(3) Error display and trouble locating
1. Display details
After conducting the self-check referring to 5-2(1), flashes repetitively and the error code will be displayed and divided
into tens’ place and ones’ place if any.
When two or more errors occur, they are displayed alternately. The error whose code has smaller number has priority to be
displayed first. There are 0.5 seconds intervals between the error codes
(2) Timing in self-check
Trouble of Defrost heater
: Self-check is conducted after defrosting.
(Make sure to confirm the display before unplugging the power cord
because it is automatically reset once the power cord is unplugged.)
Trouble of Ice maker
: Press the
switch on the panel for 5 seconds. (Ice making test mode)
The setting of ice making compartment blinks on display during the test operation.
Trouble of Fan motor
: Open the door and then close it.
When abnormality is found in fan motor, buzzer sound is heard every time the door is closed.
Trouble of Inverter
: Check the error when compressor starts up or is operating.
Trouble of Thermistor
: Self-check is continuously working
For 2 minutes in self-check, a high-tone sound is heard due to the operation check of damper.
2. Check point and measures
b) Error code
Tens’ place
…
c) Error code
Ones’ place
…
Flashing
Room display
Corresponding
values
8
4
2
1
Ice making mode display
Corresponding values
8
4
2
1
e.g.) In case the errors of refrigerator thermistor (
E13
) and ice maker gear box (
E33
) are occuring simultaneously.
Tens’ place
Ones’ place
Error code
0.5
sec.
0.5
sec.
0.5
sec.
5sec.
E13
E33
E13
E33
5sec.
5sec.
5sec.
Display
Error
code
Display
Trouble
Detecting method
(*3)
Check point
Measures
Control
Tens' place Ones' place
Self-check
Testing (*1)
Ice maker is under testing
Error display
E 01
(*4)
Communication
error of
operation panel
When the following com-
munication errors occur
between control board and
operation P.C. board:
• They transmit and receive
data that has nothing to
do with settings.
• They cannot transmit
and receive data each
other for about 2 seconds.
1. Connector CN10K, CN9S, CN5D on con-
trol board
5-pin wire to wire connector (hinge)
5-pin connector on operation P.C. board
Repair the
contact failure.
Keep the same operation
as the one before the
communication error has
occurred.
2. Trouble of control board and operation
P.C. board
Replace.
E 02
Communication
error of inverter
When abnormality is found in the
communication between refrig-
erator control circuit and inverter
control circuit in control board.
(When they do not transmit and
receive data for 10 seconds.)
Replace the
control board.
Compressor OFF.
E 03
Trouble of
model judge-
ment
When the model of
control board is different
from that of operation
P.C. board.
1. Check the model name of control board. Replace.
Keep operating the unit,
and conduct error code
indication only.
2. Check the operation P.C. board.
Replace.
E 10
Trouble of ice
making tray
thermistor
When there is a short
or open circuit in the ice
making tray thermistor.
1. Connector CN9S on control board, ice gear
box 6-pin wire to wire connector, 8-pin wire
to wire connector
Repair the
contact failure.
When the compartment door
has been closed for 3 hours
and when freezer compart-
ment thermistor is -10 or
less, ice-detecting operation
starts.
2. Check the resistance of thermistor.
Replace.
E 11
Trouble of
freezer com-
partment
thermistor
When there is a short
or open circuit in the
freezer compartment
thermistor.
1. Connector CN9S on control board,
4-pin wire to wire connector
Repair the
contact failure.
After 10 minutes off, the
compressor repeats 30-
minute ON and 20-minute
OFF.
2. Check the resistance of thermistor.
Replace.
E 12
Trouble of
defrost
thermistor
When there is a short
or open circuit in the
defrost thermistor.
1. Connector CN9S on control board,
2-pin wire to wire connector
Repair the
contact failure.
The defrost heater won’t
be turned ON.
2. Check the resistance of thermistor.
Replace.