600

600

330

370

225

225

1050

28

3. Installing the outdoor unit

•   Be sure to install the unit in a sturdy, level surface to prevent rattling noises during 

operation. (Fig. 3-1)

<Foundation specifications>

Foundation bolt

M10 (3/8")

Thickness of concrete

120 mm

Length of bolt

70 mm

Weight-bearing capacity

320 kg

•   Make sure that the length of the foundation bolt is within 30 mm of the bottom 

surface of the base.

•   Secure the base of the unit firmly with four-M10 foundation bolts in sturdy loca-

tions. 

Installing the outdoor unit

•   Do not block the vent. If the vent is blocked, operation will be hindered and break-

down may result.

•   In addition to the unit base, use the installation holes on the back of the unit to 

attach wires, etc., if necessary to install the unit. Use self-tapping screws (ø5 × 15 

mm or less) and install on site.

 Warning:

•   The  unit  must  be  securely  installed  on  a  structure  that  can  sustain  its 

weight. If the unit is mounted on an unstable structure, it may fall down and 

cause damage or injuries.

•   The unit must be installed according to the instructions in order to minimize 

the risk of damage from earthquakes, typhoons, or strong winds. An incor

-

rectly installed unit may fall down and cause damage or injuries.

(mm)

B

4. Installing the refrigerant piping

4.1.  Precautions for devices that use R410A refrigerant

•   Refer to 1.5. for precautions not included below on using air conditioners 

with R410A refrigerant.

•   Use ester oil, ether oil, alkylbenzene oil (small amount) as the refrigeration 

oil applied to the flared sections.

•   Use  C1220  copper  phosphorus,  for  copper  and  copper  alloy  seamless 

pipes, to connect the refrigerant pipes. Use refrigerant pipes with the thick

-

nesses  specified  in  the  table  to  the  below.  Make  sure  the  insides  of  the 

pipes are clean and do not contain any harmful contaminants such as sul-

furic compounds, oxidants, debris, or dust.

 Always apply no-oxidation brazing when brazing the pipes, otherwise, the 

compressor will be damaged.

 Warning:

When installing or relocating, or servicing the air conditioner, use only the 

specified refrigerant (R410A) to charge the refrigerant lines. Do not mix it with 

any other refrigerant and do not allow air to remain in the lines.

 If air is mixed with the refrigerant, then it can be the cause of abnormal high 

pressure in the refrigerant line, and may result in an explosion and other haz

-

ards.

The use of any refrigerant other than that specified for the system will cause 

mechanical  failure  or  system  malfunction  or  unit  breakdown.  In  the  worst 

case, this could lead to a serious impediment to securing product safety.

Pipe size (mm)

ø9.52

ø12.7

ø15.88

ø19.05

Thickness (mm)

0.8

0.8

1.0

1.0

•   Do not use pipes thinner than those specified above.

•   Use 1/2 H or H pipes if the diameter is 19.05 mm or larger.

C

E

A

Fig. 3-1

Max. 30

*  When installing a single outdoor unit, the clearance is 15 mm or more.

Min. 500

Min. 25*

A

  M10 (3/8") bolt

B

  Base

C

  As long as possible.

Vent

E

  Set deep in the ground

D

RG79Y933H01_EN.indd   5

2017/06/27   11:50:39

Summary of Contents for Mr.Slim PUHZ-P100VKA

Page 1: ...o correcto y seguro lea detalladamente este manual y el manual de instalación de la unidad interior antes de instalar la unidad de aire acondicionado MANUALE DI INSTALLAZIONE Per un uso sicuro e corretto leggere attentamente il presente manuale ed il manuale d installazione dell unità interna prima di installare il condizionatore d aria MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta le...

Page 2: ...he unit electric shock or fire may result When installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an expl...

Page 3: ...tion The refrigerant pipes are hot or cold depending on the condition of the flowing refrigerant If you touch the pipes burns or frostbite may result After stopping operation be sure to wait at least five minutes before turn ing off the main power switch Otherwise water leakage or breakdown may result 1 5 Using R410A refrigerant air conditioners Caution Use C1220 copper phosphorus for copper and c...

