35
NOTE
●
When the indoor coil thermistor reads above 64˚F, indoor fan operates at VLo for 30 seconds.
●
When the indoor coil thermistor reads 64˚F or less, the indoor fan stops.
(3) Defrost time chart
Defrost thermistor
38˚F or more
RT61 27˚F or less
Outdoor 52C
relay(Compressor)
X62
(Solenoid coil)
SR61
Outdoor fan
Defrost
counter
Indoor fan
Indoor vane
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Horizontal
set position
Max 10 min.
30 sec.
15 sec.
30 sec.
15 sec.
VLo
❈