background image

Contents

1.  The following should always be observed for safety  . . . . . . . . . . . . . . . . . . . .  

.  Selecting the installation location  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3

3.  Installation diagram  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  3

4.  Refrigerant piping work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  4

5.  Electrical work  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  6

6.  Maintenance   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7

1. The following should always be observed for safety

 Caution:

Could lead to serious injury when operated incorrectly.

•  After reading this manual, be sure to keep it together with the instruction 

manual in a handy place on the customer’s site.

 : Indicates a part which must be grounded.

 Warning:

Carefully read the labels affixed to the main unit.

 Warning:

  Do not install the unit by yourself (user).

Improper or incomplete installation could cause fire, electric shock, injury due to 

the unit falling, or water leakage. Consult a qualified installer or the dealer from 

whom you purchased the unit.

  Follow the instructions detailed in the installation manual.

Incomplete installation could cause fire or electric shock, injury due to the unit 

falling, or leakage of water.

  Install the unit securely in a place that can bear the weight of the unit.

If the installation location cannot bear the weight of the unit, the unit could fall 

causing injury.

  Perform electrical work according to the installation manual and be sure to 

use an exclusive circuit. Do not connect other electrical appliances to the 

circuit.

If the capacity of the power circuit is insufficient or there is incomplete electrical 

work, it could result in a fire or an electric shock.

  Ground the unit correctly.

Do not connect the ground wire to a gas pipe, water pipe, lightning rod or tele-

phone ground. Defective grounding could cause electric shock.

  Do not damage the wires.

Damaged wires could cause fire.

  Be sure to shut off the main power when setting up the indoor P.C. board 

or wiring.

Failure to do so could cause electric shock.

  Use the specified wires to securely connect the indoor and outdoor units. 

Attach the wires firmly to avoid applying stress to the terminal block.

Improper connection could cause fire.

  Do not install the unit in a place where flammable gas may leak.

If gas leaks and accumulates around the unit, it could cause an explosion.

  Do not use intermediate connection of the power cord or the extension 

cord. Do not connect many devices to one AC outlet.

It could cause a fire or an electric shock.

  Use the parts provided or specified parts for the installation work.

The use of defective parts could cause an injury or leakage of water due to a 

fire, an electric shock, the unit falling, etc.

  Securely attach the electrical cover to the indoor unit and the service panel 

to the outdoor unit.

If the electrical cover of the indoor unit and/or the service panel of the outdoor 

unit are not attached securely, dust, water, etc. could collect in the unit and could 

cause a fire or an electric shock.

  When installing or relocating the unit, make sure that no substance other 

than the specified refrigerant (R410A) enters the refrigerant circuit.

Any foreign substances in the refrigerant circuit can cause abnormal pressure 

rise or an explosion.

  Do not discharge the refrigerant into the atmosphere. Check that the refrig-

erant gas does not leak after installation has been completed. If refrigerant 

leaks during installation, ventilate the room.

If refrigerant comes in contact with a fire, harmful gas could be generated.

If refrigerant gas leaks indoors, and comes into contact with the flame of a fan 

heater, space heater, stove, etc., harmful gases will be generated.

  Use appropriate tools and piping materials for installation.

The pressure of R410A is 1.6 times higher than R. Not using the appropriate 

tools and materials, or improper installation could cause the pipes to burst caus-

ing an injury.

  When pumping down the refrigerant, stop the compressor before discon-

necting the refrigerant pipes.

If the refrigerant pipes are disconnected while the compressor is running and the 

stop valve is open, air could be drawn in and the pressure in the refrigeration 

cycle could become abnormally high, causing the pipes to burst.

  When installing the unit, securely connect the refrigerant pipes before 

starting the compressor.

If the compressor is started before the refrigerant pipes are connected and the 

stop valve is open, air could be drawn in and the pressure in the refrigeration 

cycle could become abnormally high, causing the pipes to burst.

  Fasten a flare nut with a torque wrench as specified in this manual.

If fastened too tight, a flare nut could break and cause refrigerant leakage.

  Install the unit according to national wiring regulations.

 Caution:

  Depending on the installation area, install a Ground Fault Interrupt (GFI) 

circuit breaker.

If the Ground Fault Interrupt (GFI) circuit breaker is not installed, an electric 

shock could occur.

  Perform the drainage/piping work securely according to the installation 

manual.

If there is defect in the drainage/piping work, water could drip from the unit, and 

damage household items.

•  Please provide an exclusive circuit for the air conditioner and do not con

-

nect other electrical appliances to it.

•  Be sure to read “The following should always be observed for safety” be-

fore installing the air conditioner.

•  Be sure to observe the cautions specified here as they include important 

items related to safety.

•  The indications and meanings are as follows.

 Warning:

Could lead to death or serious injury.

  Do not touch the air inlet or the aluminum fins of the outdoor unit.

This could cause injury.

  Do not install the outdoor unit where small animals may live.

If small animals enter the unit and damage its electrical parts, it could cause a 

malfunction, smoke emission, or fire. Keep the area around the unit clean.

Summary of Contents for Mr.SLIM SUZ-KA09NA

Page 1: ...talling the air conditioner unit MANUEL D INSTALLATION Avant d installer le climatiseur lire attentivement ce manuel ainsi que le manuel d installation de l appareil intérieur pour une utilisation sûre et correcte MANUAL DE INSTALACIÓN Para un uso correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado Fran...

Page 2: ...t in the unit and could cause a fire or an electric shock When installing or relocating the unit make sure that no substance other than the specified refrigerant R410A enters the refrigerant circuit Any foreign substances in the refrigerant circuit can cause abnormal pressure rise or an explosion Do not discharge the refrigerant into the atmosphere Check that the refrig erant gas does not leak aft...

Page 3: ...ct the in stallation place to ensure to prevent the outdoor unit and or the grounds from being wet by drain water or damaged by frozen drain water 2 Selecting the installation location Open 2 sides of left right or rear side 4 in 100 mm or more 14 in 350 mm or more 8 in 200 mm or more Basically open 4 in 100 mm or more without any obstruction in front and on both sides of the unit 4 in 100 mm or m...

Page 4: ...0 mm or more Caution Be sure to use the insulation of specified thickness table on the above Excessive insulation may cause incorrect installation of the indoor unit and too little insulation may cause condensate to form The unit has flared connections on both indoor and outdoor sides Remove the valve cover from the outdoor unit then connect the pipe Refrigerant pipes are used to connect the indoo...

Page 5: ...16 6 5 8 15 88 49 64 25 32 19 3 19 7 Fig 4 4 4 4 Purging procedures and leak test 1 Remove service port cap of stop valve on the side of the outdoor unit gas pipe 2 Connect gauge manifold valve and vacuum pump to service port of stop valve on the gas pipe side of the outdoor unit 3 Run the vacuum pump 15 minutes or more 4 Check the vacuum with the gauge manifold valve then close it and shut off th...

Page 6: ...oor outdoor unit connecting wire A Service panel Lock nut Conduit cover Connector TB support Grounding terminal INDOOR UNIT Terminal block 208 230 V AC 1phase 60 Hz Grounding terminal Disconnect switch OUTDOOR UNIT Grounding terminal Ground Power supply 208 230 V AC 1phase 2wires 60 Hz Terminal block 1 Remark A disconnect switch is required Check the local code Use a ring tongue termi nal in order...

Page 7: ...ith the applicable local and national code 2 Use copper supply wires 3 Use wires rated 600V or more for the power supply cables and the indoor outdoor unit connecting cables 4 Install an earth longer than other cables 6 1 Gas charge Fig 6 1 1 Connect gas cylinder to the service port of stop valve 3 way 2 Execute air purge of the pipe or hose coming from refrigerant gas cylinder 3 Replenish specifi...

Page 8: ...ité veillez à ce qu aucune autre substance que le réfrigérant spécifié R410A ne pénètre dans le cir cuit de réfrigération La présence d une substance étrangère dans le circuit de réfrigération peut pro voquer une augmentation anormale de la pression voire une explosion Ne libérez pas le réfrigérant dans l atmosphère Vérifiez l absence de fuites de gaz réfrigérant une fois l installation terminée E...

Page 9: ...viter à l unité extérieure et ou aux sols d être mouillés par les condensats ou endommagés par le gel des condensats 2 Choisir l emplacement de l installation 4 pouce 100 mm minimum 14 pouce 350 mm minimum 8 pouce 200 mm minimum 4 pouce 100 mm minimum m m Unité Unité pouce 31 1 2 19 11 16 Entrée d air 13 9 16 11 1 4 2 3 8 13 16 12 12 3 4 1 9 16 800 500 2 10 21 344 5 285 150 40 304 325 5 15 16 m m ...

Page 10: ...doit être de 4 pouce 100 mm minimum Attention Utilisez toujours un matériau d isolation de l épaisseur spécifiée tableau à droite Une isolation trop épaisse peut être à l origine d une installation incorrecte de l unité interne une isolation trop fine peut provoquer la formation de condensation L unité comporte des raccordements évasés sur les faces intérieure et extérieure Retirez le couvercle de...

Page 11: ...trique 2 Evaser les conduits de liquide et de gaz puis appliquer un fi lm mince d huile réfrigérante application sur site Avertissement Attention aux écrous évasés volants pressurisation interne Retirer l écrou évasé en procédant comme suit 1 Desserrer l écrou jusqu à ce qu un sifflement se fasse entendre 2 Ne jamais retirer l écrou tant que tout le gaz ne s est pas échappé c est àdire lorsque le ...

Page 12: ... attention de brancher les fils correctement Serrer fermement les vis des bornes pour les empêcher de se desserrer Puis tirer légèrement sur les fils pour vous assurer qu ils ne bougent pas Avertissement Veiller à visser correctement le panneau de service à l appareil extérieur Si le panneau de service n est pas bien installé de l eau des poussières etc pourraient pénétrer à l intérieur de l appar...

Page 13: ...n en cuivre 3 Utiliser des fils d une intensité nominale de 600V ou plus pour les câbles d alimentation et les câbles de raccordement de l appareil intérieur l appareil extérieur 4 Installer un câble de terre plus long que les autres câbles 6 1 Charge de Gaz Fig 6 1 1 Raccorder le tuyau de gaz au port de service de la vanne d arrêt à 3 voies 2 Purger l air du tuyau raccordé au tuyau de gaz réfrigé...

Page 14: ... y producirse un incendio o una descarga eléctrica Al instalar o reubicar la unidad asegúrese de que no entra ninguna otra sustancia excepto el refrigerante especificado R410A en el circuito de refrigeración Cualquier sustancia extraña en el circuito de refrigeración puede provocar una elevación anómala de la presión o una explosión No descargue el refrigerante en el ambiente Una vez acabada la in...

Page 15: ... instalación en el que la unidad exterior y las tomas de tierra no se humedezcan con agua de drenaje ni se dañen debido a la congelación de este agua de drenaje 2 Selección del lugar de instalación 4 pulg 100 mm o más 14 pulg 350 mm o más 8 pulg 200 mm o más 4 pulg 100 mm o más pulganda Unidad 31 1 2 19 11 16 Entrada de aire 13 9 16 11 1 4 Ranura de 2 3 8 13 16 12 12 3 4 1 9 16 800 500 Salida de a...

Page 16: ...instalación incorrecta de la unidad interior y el uso de una cantidad insuficiente de aislante puede provocar la condensación Las unidad tiene conexiones abocinadas en los lados interior y exterior Retire la tapa de la válvula de la unidad exterior y a continuación conecte la tubería Las tuberías de refrigerante se emplean para conectar las unidades interior y exterior Tenga cuidado de no romper n...

Page 17: ...ura de servicio de la válvula de retención situada en el lado de la tubería de gas de la unidad exterior 2 Conecte la válvula colectora de manómetro y la bomba de vacío al puerto de servicio de la válvula de retención en el lado de la tubería del gas de la unidad exterior 3 Ponga en funcionamiento la bomba de vacío durante 15 minutos o más 4 Compruebe el vacío con la válvula colectora de manómetro...

Page 18: ...n en la figura Tenga cuidado de que el cable de conexión no haga contacto con los tubos Cuidado Asegúrese de no realizar un mal cableado Apriete firmemente los tornillos de la terminal para evitar que se aflojen Tras apretarlos tire ligeramente de los cables para confirmar que no se muevan Atención Asegúrese de fijar firmemente el panel de servicio de la unidad exterior Si no se monta correctament...

Page 19: ...o superior para los cables de la fuente de alimentación y los cables de conexión de las unidades in terior exterior 4 Instale un cable de toma de tierra más largo que el resto de los cables 6 1 Carga de gas Fig 6 1 1 Conecte el cilindro de gas a la abertura de servicio de la válvula de parada de 3 vías 2 Purgue el aire del tubo o conducto procedente del cilindro de gas refrigerante 3 Vuelva a llen...

Page 20: ...OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer BH79D173H02 Printed in Thailand ...

Reviews: