100
APPX
Appendix 3 Buffer Memory
Event time stamp condition setting
Set the event time stamp condition for each input.
When a value other than the above is set, the event time stamp condition setting error (error code: 198
H) occurs.
indicates the number of an I/O terminal in which the error has occurred. (
= 0H to FH)
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 0 (Rise) for all the inputs.
Setting for not-refreshed data
Set whether to overwrite older data with new event data for when 128 or more non-refreshed event time stamp data sets exist.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 0 (Not overwrite) for all the inputs.
Setting value
Description
0
Rise
1
Fall
2
Rise + Fall
Buffer memory name
X00
X01
X02
X03
X04
X05
X06
X07
X08
X09
X0A
X0B
X0C
X0D
X0E
X0F
Event time stamp condition
setting
1252
1253
1254
1255
1256
1257
1258
1259
1260
1261
1262
1263
1264
1265
1266
1267
Setting value
Description
0
Not overwrite
1
Overwrite
Buffer memory name
X0 to XF
Setting for not-refreshed data
1280