6.5.2
Grounding
Observe the following:
• Provide independent grounding when possible. Ground the FG and LG terminals to the protective ground
conductor dedicated to the programmable controller.
• If independent grounding cannot be provided, employ (2) Shared grounding shown below.
• Use thick cables up to 2
. Bring the grounding point close to the programmable controller as much as
possible so that the ground cable can be shortened.
(3) Joint grounding Not allowed
Grounding
Programmable
controller
Programmable
controller
Programmable
controller
Another
equipment
Another
equipment
Another
equipment
Grounding
(1) Independent grounding Best
(2) Common grounding Good