background image

7

4. Installing the refrigerant piping

A

  Stop valve <Liquid side>

B

  Stop valve <Gas side>

C

  Service port

D

  Open/Close section

E

  Local pipe

F

  Sealed, same way for gas side

G

  Pipe cover

Fig. 4-4

4.4. Refrigerant pipe airtight testing method (Fig. 4-4)

(1) Connect the testing tools.

  •   Make sure the stop valves 

A

 

B

 are closed and do not open them.

  •   Add pressure to the refrigerant lines through the service port 

C

 of the liquid 

stop valve 

A

.

(2)  Do not add pressure to the specified pressure all at once; add pressure little by 

little.

 

1

  Pressurize to 0.5 MPa (5 kgf/cm

2

G), wait five minutes, and make sure the pres-

sure does not decrease.

 

2

  Pressurize to 1.5 MPa (15 kgf/cm

2

G), wait five minutes, and make sure the 

pressure does not decrease.

 

3

  Pressurize to 4.15 MPa (41.5 kgf/cm

2

G) and measure the surrounding tem-

perature and refrigerant pressure.

(3)  If the specified pressure holds for about one day and does not decrease, the pipes 

have passed the test and there are no leaks.

  •   If the surrounding temperature changes by 1 °C, the pressure will change by 

about 0.01 MPa (0.1 kgf/cm

2

G). Make the necessary corrections.

(4)  If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the 

source of the gas leak.

4.5. Stop valve opening method

The stop valve opening method varies according to the outdoor unit model. Use the 

appropriate method to open the stop valves.

(1) Gas side (Fig. 4-5)

1

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 5 mm hexagonal wrench. Stop turning when it hits the stopper. 

  (ø 15.88: Approximately 13 revolutions)

2

  Make sure that the stop valve is open completely and rotate the cap back to its 

original position.

(2) Liquid side (Fig. 4-6)

1

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.

   (ø9.52: Approximately 10 revolutions)

2

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

Refrigerant pipes are protectively wrapped

•   The pipes can be protectively wrapped up to a diameter of ø90 before or after 

connecting the pipes. Cut out the knockout in the pipe cover following the groove 

and wrap the pipes. 

Pipe inlet gap

•   Use putty or sealant to seal the pipe inlet around the pipes so that no gaps remain. 

(If the gaps are not closed, noise may be emitted or water and dust will enter the 

unit and breakdown may result.)

Precautions when using the charge valve (Fig. 4-7)

Do not tighten the service port too much when installing it, otherwise, the valve core 

could be deformed and become loose, causing a gas leak.

After positioning section 

B

 in the desired direction, turn section 

A

 only and tighten it.

Do not further tighten sections 

A

 and 

B

 together after tightening section 

A

.

 Warning:

When installing the unit, securely connect the refrigerant pipes before starting 

the compressor.

4.6. Addition of refrigerant

•   Additional charging is not necessary if the pipe length does not exceed 30 m.

•   If the pipe length exceeds 30m, charge the unit with additional R410A refrigerant 

according to the permitted pipe lengths in the chart below.

  *   When the unit is stopped, charge the unit with the additional refrigerant through 

the liquid stop valve after the pipe extensions and indoor unit have been vacu-

umized.

     When  the  unit  is  operating,  add  refrigerant  to  the  gas  check  valve  using  a 

safety charger. Do not add liquid refrigerant directly to the check valve.

  *   After charging the unit with refrigerant, note the added refrigerant amount on 

the service label (attached to the unit).

     Refer to the “1.5. Using R410A refrigerant air conditioners” for more informa-

tion.

•   Be careful when installing multiple units. Connecting to an incorrect indoor unit 

can  lead  to  abnormally  high  pressure  and  have  a  serious  effect  on  operation 

performance.

Model

Permitted 

pipe length

Permitted 

vertical 

difference

Additional refrigerant charging 

amount

31 - 40 m

41 - 50 m

P100, 125, 140

- 50 m

- 30 m

0.6 kg

1.2 kg

H

  Double spanner section

   (Do not apply a spanner other than to this section. 

Doing so would cause coolant leaks.)

I

  Seal section

   (Seal the end of the heat insulation material at the 

pipe connection section with whatever seal material 
you have on hand so that water does not infiltrate 
the heat insulation material.)

A

  Valve

B

  Unit side

C

  Cap

Local pipe side

E

  Pipe cover

F

  Service port

G

  Wrench hole

G

G

F

F

E

E

D

D

C

A

B

* The figure to the left is an example only.
  The  stop  valve  shape,  service  port  posi-

tion, etc., may vary according to the model.

* Turn section 

A

 only.

  (Do not further tighten sections 

A

 and 

B

 

together.)

C

 Charge hose

D

 Service port

A

B

C

D

Fig. 4-7

Fig. 4-5

Fig. 4-6

C

C

H

A

I

E

B

(1)

(2)

H

D

E

G

F

A

G

I

D

B

RG79Y933H01_EN.indd   7

2017/06/27   11:50:42

Summary of Contents for Mr.Slim PUHZ-P100VKA

Page 1: ...o correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta le...

Page 2: ...he unit electric shock or fire may result When installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an expl...

Page 3: ...tion The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Use C1220 copper phosphorus for copper and c...

Page 4: ...Air protection guide 3 Position the unit so that the air outlet blows perpendicularly to the seasonal wind direction if possible Fig 2 5 B Wind direction 2 4 2 When installing a single outdoor unit Refer to the last page Minimum dimensions are as follows except for Max meaning Maximum dimen sions indicated Refer to the figures for each case 1 Obstacles at rear only Fig 2 6 2 Obstacles at rear and ...

Page 5: ...with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thick nesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contami...

Page 6: ...o 4 4 Refrigerant pipe airtight testing method 4 A high performance vacuum pump is used at the stop valve service port to main tain a vacuum for an adequate time at least one hour after reaching 101 kPa 5 Torr in order to vacuum dry the inside of the pipes Always check the degree of vacuum at the gauge manifold If there is any moisture left in the pipe the degree of vacuum is sometimes not reached...

Page 7: ...the pipe inlet around the pipes so that no gaps remain If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result Precautions when using the charge valve Fig 4 7 Do not tighten the service port too much when installing it otherwise the valve core could be deformed and become loose causing a gas leak After positioning section B in the desired dire...

Page 8: ...The existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping P100 125 140 Drain socket PAC SG61DS E Drain pan PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option 4 8 For twin triple combination Fig 4 8 When this unit is used as a FREE COMPO MULT...

Page 9: ...ch poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate breaker can cause the incorrect operation of inverter 2 Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 sep...

Page 10: ... SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of the outdoor unit The noise is coming from ...

Page 11: ... minutes have passed If the refrigerant collecting operation has been completed normally LED1 off LED2 lit the unit will remain stopped until the power supply is turned off 4 Turn off the power supply circuit breaker Note that when the extension piping is very long with large refrigerant amount it may not be possible to perform a pump down operation When performing the pump down operation make sur...

Page 12: ...te Business Park Ballymount Dublin 24 Ireland Italian Branch Centro Direzionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch H...

Page 13: ...140EA R410A Standard Inverter Three Phase Product Information Sheet PSA RP100 140KA R410A Standard Inverter Product Information Sheet PUHZ P100 140V Y KA Parts List OCB670 PUHZ P100 140V Y KA Service Manual OCH670 PUHZ P100 140V YKA Installation Manual ...

Reviews: