background image

11

7. Trouble Shooting

Having trouble?

Here is the solution. (Unit is operating normally.)

Noise is louder than specifications.

 

The indoor operation sound level is affected by the acoustics of the 

particular room as shown in the following table and will be higher than 

the noise specification, which was measured in an echo-free room.

High sound-

absorbing 

rooms

Normal rooms

Low sound-

absorbing 

rooms

Location 

examples

Broadcasting 

studio, music 

room, etc.

Reception 

room, hotel 

lobby, etc.

Office, hotel 

room

Noise levels

3 to 7 dB

6 to 10 dB

9 to 13 dB

Nothing appears in the wireless remote controller display, the display 

is faint, or signals are not received by the indoor unit unless the remote 

controller is close.

 

The batteries are low.

 

Replace the batteries and press the Reset button.

 

If nothing appears even after the batteries are replaced, make sure that 

the batteries are installed in the correct directions (+, –).

The operation lamp near the receiver for the wireless remote controller 

on the indoor unit is flashing.

 

The self diagnosis function has operated to protect the air conditioner.

 

Do not attempt to repair this equipment by yourself.

 

Turn off the power switch immediately and consult your dealer. Be sure 

to provide the dealer with the model name.

The wireless remote controller does not operate (the indoor unit beeps 

4 times).

 

Switch the auto mode setting to the AUTO (single set point) mode or 

AUTO (dual set point) mode. For details, refer to the included Notice (A5 

sheet) or the Installation Manual.

8. Specifications

Item 

Model

PEAD-M50JAA(D)

PEAD-M60JAA(D)

PEAD-M71JAA(D)

PEAD-M100JAA(D)

Power source

220-240 V (50/60 Hz)

Dimension

Height

mm

250

Width

mm

900

1100

1400

Depth

mm

732

Net weight*

2

kg

26(27)

29(30)

38(39)

Fan

Airflow rate (Low-Middle-High)

m

3

/min

12.0-14.5-17.0

14.5-18.0-21.0

17.5-21.0-25.0

24.0-29.0-34.0

External static pressure*

3

Pa

35/50/70/100/125

35/50/70/100/125

35/50/70/100/125

35/50/70/100/125

Sound level (Low-Mid-High)*

4

dB(A)

30-35-39

30-33-37

30-34-39

33-38-42

Filter

Standard filter

Item 

Model

PEAD-M125JAA(D)

PEAD-M140JAA(D)

Power source

220-240 V (50/60 Hz)

Dimension

Height

mm

250

Width

mm

1400

1600

Depth

mm

732

Net weight*

2

kg

39(40)

43(44)

Fan

Airflow rate (Low-Middle-High)

m

3

/min

29.5-35.5-42.0

32.0-39.0-46.0

External static pressure*

3

Pa

35/50/70/100/125

35/50/70/100/125

Sound level (Low-Mid-High)*

4

dB(A)

36-40-44

40-44-49

Filter

Standard filter

Notes:

*   Operation temperature of indoor unit.

 

Cooling mode: 15 °C WB - 24 °C WB

 

Heating mode: 15 °C DB - 27 °C DB

*1   Cooling/Heating capacity indicates the maximum value at operation under the following condition.

 

Cooling:Indoor: 27 °C DB/19 °C  

WB Outdoor: 35 °C DB

 

Heating:Indoor: 20 °C DB  

Outdoor: 7 °C DB/6 °C WB

*2  The value in the parenthesis are for the PEAD-M•JAAD model.

*3  The external static pressure is set to 50 Pa at factory shipment.

*4  The operating noise is the data that was obtained in an anechoic room.

Summary of Contents for Mr. SLIM PEAD-M100JAA

Page 1: ...ir Conditioners PEAD M50 60 71 100 125 140JAA D English OPERATION MANUAL For safe and correct use please read this operation manual thoroughly before operating the air conditioner unit FOR USER ORIGINAL ...

Page 2: ...ric shock or fire may result This air conditioner is NOT intended for use by children or infirm persons without supervision Young children must be supervised to ensure that they do not play with the air conditioner If the refrigeration gas blows out or leaks stop the operation of the air conditioner thoroughly ventilate the room and contact your dealer 1 Safety Precautions 2 2 Parts Names 3 3 Oper...

Page 3: ...he screen When the backlight is off pressing any button turns the backlight on and does not perform its function except for the ON OFF button ON OFF lamp This lamp lights up in green while the unit is in operation It blinks while the remote controller is starting up or when there is an error Function button F1 Main display Press to change the operation mode Main menu Press to move the cursor down ...

Page 4: ...hen the buttons are locked Full mode All icons are displayed for explanation Basic mode Fri Mode Temp Fan Room Cool Set temp Fri Cool Mode Temp Fan Set temp Appears when the On Off timer Night setback or Auto off timer function is enabled appears when the timer is disabled by the centralized control system Appears when the Weekly timer is enabled Appears while the units are operated in the energy ...

Page 5: ...acing the remote controller install the holder included with the remote controller on a wall and be sure to always place the remote controller in the holder after use Battery installation replacement 1 Remove the top cover insert two AAA batteries and then install the top cover Top cover Two AAA batteries Insert the negative end of each battery first Install the batteries in the correct directions...

Page 6: ...peration modes in the order of Cool Dry Fan Auto and Heat Select the desired operation mode Cool Dry Fan Auto Heat Operation modes that are not available to the connected indoor unit models will not appear on the display What the blinking mode icon means The mode icon will blink when other indoor units in the same refrigerant system connected to the same outdoor unit are already operated in a diff...

Page 7: ...tate in flashing In this case please set all the indoor units to the same operation mode There might be a case that the indoor unit which is operating in AUTO mode Cannot change over to the operating mode COOL HEAT and becomes a state of standby When indoor unit starts the operation while the defrosting of outdoor unit is being done it takes a few minutes max about 15 minutes to blow out the warm ...

Page 8: ...display If no buttons are touched for 10 minutes the screen will automatically return to the Main display Any settings that have not been saved will be lost Display of unsupported functions F1 F2 F3 F4 Title Not available Unsupported function Return The message at left will appear if the user selects a function not supported by the corresponding indoor unit model 3 5 2 Vane Vent Lossnay Accessing ...

Page 9: ...ows Press the AUTOSTOP button Time can be set while the following symbol is blinking Off time Ⓒ STOP is blinking The stop times is displayed at Ⓓ Use the h and min buttons to set the desired time To cancel the OFF timer press the AUTOSTOP button 4 Changing the set times Press the AUTOSTART or AUTOSTOP to cancel the timer and repeat from 2 or 3 Cleaning the filters Clean the filters using a vacuum ...

Page 10: ...e water on the heat exchanger evaporates and water vapor may be emitted appears in the remote controller display During central control appears in the remote controller display and air conditioner operation cannot be started or stopped using the remote controller When restarting the air conditioner soon after stopping it it does not operate even though the ON OFF button is pressed Wait approximate...

Page 11: ...itch the auto mode setting to the AUTO single set point mode or AUTO dual set point mode For details refer to the included Notice A5 sheet or the Installation Manual 8 Specifications Item Model PEAD M50JAA D PEAD M60JAA D PEAD M71JAA D PEAD M100JAA D Power source 220 240 V 50 60 Hz Dimension Height mm 250 Width mm 900 1100 1400 Depth mm 732 Net weight 2 kg 26 27 29 30 38 39 Fan Airflow rate Low Mi...

Page 12: ...Please be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN VN79D606H03 ...