21
2. Maximum/minimum frequency in each operation mode
Applied model
Operational frequency (Hz)
COOL HEAT DRY
Minimum
Maximum
Minimum
Maximum
Minimum
Maximum
MUZ-GC25
32
85
28
105
32
41
MUZ-GC35
32
98
48
105
32
58
MUZ-HC25
28
85
28
105
28
41
MUZ-HC35
28
98
28
98
28
41
MUZ-FD25
10
52
18
90
28
41
MUZ-FD35VA
10
62
18
90
28
41
MUZ-FD35VAH/VABH
10
62
18
115
28
41
MUZ-FD50
20
85
20
130
20
45
MUZ-GE25
24
93
32
105
38
48
MUZ-GE35
20
98
32
98
38
55
MUZ-GE42
10
90
18
115
35
54
MUZ-GE50
20
98
20
108
20
98
MUZ-GE60
20
104
30
117
20
104
MUZ-GE71
26
120
26
124
26
120
MUZ-EF25
28
93
30
105
28
48
MUZ-EF35
20
98
30
98
20
55
MUZ-EF42
10
90
18
100
10
54
MUZ-EF50
20
98
20
108
20
83
The operation frequency in COOL mode is restricted by the upper limit frequency after 0.5 - 1 hour as shown below for
dew prevention. It is rated frequency or less.
Maximum
frequency
0.5 - 1 hour
Upper limit
frequency
Rated frequency or less
Time
2-10. PRE-HEAT CONTROL
1. Outline
Compressor is energized to improve the start-up of compressor at a low outside temperature even when compressor
is stopped.
2. Pre-heat control
MUZ-GC/HC/FD/GE
30 minutes 1 hour
ON
ON
OFF
OFF
20 °C
Compressor
Pre-heat control
Defrost thermistor
Pre-heat control ON condition
(1) Compressor is not operating. (However, pre-heat control is still OFF for 30 minutes after compressor is stopped,
regardless of the outside temperature.)
(2) Defrost thermistor reads 20°C or below.
Defrost thermistor monitor hourly, and when defrost thermistor reads 20°C or below, pre-heat control is turned ON.
When pre-heat control is turned ON, compressor is energized about 50 W (40-60 W). (Compressor and fan are not operated.)