4 APPLICABLE FUNCTIONS
4.3 Drive recorder
93
4
■
Reconfiguring parameters
Servo parameters that set the sampling cycle, trigger condition, and other areas cannot be changed during sampling. Use the
following procedure to change these parameters.
1.
Set [Pr. PF81.0] to "0" (stop sampling) and stop sampling.
2.
Set the sampling cycle, trigger condition, and other areas with servo parameters.
3.
Set [Pr. PF81.0] to "1" or "2". Sampling starts.
■
Return to automatic setting mode
To save in the automatic setting mode again, set [Pr. PF80.0] to "0" (automatic setting). The automatic setting mode operates
automatically.
Item
Servo parameter
Reference
Sampling cycle
[Pr. PF80.2-3]
Trigger condition
[Pr. PF82] to [Pr. PF86]
Channels for sampling
[Pr. PF87] to [Pr. PF94]