FX2N-64CL-M CC-Link/LT Master Block
Program Example 11
11-3
11.1
System Startup Procedure
Start
Install the FX
2N
-64CL-M, remote I/O units and power adapter to the control panel and machine.
Connect the FX
2N
-64CL-M, remote I/O units and power adapter with the dedicated flat cables.
Connect terminating resistors at the both ends of the trunk line.
Terminating CONFIG mode
Turn OFF the power to the power adapter and main unit.
Set the DIP switch in the FX
2N
-64CL-M to the ONLINE mode.
Supply power to the power adapter before the main unit.
Confirming the operation based upon LEDs
FX
2N
-64CL-M
- Data link is normal: L RUN is lit.
- Data link is abnormal: L ERR. is lit or flickering.
- Setting is abnormal: The ERR. is lit.
Remote I/O unit
- Confirm remote station connection by checking buffer memory [BFM #0 (0h) to
#3 (3h)] in the FX
2N
-64CL-M.
- Confirm device operation using peripheral equipment for the PLC (with regard to monitorly and
forcing outputs ON and OFF).
Write a control program to the main unit.
Operate the system.
End
Set the transmission speed, point mode, station No., etc. of the FX
2N
-64CL-M and remote I/O units
using the DIP switches. (Set the FX
2N
-64CL-M to the CONFIG mode.)
Check the following items before turning the power ON.
- Confirm the installation status of the FX
2N
-64CL-M, remote I/O units and power adapter.
- Confirm the supply voltage for the power adapter.
- Confirm that the RUN/STOP switch for the main unit is set to STOP.
- Confirm that the same station No. is not used in two or more remote I/O units.
Executing CONFIG mode
Supply power to the power adapter before the main unit.
(Specify reserved stations and edit the detailed remote station information here if necessary.)
Refer to
Section 5.
Refer to
Section 6.
Refer to
Sections 1
and 7.
Refer to
Section 8.
Refer to
Sections 10
and 12.
Refer to
Section 11.
Summary of Contents for MELSEC FX2N-64CL-M
Page 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Page 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Page 12: ...FX2N 64CL M CC Link LT Master Block Generic Names and Abbreviations 2 MEMO ...
Page 22: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 MEMO ...
Page 26: ...FX2N 64CL M CC Link LT Master Block System Configuration 4 4 4 MEMO ...
Page 36: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 MEMO ...