APPX
Appendix 3 Buffer Memory
97
A
Input delay type setting
Set the input delay type for each input.
When a value other than the above is set, the input delay type setting error (error code: 192
H) occurs.
indicates the
number of an I/O terminal in which the error has occurred. (
= 0 to F)
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 0 (OFF delay) for all the inputs.
Input delay time setting
Set the input delay time for each input.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Setting range
• The available range is 1 to 150000 (400
s to 60s). (Set the range in increments of 400
s.)
• The input delay time setting error (error code: 194
H) occurs in the input terminal where a value out of the setting range
has been set.
indicates the number of an I/O terminal in which the error has occurred. (
= 0 to F)
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 1 (400
s) for all the inputs.
Setting value
Description
0
OFF delay
1
ON delay
2
Pulse stretch
Buffer memory name
X00
X01
X02
X03
X04
X05
X06
X07
X08
X09
X0A
X0B
X0C
X0D
X0E
X0F
Input delay type setting
1060
1061
1062
1063
1064
1065
1066
1067
1068
1069
1070
1071
1072
1073
1074
1075
Buffer memory name
X00
X01
X02
X03
X04
X05
X06
X07
X08
X09
X0A
X0B
X0C
X0D
X0E
X0F
Input delay time setting
1088
1089
1090
1091
1092
1093
1094
1095
1096
1097
1098
1099
1100
1101
1102
1103
1104
1105
1106
1107
1108
1109
1110
1111
1112
1113
1114
1115
1116
1117
1118
1119
Summary of Contents for MELSEC iQ-RX40NC6B
Page 1: ...MELSEC iQ R I O Module With Diagnostic Functions User s Manual Application RX40NC6B RY40PT5B ...
Page 2: ......
Page 125: ...4 OVERVIEW 123 4 MEMO ...
Page 191: ...12 MAINTENANCE AND INSPECTION 189 12 MEMO ...
Page 227: ......