46
6. WRONG WIRING ON SITE
6-1 Between remote controller and indoor unit
If wire is disconnected between the remote controller and the indoor unit, the POWER ON display does not appear despite
turning the power switch ON. The beep sound is not heard, either.
6-2 Phenomena due to wrong wiring between indoor and outdoor units
Wrong wiring
Thermostat
Phenomena
Outdoor unit
Indoor unit
1
2
1
2
OFF
The outdoor unit stops.
ON
Operation stops. 9 minutes later, the check code ¨P8¨ appears
on the remote controller display.
OFF
Operation stops.
ON
9 minutes later, the check code ¨P8¨ appears on the remote con-
troller display.
Disconnect between 1 and 1 or 2 and
2.