6. Electrical work

6.1. Outdoor unit (Fig. 6-1, Fig. 6-2)

 

1

  Remove the service panel.

 

2

  Wire the cables referring to the Fig. 6-1 and the Fig. 6-2.

C

Fig. 6-1

A

  Indoor unit

B

  Outdoor unit

C

  Remote controller

D

  Main switch (Breaker)

E

  Earth

Fig. 6-2

A

B

D

D

A

A

A

B

C

E

E

E

For Power

For Power

L

N

S1 S2 S3

J

J

L1 L2 L3 N

S1 S2 S3

J

J

Termial block

Indoor/Outdoor connection terminal block (S1, S2, S3)

Service panel

Clamp

* Clamp the cables so that they do not contact the center of the service panel or the gas valve.

J

  Earth terminal

Note : 

If the protective sheet for the electrical box is removed during servicing, be sure to 

reinstall it.

 Caution:

Be sure to install N-Line. Without N-Line, it could cause damage to unit.

 

P100, 125, 140V

 

P100, 125, 140Y

S1

S2

S3

S1

S2

S3

6.2. Field electrical wiring

Outdoor unit model

P100,125V

P140V

P100, 125, 140Y

Outdoor unit power supply

~/N (single), 50 Hz, 230 V

~/N (single), 50 Hz, 230 V

3N~ (3 ph 4-wires), 50 Hz, 400 V

Outdoor unit input capacity Main switch (Breaker)

*1

32 A

40 A

16 A

Wiring Wire 

No. × size 

(mm

2

)

Outdoor unit power supply

3 × Min. 6

3 × Min. 6

5 × Min. 1.5

Indoor unit-Outdoor unit

*2

3 × 1.5 (Polar)

3 × 1.5 (Polar)

3 × 1.5 (Polar)

Indoor unit-Outdoor unit earth

*2

1 × Min. 1.5

1 × Min. 1.5

1 × Min. 1.5

Remote controller-Indoor unit

*3

2 × 0.3 (Non-polar)

2 × 0.3 (Non-polar)

2 × 0.3 (Non-polar)

Circuit rating

Outdoor unit L-N (single)
Outdoor unit L1-N, L2-N, L3-N (3 phase)

*4

230 VAC

230 VAC

230 VAC

Indoor unit-Outdoor unit S1-S2

*4

230 VAC

230 VAC

230 VAC

Indoor unit-Outdoor unit S2-S3

*4

24 VDC

24 VDC

24 VDC

Remote controller-Indoor unit

*4

12 VDC

12 VDC

12 VDC

*1. A breaker with at least 3.0 mm contact separation in each poles shall be provided. Use earth leakage breaker (NV).
  Make sure that the current leakage breaker is one compatible with higher harmonics.
  Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter.
  The use of an inadequate breaker can cause the incorrect operation of inverter.
*2. Max. 45 m
  If 2.5 mm

2

 used, Max. 50 m

  If 2.5 mm

2

 used and S3 separated, Max. 80 m

• Use one cable for S1 and S2 and another for S3 as shown in the picture.
• Max. 50 m Total Max. for PEA. Wiring size 3 × 1.5 (Polar).

*3. The 10 m wire is attached in the remote controller accessory.
*4.  The figures are NOT always against the ground.
  S3 terminal has 24 VDC against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulataed by the transformer or other device.

Notes:  1.  Wiring size must comply with the applicable local and national code.

      2.  Power supply cords and Indoor/Outdoor unit connecting cords shall not be lighter than polychloroprene sheathed flexible cord. (Design 60245 IEC 57)

      3.  Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.

A-Control 

Outdoor Unit

3 poles isolator

Power supply

Isolator

A-Control 

Indoor Unit

 Warning:

•  In case of A-control wiring, there is high voltage potential 

on the S3 terminal caused by electrical circuit design that 

has no electrical insulation between power line and com

-

munication signal line. Therefore, please turn off the main 

power supply when servicing. And do not touch the S1, 

S2, S3 terminals when the power is energized. If isolator 

should be used between indoor unit and outdoor unit, 

please use 3-pole type.

Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a fire or communication failure.

RG79Y933H01_EN.indd   9

2017/06/27   11:50:45

Summary of Contents for Mr.Slim PUHZ-P100VKA

Page 1: ...o correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta le...

Page 2: ...he unit electric shock or fire may result When installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an expl...

Page 3: ...tion The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Use C1220 copper phosphorus for copper and c...

Page 4: ...Air protection guide 3 Position the unit so that the air outlet blows perpendicularly to the seasonal wind direction if possible Fig 2 5 B Wind direction 2 4 2 When installing a single outdoor unit Refer to the last page Minimum dimensions are as follows except for Max meaning Maximum dimen sions indicated Refer to the figures for each case 1 Obstacles at rear only Fig 2 6 2 Obstacles at rear and ...

Page 5: ...with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thick nesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contami...

Page 6: ...o 4 4 Refrigerant pipe airtight testing method 4 A high performance vacuum pump is used at the stop valve service port to main tain a vacuum for an adequate time at least one hour after reaching 101 kPa 5 Torr in order to vacuum dry the inside of the pipes Always check the degree of vacuum at the gauge manifold If there is any moisture left in the pipe the degree of vacuum is sometimes not reached...

Page 7: ...the pipe inlet around the pipes so that no gaps remain If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result Precautions when using the charge valve Fig 4 7 Do not tighten the service port too much when installing it otherwise the valve core could be deformed and become loose causing a gas leak After positioning section B in the desired dire...

Page 8: ...The existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping P100 125 140 Drain socket PAC SG61DS E Drain pan PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option 4 8 For twin triple combination Fig 4 8 When this unit is used as a FREE COMPO MULT...

Page 9: ...ch poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate breaker can cause the incorrect operation of inverter 2 Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 sep...

Page 10: ... SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of the outdoor unit The noise is coming from ...

Page 11: ... minutes have passed If the refrigerant collecting operation has been completed normally LED1 off LED2 lit the unit will remain stopped until the power supply is turned off 4 Turn off the power supply circuit breaker Note that when the extension piping is very long with large refrigerant amount it may not be possible to perform a pump down operation When performing the pump down operation make sur...

Page 12: ...te Business Park Ballymount Dublin 24 Ireland Italian Branch Centro Direzionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch H...

Page 13: ...140EA R410A Standard Inverter Three Phase Product Information Sheet PSA RP100 140KA R410A Standard Inverter Product Information Sheet PUHZ P100 140V Y KA Parts List OCB670 PUHZ P100 140V Y KA Service Manual OCH670 PUHZ P100 140V YKA Installation Manual ...

Reviews: