3 TROUBLESHOOTING
3.4 List of Error Codes
3.4
List of Error Codes
If an error occurs during operation, the I/O module with diagnostic functions stores the corresponding error code in the buffer
memory area 'Latest error code' (Un\G2560). Additionally, 'Error flag' (X10) turns on. Turning on 'Error clear request' (Y10)
clears the error code in 'Latest error code' (Un\G2560) and 'Error flag' (X10) turns off.
Error codes of the I/O module with diagnostic functions are classified into minor errors and moderate errors.
• Minor error: Errors that occur due to an incorrect setting in programs or parameters (1000Hs)
• Moderate error: Errors including hardware failures or errors at execution of the inter-module synchronization function
(2000Hs, 3000Hs)
The following table lists error codes to be stored.
in an error code: Indicates the number of an I/O terminal in which the error has occurred. In accordance with X0 to XF (input
module) or Y0 to YF (output module), a numerical value of 0 to F is assigned.
in an error code: Refer to the error description and cause.
Error code
Error name
Error description and cause
Action
181
H
Interrupt condition target setting
range error
■
Input module with diagnostic functions
A value other than 0 to 3 and 7 to 10 has been
set in Interrupt condition target setting [n].
■
Output module with diagnostic functions
A value other than 0 to 4 and 7 has been set in
Interrupt condition target setting [n].
indicates the interrupt setting corresponding
to the error, as follows.
0: Setting 1 to F: Setting 16
■
Input module with diagnostic functions
Set a value of 0 to 3 and 7 to 10 in Interrupt
condition target setting [n].
For Interrupt condition target setting [n], refer to
the following.
Page 93 Interrupt condition target setting [n]
■
Output module with diagnostic functions
Set a value of 0 to 4 and 7 in Interrupt condition
target setting [n].
For Interrupt condition target setting [n], refer to
the following.
Page 93 Interrupt condition target setting [n]
182
H
Interrupt condition target I/O
terminal setting range error
A value other than 0 to 16 has been set in
Interrupt condition target I/O terminal setting [n].
indicates the interrupt setting corresponding
to the error, as follows.
0: Setting 1 to F: Setting 16
Set a value of 0 to 16 in Interrupt condition target I/
O terminal setting [n].
For Interrupt condition target I/O terminal setting
[n], refer to the following.
Page 94 Interrupt condition target I/O terminal
190
H
Input response time setting error
A value other than 9H to DH has been set in
Input response time setting.
Set a value of 9H to DH in Input response time
setting.
For details on Input response time setting, refer to
the following.
Page 95 Input response time setting
192
H
Input delay type setting error
A value other than 0 to 2 has been set in Input
delay type setting.
Set a value of 0 to 2 in Input delay type setting.
For details on Input delay type setting, refer to the
following.
Page 97 Input delay type setting
194
H
Input delay time setting error
A value other than 1 to 150000 has been set in
Input delay time setting.
Set a value of 1 to 150000 in Input delay time
setting.
196
H
Number of input ON times alarm
detection count setting error
A value other than 1 to 4294967295 has been
set in Number of input ON times alarm detection
count setting.
Set a value of 1 to 4294967295 in Number of input
ON times alarm detection count setting.
198
H
Event time stamp condition
setting error
A value other than 0 to 2 has been set in Event
time stamp condition setting.
Set a value of 0 to 2 in Event time stamp condition
setting.
For details on Event time stamp condition setting,
refer to the following.
Page 100 Event time stamp condition setting
1A2
H
Output delay type setting error
A value other than 0 and 1 has been set in
Output delay type setting.
Set a value 0 or 1 in Output delay type setting.
For details on Output delay type setting, refer to
the following.
Page 102 Output delay type setting
1A4
H
Output delay time setting error
A value other than 1 to 150000 has been set in
Output delay time setting.
Set a value of 1 to 150000 in Output delay time
setting.
1A6
H
Number of output ON times alarm
detection count setting error
A value other than 1 to 4294967295 has been
set in Number of output ON times alarm
detection count setting.
Set a value of 1 to 4294967295 in Number of
output ON times alarm detection count setting.