57
M How to check miswiring and serial signal error
• Turn OFF inverter-controlled lighting
equipment.
• Turn OFF the power supply and then
turn ON again.
• Press EMERGENCY OPERATION
switch.
A
Is serial signal
error indicated 6
minutes later?
B
Yes
• Reinstall
either the unit
or the light
away from
each other.
•
Attach a filter
on remote
control receiv-
ing section
of the indoor
unit.
No
Turn OFF the power supply.
Is there rated voltage in the power supply?
Yes
No
Turn ON the power supply.
Check the power supply.
Is there rated voltage between the outdoor terminal block S1 and S2?
No
Check the wiring.
Press EMERGENCY OPERATION switch once.
Does the left lamp of OPERATION INDICATOR
lamp light up? <Confirmation of the power to
the indoor unit>
Yes
No
Is serial signal error indicated 6 minutes later?
Yes
No
Is there any miswiring,
poor contact, or wire
disconnection of the
indoor/outdoor connect-
ing wire?
Yes Correct them.
No
A
Turn OFF the power supply.
Check once more if the indoor/outdoor
connecting wire is not miswiring.
Bridge the outdoor terminal block S2 and
S3. *1
B
*
1. Miswiring may damage indoor electronic control P.C.
board during the operation.
Be sure to confirm the wiring is correct before the opera
-
tion starts.
Turn ON the power supply.
Does the LED on the inverter P.C. board repeat
"3.6-second-OFF and 0.8-second-ON quick blinking"? *3
Yes
No
(Lit or
not lit)
Replace the inverter P.C. board . *2
*
2. Be careful of the residual voltage of smoothing
capacitor.
Is there amplitude of 10 to 20 V DC between the indoor terminal block
S2 and S3? <Confirmation of serial signal>
Yes
Check the wiring
If there are any error of the indoor/outdoor connecting wire:
such as the damage of the wire, intermediate connection,
and/or poor contact to the terminal block, replace the indoor/
outdoor connecting wire.
No
Is there 2 V DC or less between CN202 (+)
and JPG (GND)(-) on the indoor electronic
control P.C. board?
No
Yes
Yes
*
3. Be sure to check this within 3 minutes after turning ON.
After 3 minutes, LED blinks 6 times. Even when the
inverter P.C. board is normal, LED blinks 6 times after 3
minutes.
Is there 2 V DC or less between
CN202 (+) and JPG (GND)(-) on
the indoor electronic control P.C.
board?
Is there 2 V DC or less between
CN202A (+) and JPG (GND)(-)
on the indoor electronic control P.C.
board?
Replace the indoor elec-
tronic control P.C. board.
No
Yes
No
Yes
Is the bus-bar voltage of the inverter P.C. board normal?
(Refer to "TEST POINT DIAGRAM AND VOLTAGE" in the outdoor service manual.)
No
Yes
Check of power supply.
Turn OFF the power supply.
Remove the bridge between the outdoor terminal block S2 and S3.
Turn ON the power supply.
Yes
No
Replace the indoor power
P.C. board.
Is there rated voltage between the indoor terminal block S1 and S2?
<Confirmation of power voltage>
MUZ-GL09/12/15NA
MUZ-GL09/12/15NAH
MUY-GL09/12/15NA
OBH733J
Summary of Contents for MSY-GL-NA Series
Page 9: ...9 5 WIRING DIAGRAM MUZ GL09NA U1 U8 MUZ GL12NA U1 MUZ GL09NA U2 MUZ GL12NA U2 OBH733J ...
Page 10: ...10 MUZ GL09NAH U2 MUZ GL12NAH U2 MUZ GL09NAH U1 U8 MUZ GL12NAH U1 OBH733J ...
Page 11: ...11 MUY GL09NA U1 MUY GL12NA U1 MUY GL09NA U2 MUY GL12NA U2 OBH733J ...
Page 12: ...12 MUZ GL15NA U2 MUZ GL15NA U1 OBH733J ...
Page 13: ...13 MUZ GL15NAH U2 MUZ GL15NAH U1 OBH733J ...
Page 14: ...14 MUY GL15NA U1 MUY GL15NA U2 OBH733J ...
Page 15: ...15 MUZ GL18NA OBH733J ...
Page 16: ...16 MUZ GL18NAH OBH733J ...
Page 17: ...17 MUY GL18NA OBH733J ...
Page 18: ...18 MUZ GL24NA OBH733J ...
Page 19: ...19 MUZ GL24NAH OBH733J ...
Page 20: ...20 MUY GL24NA OBH733J ...
Page 75: ...75 OBH733J ...