APPX
Appendix 3 Buffer Memory
93
A
Interrupt condition target setting [n]
Set the factor to be detected for interrupt operation.
• Input module with diagnostic functions
*1 When the input response time setting function or input delay function is enabled, the status of an input signal may be different from the
status of the actual external input signal (X00 to X0F).
• Output module with diagnostic functions
When a value other than the above is set, the interrupt condition target setting range error (error code: 181
H) occurs.
indicates the interrupt setting number. (
= 1 to 16)
When an input signal (X), output signal (Y), or buffer memory area set in 'Interrupt condition target setting [n]' (Un\G560 to
Un\G575) is turned on, an interrupt request is sent to the CPU module.
n indicates the interrupt setting number. (n = 1 to 16)
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 0 for all the areas.
Setting value
Description
0
Disable
1
'Error flag' (X10)
2
'Alarm flag' (X11)
3
Input disconnection detection status
7
Number of input ON times alarm detection status
8
Input signal (rise)
9
Input signal (fall)
10
Input signal (rise + fall)
Setting value
Description
0
Disable
1
'Error flag' (X10)
2
'Alarm flag' (X11)
3
Output disconnection detection status
4
Output short-circuit detection status
7
Number of output ON times alarm detection status
Buffer memory name
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Interrupt condition target
setting [n]
560
561
562
563
564
565
566
567
568
569
570
571
572
573
574
575