52
H Check of R.V. coil
MUZ-GL09/12/15/18NA MUZ-GL09/12/15/18NAH
(MUZ)
MUZ-GL24NA MUZ-GL24NAH
* First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.
* In case CN721 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN721 is connected.
Is there 208/230 V AC between CN721
and on the inverter P.C. board
3 minutes after the power supply is turned
ON?
No
Yes
Replace the inverter
P.C. board.
Replace the 4-way valve.
Unit operates in COOL mode even if it is set to HEAT mode.
Is there 208/230 V AC between CN721
and on the inverter P.C. board
3 minutes after the power supply is turned
ON?
Yes
No
Replace the inverter
P.C. board.
Replace the 4-way valve.
Unit operates in HEAT mode even if it is set to COOL mode.
Disconnect connector between the
compressor and the power module
(IC700).
Turn ON the power supply and press
EMERGENCY OPERATION switch
twice (HEAT mode).
Disconnect connector between the
compressor and the power module
(IC700).
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
* First of all, measure the resistance of R.V. coil to check if the coil is defective. Refer to 10-4.
* In case CN602 is disconnected or R.V. coil is open, voltage is generated between the terminal pins of the connector
although no signal is being transmitted to R.V. coil.
Check if CN602 is connected.
Is there 208/230 V AC between CN602
and on the inverter P.C. board
3 minutes after the power supply is turned
ON?
No
Yes
Replace the inverter
P.C. board.
Replace the 4-way valve.
Unit operates in COOL mode even if it is set to HEAT mode.
Is there 208/230 V AC between CN602
and on the inverter P.C. board
3 minutes after the power supply is turned
ON?
Yes
No
Replace the inverter
P.C. board.
Replace the 4-way valve.
Unit operates in HEAT mode even if it is set to COOL mode.
Disconnect connector between the
compressor and the IGBT module
(IC700).
Turn ON the power supply and press
EMERGENCY OPERATION switch
twice (HEAT mode).
Disconnect connector between the
compressor and the IGBT module
(IC700).
Turn ON the power supply and
press EMERGENCY OPERATION
switch once (COOL mode).
OBH733J
Summary of Contents for MSY-GL-NA Series
Page 9: ...9 5 WIRING DIAGRAM MUZ GL09NA U1 U8 MUZ GL12NA U1 MUZ GL09NA U2 MUZ GL12NA U2 OBH733J ...
Page 10: ...10 MUZ GL09NAH U2 MUZ GL12NAH U2 MUZ GL09NAH U1 U8 MUZ GL12NAH U1 OBH733J ...
Page 11: ...11 MUY GL09NA U1 MUY GL12NA U1 MUY GL09NA U2 MUY GL12NA U2 OBH733J ...
Page 12: ...12 MUZ GL15NA U2 MUZ GL15NA U1 OBH733J ...
Page 13: ...13 MUZ GL15NAH U2 MUZ GL15NAH U1 OBH733J ...
Page 14: ...14 MUY GL15NA U1 MUY GL15NA U2 OBH733J ...
Page 15: ...15 MUZ GL18NA OBH733J ...
Page 16: ...16 MUZ GL18NAH OBH733J ...
Page 17: ...17 MUY GL18NA OBH733J ...
Page 18: ...18 MUZ GL24NA OBH733J ...
Page 19: ...19 MUZ GL24NAH OBH733J ...
Page 20: ...20 MUY GL24NA OBH733J ...
Page 75: ...75 OBH733J ...