FX2N-64CL-M CC-Link/LT Master Block Model
Assignment of Buffer Memory 10
10-10
10.2.12 Model code [BFM #30 (1Eh)]
The model code (K7120) of the FX
2N
-64CL-M is stored here.
10.2.13 Detailed remote station information [BFM #32 (20h) to #95 (5Fh)]
The information (I/O type, number of points) on remote stations is stored here.
In the CONFIG mode, the contents of these buffers can be changed.
(For the details of content changes, refer to "8.4 Specification of reserved station" and "8.5
Editing the detailed remote station information".)
Buffer memory assignment
Configuration of detailed remote station information
Details of each item of detailed remote station information
1) Number of I/O points
The number of I/O points used in each station No. assigned to each buffer memory is stored
here.
The maximum number of points is 4 or 16 according to the number of points per station set
by the DIP switch.
For example, when a remote I/O unit having 16 I/O points is used in the 4-point mode, the
number of points per buffer memory is 4, and the I/O points of the remote I/O station are
assigned to four buffer memories.
In the case of composite I/O type remote unit, the larger amount between the number of
input points and the number of output points is stored.
Buffer memory No.
Description
BFM #32 (20h)
Remote station information area for the station No.1
BFM #33 (21h)
Remote station information area for the station No.2
...
...
BFM #95 (5Fh)
Remote station information area for the station No.64
Bit
Function
1(ON)
0(OFF)
b0
Number of I/O points
00001:1point
00101:5points
01001: 9points
01101:13points
00010:2points
00110:6points
01010:10points
01110:14points
00011:3points
00111:7points
01011:11points
01111:15points
00100:4points
01000:8points
01100:12points
10000:16points
The bits above are in the order "b4, b3, b2, b1, b0".
b1
b2
b3
b4
b5 to b7
(Setting prohibited)
Set these bits to 0.
b8
Input flag
Input is given.
Input is not given.
b9
Output flag
Output is given.
Output is not given.
b10
(Setting prohibited)
Set these bits to 0.
b11
Head station flag
This is the head station.
This is not the head station.
b12
Input filter setting
High-speed input
General-purpose input
b13
Output hold/clear setting
HOLD
CLEAR
b14
(Setting prohibited)
Set these bits to 0.
b15
Reserved station flag
This is specified as reserved
station.
This is not specified as
reserved station.
Summary of Contents for MELSEC FX2N-64CL-M
Page 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Page 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Page 12: ...FX2N 64CL M CC Link LT Master Block Generic Names and Abbreviations 2 MEMO ...
Page 22: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 MEMO ...
Page 26: ...FX2N 64CL M CC Link LT Master Block System Configuration 4 4 4 MEMO ...
Page 36: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 MEMO ...