23
In COOL operation, the two indoor coil
thermistors (one main and one sub) sense
temperature ununiformity (super heat)
at the heat exchanger, and when tem-
perature difference have developed, the
indoor coil thermistors adjust LEV open-
ing degree to get approximate 10°C lower
temperature than the target discharge
temperature in the table on the left, thus
diminishing super heat.
(3) Control data
Reference value of target discharge temperature (COOL/HEAT °C)
Applied model
A
B
C
D
E
F
MUZ-GC25
54/36 59/46 65/55 70/63 75/70 79/76
MUZ-
HC35VA(B)-
E2
52/46
57/50
64/55
70/64
74/73
74/73
MUZ-GC35
51/42 57/50 62/58 67/65 71/70 71/70
MUZ-FD25/35
MUZ-GE42
49/43 55/51 61/59 67/69 72/75 76/80
MUZ-FD50
45/51
58/59
65/65
72/72
72/72
72/72
MUZ-GE25
52/43
58/50
65/55
67/59
70/65
71/69
MUZ-GE35
53/43
60/51
64/58
67/59
72/69
76/75
MUZ-GE50
57/60
60/65
62/70
67/75
74/75
81/75
MUZ-GE60
49/42
53/49
59/58
64/67
69/75
74/83
MUZ-GE71
55/46
61/56
66/66
72/75
77/83
81/86
MUZ-EF25
52/43
58/50
65/55
67/59
70/65
71/69
MUZ-EF35
53/43
60/51
64/58
67/59
72/69
76/75
MUZ-EF42
49/43
55/51
61/59
67/69
72/75
76/80
MUZ-EF50
49/42
53/49
59/58
64/67
69/75
74/83
F
E
D
C
B
A
T
arget discharge
temperature
30
50
70
Operational frequency of the compressor (Hz)
90
110
130
23
38
53
69
84
99
(
GE60/71
)
(
Other models
)
2-12. STANDBY POWER CONTROL
MUZ-EF
(1) Outline
This control allows the power consumption in the standby mode to be maintained at 1 W or less. The control is ena-
bled from the moment the main power is turned on until the operation starts. About 10 minutes later after the opera-
tion stops, the control becomes enabled again until the main power is turned off.
(2) Standby power control time chart
[e.g.] Remote controller
ON
[e.g.] Remote controller
OFF
[e.g.] Remote controller
ON
Main power
ON
Operarion
Standby
power control
Disabled
Enabled
About 10 minutes
1 W or less
1 W or less
ON
OFF