Page 4: ...Air protection guide 3 Position the unit so that the air outlet blows perpendicularly to the seasonal wind direction if possible Fig 2 5 B Wind direction 2 4 2 When installing a single outdoor unit Refer to the last page Minimum dimensions are as follows except for Max meaning Maximum dimen sions indicated Refer to the figures for each case 1 Obstacles at rear only Fig 2 6 2 Obstacles at rear and ...

Page 5: ...with R410A refrigerant Use ester oil ether oil alkylbenzene oil small amount as the refrigeration oil applied to the flared sections Use C1220 copper phosphorus for copper and copper alloy seamless pipes to connect the refrigerant pipes Use refrigerant pipes with the thick nesses specified in the table to the below Make sure the insides of the pipes are clean and do not contain any harmful contami...

Page 6: ...o 4 4 Refrigerant pipe airtight testing method 4 A high performance vacuum pump is used at the stop valve service port to main tain a vacuum for an adequate time at least one hour after reaching 101 kPa 5 Torr in order to vacuum dry the inside of the pipes Always check the degree of vacuum at the gauge manifold If there is any moisture left in the pipe the degree of vacuum is sometimes not reached...

Page 7: ...the pipe inlet around the pipes so that no gaps remain If the gaps are not closed noise may be emitted or water and dust will enter the unit and breakdown may result Precautions when using the charge valve Fig 4 7 Do not tighten the service port too much when installing it otherwise the valve core could be deformed and become loose causing a gas leak After positioning section B in the desired dire...

Page 8: ...The existing pipe thickness does not meet specifications or the pipes are damaged 4 Installing the refrigerant piping P100 125 140 Drain socket PAC SG61DS E Drain pan PAC SH97DP E 5 Drainage piping work Outdoor unit drainage pipe connection When drain piping is necessary use the drain socket or the drain pan option 4 8 For twin triple combination Fig 4 8 When this unit is used as a FREE COMPO MULT...

Page 9: ...ch poles shall be provided Use earth leakage breaker NV Make sure that the current leakage breaker is one compatible with higher harmonics Always use a current leakage breaker that is compatible with higher harmonics as this unit is equipped with an inverter The use of an inadequate breaker can cause the incorrect operation of inverter 2 Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 sep...

Page 10: ... SW4 2 OFF SW4 1 ON Heating operation SW4 2 ON After performing the test run set SW4 1 to OFF After power is supplied a small clicking noise may be heard from the inside of the outdoor unit The electronic expansion valve is opening and closing The unit is not faulty A few seconds after the compressor starts a clanging noise may be heard from the inside of the outdoor unit The noise is coming from ...

Page 11: ... minutes have passed If the refrigerant collecting operation has been completed normally LED1 off LED2 lit the unit will remain stopped until the power supply is turned off 4 Turn off the power supply circuit breaker Note that when the extension piping is very long with large refrigerant amount it may not be possible to perform a pump down operation When performing the pump down operation make sur...

Page 12: ...te Business Park Ballymount Dublin 24 Ireland Italian Branch Centro Direzionale Colleoni Palazzo Sirio Ingresso 1 Viale Colleoni 7 20864 Agrate Brianza MB Italy Norwegian Branch Gneisveien 2D 1914 Ytre Enebakk Norway Portuguese Branch Avda do Forte 10 2799 514 Carnaxide Lisbon Portugal Spanish Branch Carretera de Rubi 76 80 Apdo 420 08173 Sant Cugat del Valles Barcelona Spain Scandinavian Branch H...

Page 13: ...140EA R410A Standard Inverter Three Phase Product Information Sheet PSA RP100 140KA R410A Standard Inverter Product Information Sheet PUHZ P100 140V Y KA Parts List OCB670 PUHZ P100 140V Y KA Service Manual OCH670 PUHZ P100 140V YKA Installation Manual ...

Reviews: