Mitsubishi Electric Mr. Slim PKA-RP-GAL Installation Manual Download Page 9

9

7. Test run

• For description of each check code, refer to the following table.

1

 Check code

Symptom

2

 Buzzer sound

3

 OPE LED

P1

Intake sensor error

Single beep 

×

 1

Lit for 1 sec. 

×

 1

P2

Pipe sensor error

Single beep 

×

 2

Lit for 1 sec. 

×

 2

P4

Drain sensor error

Single beep 

×

 4

Lit for 1 sec. 

×

 4

P5

Drain pump error

Single beep 

×

 5

Lit for 1 sec. 

×

 5

P6

Freezing/Overheating safeguard operation

Single beep 

×

 6

Lit for 1 sec. 

×

 6

P8

Pipe temperature error

Single beep 

×

 8

Lit for 1 sec. 

×

 8

P9

TH5 sensor error

Single beep 

×

 2

Lit for 1 sec. 

×

 2

U0–UP

Outdoor unit error

Double beep 

×

 1

Lit for 0.4 sec. + 0.4 sec. 

×

 1

F1–FA

Outdoor unit error

Double beep 

×

 1

Lit for 0.4 sec. + 0.4 sec. 

×

 1

E0–E5

Signal error between remote controller and indoor units

Sounds other than above

Lights other than above

E6–EF

Communication error between indoor and outdoor units

Sounds other than above

Lights other than above

– –

No alarm history

No sound

Not lit

F F F F

No unit

Triple beep

Not lit

• On wireless remote controller

2

The continuous buzzer sounds from receiving section of indoor unit.

3

Blink of operation lamp

• On wired remote controller

1

Check code displayed in the LCD.

• If the unit cannot be operated properly after the above test run has been performed, refer to the following table to remove the cause.

Symptom

Cause

Wired remote controller

LED 1, 2 (PCB in outdoor unit)

H0

H0 

 Error code

Display messages do not apper even
when operation switch is turned ON
(operation lamp does not light up).

For about 2
minutes following
power-on

After about 2
minutes has
expired following
power-on

After LED 1, 2 are lighted, LED 2 is turned off,
then only LED 1 is lighted. (Correct operation)

Only LED 1 is lighted. 

 LED 1, 2 blink.

Only LED 1 is lighted. 

 LED 1 blinks twice,

LED 2 blinks once.

• For about 2 minutes following power-on, operation of the

remote controller is not possible due to system start-up. (Cor-
rect operation)

• Connector for the outdoor unit’s protection device is not con-

nected.

• Reverse or open phase wiring for the outdoor unit’s power

terminal block (L1, L2, L3)

• Incorrect wiring between indoor and outdoor units (incorrect

polarity of S1, S2, S3)

• Remote controller wire short

On the wireless remote controller with condition above, following phenomena takes place.
• No signals from the remote controller are accepted.
• OPE lamp is blinking.
• The buzzer makes a short pipng sound.

Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)

For description of each LED (LED 1, 2, 3) provided on the indoor controller, refer to the following table.

LED 1 (power for microcomputer)

Indicates whether control power is supplied. Make sure that this LED is always lit.

LED 2 (power for remote controller)

Indicates whether power is supplied to the remote controller. This LED lights only in the case of the
indoor unit which is connected to the outdoor unit refrigerant address “0”.

LED 3 (communication between indoor and outdoor units)

Indicates state of communication between the indoor and outdoor units. Make sure that this LED is
always blinking.

Summary of Contents for Mr. Slim PKA-RP-GAL

Page 1: ...ondizionatore d aria MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛÊ ÏÂÈ Î È ÛˆÛÙ Ú ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente est...

Page 2: ... If combustible gas accumulates around the unit fire or explo sion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not instal...

Page 3: ...e determine the unit s installation position and the locations of the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor A Supporting piece J Bottom right pipe slot ø90 B Mount board K Bottom right pipe slot knockout hole C Main body L Liquid pipe flare connection position D Slot 6 11 20 M Gas pipe flare connection position E Unit center ...

Page 4: ...ling pipe and drain pipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessary Remove the corner box by pushing in a downward direction b while at the same time pressing in the upper side part of the corner box a A Corner box B Under cover Left and left r...

Page 5: ...ping Fig 4 2 Fig 4 4 E D B C A C B D F 35 449 581 280 31 54 86 153 700 A E 60 10 22 70 21 245 D 8 B E D 10 190 22 70 35 8 60 C E 8 60 10 22 70 21 245 D Fig 4 3 1 A B C D E F G 4 3 Refrigerant piping Fig 4 4 Indoor unit 1 Remove the flare nut and cap of the indoor unit 2 Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil available from your local supplier to the flare...

Page 6: ...Pour water in the drain pan and check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 6 1 Indoor unit Fig 6 1 1 Remove the corner box 2 Install each wire into the unit 3 Open the front grill remove 1 tapping screw and remove the terminal block cover A Terminal block cover 4 Connect each wire properly to the terminal block In consideratio...

Page 7: ...er you want to set 4 Press the SET button with something sharp at the end Set pair number is lighted for three seconds then turned off A Pair No of wireless remote controller Indoor PC board 0 Factory setting 1 Cut J41 2 Cut J42 3 9 Cut J41 J42 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODELSELECT 1 4 3 A 2 Fig 6 4 3 CHECK 4 CHECK ON OFF TEMP FAN VA...

Page 8: ...und is at least 1 0 MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0 MΩ Ω Ω Ω Ω Insulation resistance Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main power switch can result in severe damage to intern...

Page 9: ... operation lamp does not light up For about 2 minutes following power on After about 2 minutes has expired following power on After LED 1 2 are lighted LED 2 is turned off then only LED 1 is lighted Correct operation Only LED 1 is lighted LED 1 2 blink Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once For about 2 minutes following power on operation of the remote controller is not possibl...

Page 10: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U304H01 The product at hand is based on the following EU regulations ...

Reviews: