25
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER
OUTDOOR UNIT: MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
•Unit won’t operate in case the total capacity of indoor units exceeds the capacity of outdoor units.
Do not connect indoor units beyond the outdoor unit capacity.
Operation indicator lamp flashes as shown in the figure below.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and the
other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor units will start
the operation later cannot operate, indicating as shown in the figure below. In this case, please set all the indoor units
to the same operation mode.
•When indoor units start operation while the defrosting of outdoor unit is being done, it takes a few minutes (max. 10
minutes) to blow out the warm air.
•In heating operation, even though the indoor unit is not in operation, the room may get warm or the sound of refriger-
ant flowing may be heard. This is not a malfunction. The refrigerant continuously flowing into it causes this.
TROUBLESHOOTING
10
10-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing.
1) Before servicing the air conditioner, be sure to turn OFF the unit first with the remote controller, and then after
confirming the horizontal vane is closed, turn OFF the breaker and / or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel and the
electronic control P.C. board.
3) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
4) When connecting or disconnecting the connectors, hold the housing of the connector. DO NOT pull the lead wires.
MFZ-KA25VA MFZ-KA35VA MFZ-KA50VA
3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is flashing ON and OFF to indicate an abnormality.
To make sure, check how many times the OPERATION INDICATOR lamp is flashing ON and OFF before starting service work.
2) Before servicing, check that the connector and terminal are connected properly.
3) When the electronic control P.C. board seems to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to 10-2, 10-3 and 10-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
RESET button
Insert the negative pole of the
batteries first. Check if the polarity
of the batteries is correct.
NOTE
: 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced.
This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by
the battery replacement.
3. Do not use the leaking batteries.
Press RESET button with a thin instrument, and
then use the remote controller.
Remove the front lid and insert batteries.
Then reattach the front lid.
OPERATION INDICATOR
Not lighted
Blinking
Lighted (Green)
(Green or Orange)
Blinking green : Standby for normal operation
Blinking orange : Standby for i-save operation
Lead wiring
Housing point
<Incorrect>
<Correct>
OB409E