2
Use the specified refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by
failure to follow the instructions.
Revision A:
• MUZ-GL12/15NA-
U1
, MUZ-GL12/15NAH-
U1
and MUY-GL09/12/15NA-
U1
have been added.
Revision B:
• MUZ-GL09NA-
U8
and MUZ-GL09NAH-
U8
have been added.
Revision C:
• MUZ-GL09NA-
U1
and MUZ-GL09NAH-
U1
have been added.
Revision D:
• MUZ-GL24NAH-
U1
has been added.
Revision E:
• Capacity corrections have been corrected [7-1. 2), 3)].
Revision F:
• MUZ-GL24NA-
U2
has been added.
Revision G:
• MUZ-GL09/12/15NA-
U2
, MUZ-GL09/12/15NAH-
U2
and MUY-GL09/12/15NA-
U2
have been added.
Revision H:
• 10-6. Voltage values of MUZ-GL09/12/15NA-
U2
, MUZ-GL09/12/15NAH-
U2
and MUY-GL09/12/15NA-
U2
have been corrected.
<Preparation before the repair service>
Prepare the proper tools.
Prepare the proper protectors.
Provide adequate ventilation.
After stopping the operation of the air conditioner, turn off the power-supply breaker and pull the power plug.
Discharge the capacitor before the work involving the electric parts.
<Precautions during the repair service>
Do not perform the work involving the electric parts with wet hands.
Do not pour water into the electric parts.
Do not touch the refrigerant.
Do not touch the hot or cold areas in the refrigeration cycle.
When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.
WARNING
• When the refrigeration circuit has a leak, do not execute pump down with the
compressor.
• When pumping down the refrigerant, stop the compressor before disconnecting the
refrigerant pipes. The compressor may burst if air etc. get into it.
• When opening or closing the valve below freezing temperatures, refrigerant may
spurt out from the gap between the valve stem and the valve body, resulting in injuries.
Revision J:
• A warning when opening or closing the valve has been added.
OBH733J
Summary of Contents for MSY-GL-NA Series
Page 9: ...9 5 WIRING DIAGRAM MUZ GL09NA U1 U8 MUZ GL12NA U1 MUZ GL09NA U2 MUZ GL12NA U2 OBH733J ...
Page 10: ...10 MUZ GL09NAH U2 MUZ GL12NAH U2 MUZ GL09NAH U1 U8 MUZ GL12NAH U1 OBH733J ...
Page 11: ...11 MUY GL09NA U1 MUY GL12NA U1 MUY GL09NA U2 MUY GL12NA U2 OBH733J ...
Page 12: ...12 MUZ GL15NA U2 MUZ GL15NA U1 OBH733J ...
Page 13: ...13 MUZ GL15NAH U2 MUZ GL15NAH U1 OBH733J ...
Page 14: ...14 MUY GL15NA U1 MUY GL15NA U2 OBH733J ...
Page 15: ...15 MUZ GL18NA OBH733J ...
Page 16: ...16 MUZ GL18NAH OBH733J ...
Page 17: ...17 MUY GL18NA OBH733J ...
Page 18: ...18 MUZ GL24NA OBH733J ...
Page 19: ...19 MUZ GL24NAH OBH733J ...
Page 20: ...20 MUY GL24NA OBH733J ...
Page 75: ...75 OBH733J ...