motor (MV2)
(Horizontal Lower)
Measure the resistance between the terminals with a multimeter.
(Temperature: 10 to 30°C)
Color of the lead wire
Normal
RED - SKY*
257 - 333 Ω
Vane motor (MV3)
(Vertical)
Measure the resistance between the terminals with a multimeter.
(Temperature: 10 to 30°C)
Color of the lead wire
Normal
RED - SKY*
219 - 273 Ω
AIR PURIFYING power
Check 10-6. .
*SKY = SKY BLUE
OPERATION INDICATOR
Lit
Blinking
Not lit
No.
Abnormal
point
Operation indicator lamp
Symptom
Condition
Remedy
1
AIR
PURIFYING
power
control
AIR PURIFYING lamp blinks.
2.5-second OFF
Indoor unit and
outdoor unit do
not operate.
When AIR PURIFYING power cannot be
turned OFF even if the AIR PURIFYING
operation is turned OFF by remote controller.
• Refer to 10-6. “Check of AIR
PURIFYING power”.
OBH932