background image

8

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

CHECK

2

4

A

3

B

Fig. 7-2

6. Electrical work

Function table

Select unit number 00

Mode
Power failure automatic recovery

Indoor temperature detecting

LOSSNAY connectivity

Power voltage

Auto mode (only for PUHZ)

Settings
Not available
Available
Indoor unit operating average
Set by indoor unit’s remote controller
Remote controller’s internal sensor
Not Supported
Supported (indoor unit is not equipped with outdoor-air intake)
Supported (indoor unit is equipped with outdoor-air intake)
240 V
220 V, 230 V
Energy saving cycle automatically enabled
Energy saving cycle automatically disabled

Mode no.

Setting no. Initial setting

Setting

01

1
2
1

02

2
3

1

03

2
3

04

1
2

05

1
2

Mode
Filter sign

Fan speed

No. of air outlets

Installed options (high-performance filter)

Up/down vane setting

Energy saving air flow
(Heating mode)

Settings
100 Hr
2500 Hr
No filter sign indicator
Standard (PLH/PLA)/Silent (PCH/PCA)
High ceiling 

1

 (PLH/PLA)/Standard (PCH/PCA)

High ceiling 

2

 (PLH/PLA)/High ceiling PCH/PCA)

4 directions
3 directions
2 directions
Not supported
Supported
No vanes
Equipped with vanes (vanes angle setup 

1

)

Equipped with vanes (vanes angle setup 

2

)

Disabled
Enabled

Mode no.

Setting no. Initial setting

Setting

1

07

2
3
1

08

2

3
1

09

2

3

10

1
2

11

1
2

3

12

1
2

Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])

7. Test run

7.1. Before test run

s

After completing installation and the wiring and piping of the indoor and outdoor
units, check for refrigerant leakage, looseness in the power supply or control
wiring, wrong polarity, and no disconnection of one phase in the supply.

s

Use a 500-volt megohmmeter to check that the resistance between the power
supply terminals and ground is at least 1.0 M

.

s

Do not carry out this test on the control wiring (low voltage circuit) termi-
nals.

 Warning:

• Do not use the air conditioner if the insulation resistance is less than 1.0 M

.

Insulation resistance

• Turn on the power at least 12 hours before starting operation.

- Starting operation immediately after turning on the main power switch can result in

severe damage to internal parts. Keep the power switch turned on during the op-
erational season.

7.2. Test run

7.2.1. Using wireless remote controller (Fig. 7-1)

1

Turn on the power to the unit at least 12 hours before the test run.

2

Press the 

TEST RUN

 button twice continuously.

(Start this operation from the status of remote controller display turned off.)

A

TEST RUN

 and current operation mode are displayed.

3

Press the 

MODE

 

 button to activate 

COOL

 mode, then check whether

cool air is blown out from the unit.

4

Press the 

MODE

 

 button to activate 

HEAT

 mode, then check whether

warm air is blown out from the unit.

5

Press the 

FAN

 button and check whether fan speed changes.

6

Press the 

VANE

 button and check whether the auto vane operates properly.

7

Press the ON/OFF button to stop the test run.

Note:
• Point the remote controller towards the indoor unit receiver while following

steps 

2

 to 

7

.

• It is not possible to run the in FAN, DRY or AUTO mode.

7.2.2. Using SW4 in outdoor unit

Refer to the outdoor unit installation manual.

7.3. Self-check (Fig. 7-2)

1

Turn on the power.

2

Press the 

CHECK

 button twice.

(Start this operation from the status of remote controller display turned off.)

A

CHECK

 begins to light.

B

«00» begins to blink.

3

While pointing the remote controller toward the unit’s receiver, press the 

h

button. The check code will be indicated by the number of times that the buzzer
sounds from the receiver section and the number of blinks of the operation lamp.

4

Press the ON/OFF button to stop the self-check.

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

TEST RUN

5

7

A

3

,

4

2

6

Fig. 7-1

Summary of Contents for Mr. Slim PKA-RP-GAL

Page 1: ...ondizionatore d aria MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛÊ ÏÂÈ Î È ÛˆÛÙ Ú ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente est...

Page 2: ... If combustible gas accumulates around the unit fire or explo sion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not instal...

Page 3: ...e determine the unit s installation position and the locations of the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor A Supporting piece J Bottom right pipe slot ø90 B Mount board K Bottom right pipe slot knockout hole C Main body L Liquid pipe flare connection position D Slot 6 11 20 M Gas pipe flare connection position E Unit center ...

Page 4: ...ling pipe and drain pipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessary Remove the corner box by pushing in a downward direction b while at the same time pressing in the upper side part of the corner box a A Corner box B Under cover Left and left r...

Page 5: ...ping Fig 4 2 Fig 4 4 E D B C A C B D F 35 449 581 280 31 54 86 153 700 A E 60 10 22 70 21 245 D 8 B E D 10 190 22 70 35 8 60 C E 8 60 10 22 70 21 245 D Fig 4 3 1 A B C D E F G 4 3 Refrigerant piping Fig 4 4 Indoor unit 1 Remove the flare nut and cap of the indoor unit 2 Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil available from your local supplier to the flare...

Page 6: ...Pour water in the drain pan and check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 6 1 Indoor unit Fig 6 1 1 Remove the corner box 2 Install each wire into the unit 3 Open the front grill remove 1 tapping screw and remove the terminal block cover A Terminal block cover 4 Connect each wire properly to the terminal block In consideratio...

Page 7: ...er you want to set 4 Press the SET button with something sharp at the end Set pair number is lighted for three seconds then turned off A Pair No of wireless remote controller Indoor PC board 0 Factory setting 1 Cut J41 2 Cut J42 3 9 Cut J41 J42 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODELSELECT 1 4 3 A 2 Fig 6 4 3 CHECK 4 CHECK ON OFF TEMP FAN VA...

Page 8: ...und is at least 1 0 MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0 MΩ Ω Ω Ω Ω Insulation resistance Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main power switch can result in severe damage to intern...

Page 9: ... operation lamp does not light up For about 2 minutes following power on After about 2 minutes has expired following power on After LED 1 2 are lighted LED 2 is turned off then only LED 1 is lighted Correct operation Only LED 1 is lighted LED 1 2 blink Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once For about 2 minutes following power on operation of the remote controller is not possibl...

Page 10: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U304H01 The product at hand is based on the following EU regulations ...

Reviews: