background image

4

3. Installing the indoor unit

3.2.3. Installing the wall mounting fixture

s

Since the indoor unit weighs near 30 kg, selection of the mounting location
requires thorough consideration. If the wall does not seem to be strong
enough, reinforce it with boards or beams before installation.

s

The mounting fixture must be secured at both ends and at the centre, if
possible. Never fix it at a single spot or in any nonsymetrical way.
(If possible, secure the fixture at all the positions marked with a bold arrow.)
(Fig. 3-4)
 Warning:

If possible, secure the fixture at all positions indicated with a bold arrow.

 Caution:

• The unit body must be mounted horizontally.
• Fasten at the holes marked with 

 as shown by the arrows.

1

Fasten a thread to the hole.

2

The level can be easily obtained by hanging a weight from the string and aligning the string
with the mark.

3.3. When embedding pipes into the wall (Fig. 3-5)

• The pipes are on the bottom left.
• When the cooling pipe, drain pipes internal/external connection lines etc are to be

embedded into the wall in advance, the extruding pipes etc, may have to be bent
and have their length modified to suit the unit.

• Use marking on the mount board as a reference when adjusting the length of the

embedded cooling pipe.

• During construction, give the length of the extruding pipes etc some leeway.

A

Mount board

B

Reference marking for flare connection

C

Through hole

D

On-site piping

3.4. Preparing the indoor unit

Rear, right and lower piping (Fig. 3-6)

1. Bind the cooling pipe and drain pipe together.
• Bind the pipes together with vinyl tape at three or more points. This will facilitate

passing the pipes through the wall.

2. Remove the corner box and knock out the knockout holes as necessary.
• Remove the corner box by pushing in a downward direction 

b

, while at the same

time, pressing in the upper side part of the corner box 

a

.

A

Corner box

B

Under cover

Left and left rear piping (Fig. 3-7)

1. Remove the under cover.
• Remove the under cover by sliding it towards the rear of the unit 

b

, while at the

same time, pressing the two points marked by arrow heads 

a

.

2. Remove the corner box and knock out the knockout holes as necessary.

Fig. 3-7

Fig. 3-4

Fig. 3-5

Fig. 3-6

1

D

2

B

A

C

A

B

D

C

a

A

b

a

a

A

B

b

b

A

B

C

B

A

A

30~40

C

A

B

(mm)

A

Min. 140 mm

B

Min. 300 mm

C

Min. 55 mm

D

Mount board

Fig. 3-8

Fig. 3-9

3.5. Mounting the indoor unit

1. Affix the mounting plate to the wall.
2. Hang the indoor unit on the two hooks positioned on the upper part of the mount-

ing plate.

Rear, right and lower piping (Fig. 3-8)

3. Affix the indoor unit.
4. After connecting the pipes, put the corner box back to where it was (follow the

removal steps backwards).

A

Square hole

B

Hooks

Left and left rear piping (Fig. 3-9)

3. Cut out a mounting piece from the packaging material.
4. Pull the indoor unit up towards yourself as shown in the figure below and slide the

mounting piece in to the mounting plate using the mounting piece setting marks
as reference.

5. After connecting the pipes and wiring, put the under cover back to where it was,

and remove the mounting piece and affix the indoor unit as shown in the left
figure.

6. Put the corner box back to where it was.

A

Mounting piece

B

Ceiling

C

Rib

Summary of Contents for Mr. Slim PKA-RP-GAL

Page 1: ...ondizionatore d aria MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado E XEIPI IO O H IøN E KATA TA H È ÛÊ ÏÂÈ Î È ÛˆÛÙ Ú ÛË Ú Î ÏÂ ÛÙÂ È ÛÂÙÂ ÚÔÛÂ ÙÈÎ Ùfi ÙÔ ÂÁ ÂÈÚ ÈÔ ÂÁÎ Ù ÛÙ ÛË ÚÈÓ Ú ÛÂÙÂ ÙËÓ ÂÁÎ Ù ÛÙ ÛË ÙË ÌÔÓ ÎÏÈÌ ÙÈÛÌÔ MANUAL DE INSTALAÇÃO Para segurança e utilização correctas leia atentamente est...

Page 2: ... If combustible gas accumulates around the unit fire or explo sion may result Do not keep food plants caged pets artwork or precision instruments in the direct airflow of the indoor unit or too close to the unit as these items can be damaged by temperature changes or dripping water When the room humidity exceeds 80 or when the drainpipe is clogged wa ter may drip from the indoor unit Do not instal...

Page 3: ...e determine the unit s installation position and the locations of the piping holes to be drilled Warning Before drilling a hole in the wall you must consult the building contractor A Supporting piece J Bottom right pipe slot ø90 B Mount board K Bottom right pipe slot knockout hole C Main body L Liquid pipe flare connection position D Slot 6 11 20 M Gas pipe flare connection position E Unit center ...

Page 4: ...ling pipe and drain pipe together Bind the pipes together with vinyl tape at three or more points This will facilitate passing the pipes through the wall 2 Remove the corner box and knock out the knockout holes as necessary Remove the corner box by pushing in a downward direction b while at the same time pressing in the upper side part of the corner box a A Corner box B Under cover Left and left r...

Page 5: ...ping Fig 4 2 Fig 4 4 E D B C A C B D F 35 449 581 280 31 54 86 153 700 A E 60 10 22 70 21 245 D 8 B E D 10 190 22 70 35 8 60 C E 8 60 10 22 70 21 245 D Fig 4 3 1 A B C D E F G 4 3 Refrigerant piping Fig 4 4 Indoor unit 1 Remove the flare nut and cap of the indoor unit 2 Make a flare for the liquid pipe and gas pipe and apply refrigerating machine oil available from your local supplier to the flare...

Page 6: ...Pour water in the drain pan and check that it comes out the drain pipe end After confirmation reinstall the side panel A a b A A B 1 3 2 4 Fig 5 2 6 1 Indoor unit Fig 6 1 1 Remove the corner box 2 Install each wire into the unit 3 Open the front grill remove 1 tapping screw and remove the terminal block cover A Terminal block cover 4 Connect each wire properly to the terminal block In consideratio...

Page 7: ...er you want to set 4 Press the SET button with something sharp at the end Set pair number is lighted for three seconds then turned off A Pair No of wireless remote controller Indoor PC board 0 Factory setting 1 Cut J41 2 Cut J42 3 9 Cut J41 J42 ON OFF TEMP FAN VANE TEST RUN AUTO STOP AUTO START h min LOUVER MODE CHECK RESET SET CLOCK MODELSELECT 1 4 3 A 2 Fig 6 4 3 CHECK 4 CHECK ON OFF TEMP FAN VA...

Page 8: ...und is at least 1 0 MΩ Ω Ω Ω Ω s Do not carry out this test on the control wiring low voltage circuit termi nals Warning Do not use the air conditioner if the insulation resistance is less than 1 0 MΩ Ω Ω Ω Ω Insulation resistance Turn on the power at least 12 hours before starting operation Starting operation immediately after turning on the main power switch can result in severe damage to intern...

Page 9: ... operation lamp does not light up For about 2 minutes following power on After about 2 minutes has expired following power on After LED 1 2 are lighted LED 2 is turned off then only LED 1 is lighted Correct operation Only LED 1 is lighted LED 1 2 blink Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once For about 2 minutes following power on operation of the remote controller is not possibl...

Page 10: ... EEC Electromagnetic Compatibility Directive 89 336 EEC This product is designed and intended for use in the residential commercial and light industrial environment HEAD OFFICE MITSUBISHI DENKI BLDG 2 2 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U304H01 The product at hand is based on the following EU regulations ...

Reviews: