12
4. OPERATING RANGE
1) POWER SUPPLY
2) OPERATION
5. OUTLET AIR SPEED AND COVERAGE RANGE
●
The air coverage range is the value up to the position where the air speed is 0.8ft/sec. when air is blown out
horizontally from the unit at the High fan setting.
The coverage range should be used only as a general guideline since it varies according to the size of the
room and furniture installed inside the room.
6. ADDITIONAL REFRIGERANT CHARGE (R-22 (OZ))
Indoor unit
Outdoor unit
Rating
115V 1 phase 60Hz
208/230V 1 phase 60Hz
Allowable voltage
Min. 103V — Max. 127V
Min. 198V — Max. 253V
Function
Cooling
DB (˚F)
80
95
67
80
Condition
Standard temperature
Maximum temperature
Minimum temperature
Maxmum humidity
Indoor
Intake air temperature
Outdoor
WB (˚F)
67
71
57
75
DB (˚F)
95
115
0
80
WB (˚F)
75
75
—
75
Airflow
Air speed
Coverage range
(CFM)
(ft / sec.)
(ft)
Standard
height
(8.2ft)
PK12FK
490
14.1
32
PK18FK
710
16.1
41
PK24FK
710
16.1
41
PK30FK
990
17.7
50
PK36FK
990
17.7
50
Model
PK12FK
PK18FK
PK24FK
PK30FK
PK36FK
4 lbs 14 oz
5 lbs 8 oz
9 lbs 15 oz
10 lbs 2 oz
10 lbs 9 oz
25ft
0
0
0
0
0
40ft
0
0
0
0
0
55ft
0
0
0
0
0
70ft
0
0
0
0
0
85ft
0
0
0
0
0
Refrigerant piping length (over way)
100ft
0
0
0
0
0
115ft
2
2
2
5
5
130ft
4
4
4
10
10
150ft
—
—
7
16
16
164ft
—
—
9
20
20
Outdoor unit
precharged
(up to 100ft)
OC121--1.qxp 24/6/97 2:12 AM Page 12