1 COMMON ITEMS
1.3 MELSEC Data Link Functions
37
1
Argument specification
This section shows the argument specification of the MELSEC data link functions.
Channel
A channel implies a network and communication route to be used when communicating with a C Controller module.
It needs to be set for each module in a user program.
Channels to be used for MELSEC data link functions are as follows:
Channel
number
Network
Communication route
12
Bus interface
Used for communication via a bus.
151 to 158
CC-Link IE Controller Network
Used for communication via a CC-Link IE Controller Network module controlled by a C Controller
module.
181 to 188
CC-Link IE Field Network
Used for communication via a CC-Link IE Field Network module controlled by a C Controller
module.
51 to 54
MELSECNET/H network
Used for communication via a MELSECNET/H network module controlled by a C Controller module.
81 to 88
CC-Link
Used for communication via a CC-Link module controlled by a C Controller module.