APPX
Appendix 3 Buffer Memory
95
A
Input response time setting
Set the input response time of input signals for each input signal.
When a value other than the above is set, the input response time setting error (error code: 190
H) occurs.
indicates the
number of an I/O terminal in which the error has occurred. (
= 0 to F)
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to BH (10ms) for all the signals.
Input HOLD/CLEAR function enable/disable
Set whether to enable or disable the input HOLD/CLEAR for each input.
■
Buffer memory address
The following table shows the buffer memory address of this area.
■
Enabling the setting
Turn on and off 'Operating condition setting request' (Y12) to enable the setting.
■
Default value
The default value is set to 1 (Enable) for all the inputs.
Setting value
Description
9H
1ms
AH
5ms
BH
10ms
CH
20ms
DH
70ms
Buffer memory name
X00
X01
X02
X03
X04
X05
X06
X07
X08
X09
X0A
X0B
X0C
X0D
X0E
X0F
Input response time setting
1024
1025
1026
1027
1028
1029
1030
1031
1032
1033
1034
1035
1036
1037
1038
1039
(1) 0: Disable, 1: Enable
Buffer memory name
X00 to X0F
Input HOLD/CLEAR function enable/disable
1040
X00
(1)
X01
X02
X03
X04
X05
X06
X07
X08
X09
X0A
X0B
X0C
X0D
X0E
X0F
b0
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
Summary of Contents for MELSEC iQ-RX40NC6B
Page 1: ...MELSEC iQ R I O Module With Diagnostic Functions User s Manual Application RX40NC6B RY40PT5B ...
Page 2: ......
Page 125: ...4 OVERVIEW 123 4 MEMO ...
Page 191: ...12 MAINTENANCE AND INSPECTION 189 12 MEMO ...
Page 227: ......