5. Electrical work
5.1. Connecting wires for outdoor unit
1) Remove the service panel.
) Remove the conduit cover.
3) Attach the conduit connector to conduit plate with lock nut then secure it against
unit with screws.
4) Connect ground wires of indoor/outdoor unit connecting wire (A) and power sup-
ply cord (K) to the TB support.
5) Loosen the terminal screw, and attach indoor/outdoor unit connecting wire (A)
from the indoor unit correctly on the terminal block. Attach the wire to the termi-
nal block securely so that its core cannot be seen, and no external force affects
the connecting section of the terminal block.
6) Firmly tighten the terminal screws. After tightening, verify that the wires are
tightly fastened.
7) Connect power supply cord (K).
8) Install the conduit cover.
9) Install the service panel securely.
Lead wire
Power supply cord (K)
L1 L2
1-3/8 in.
(35 mm)
19/32 in.
(15 mm)
Terminal block
Conduit cover
Power supply cord (K)
Indoor/outdoor unit
connecting wire (A)
• Make earth wire a little longer than others.
(More than 2-3/8 in. [60 mm])
• For future servicing, leave some slack in
the connecting wires.
Service panel
Lock nut
Conduit cover
Conduit plate
Connector
Grounding
terminal
TB support
Terminal block
to conduit cover
Power supply cord (K)
Indoor/outdoor unit
connecting wire (A)
Service panel
Lock nut
Conduit cover
Connector
TB support
Grounding
terminal
INDOOR UNIT
Terminal block
208/230 V AC
1phase, 60 Hz
Grounding
terminal**
Disconnect
switch*
OUTDOOR UNIT
Grounding terminal**
Ground
Power supply
208/230 V AC,
1phase 2wires.
60 Hz
Terminal bloc
k1
Remark:
* A disconnect switch is
required.
Check the local code.
** Use a ring tongue termi-
nal in order to connect a
ground wire to terminal.
Termina
lbloc
k2
SUZ-KA09, KA12, KA15NA
SUZ-KA18NA
• Connect the cable from the indoor unit correctly on the terminal-block.
• Use the same terminal block and polarity as is used with the indoor unit.
• For aftercare maintenance, give extra length to connecting cable.
• Both ends of connecting cable (extension wire) are peeled off. When too long,
or connected by cutting off the middle, peel off power supply cable to the size
given in the figure.
• Be careful not to contact connecting cable with piping.
Caution:
• Use care not to make miswiring.
• Firmly tighten the terminal screws to prevent them from loosening.
• After tightening, pull the wires lightly to confirm that they do not move.
Warning:
• Be sure to attach the service panel of the indoor unit securely. If it is not
attached correctly, it could result in a fire or an electric shock due to dust,
water, etc.
• Tighten terminal screws securely.
• Wiring should be done so that the power lines are not subject to tension.
Otherwise, heat may be generated or fire may occur.