FX2N-64CL-M CC-Link/LT Master Block Model
Assignment of Buffer Memory 10
10-3
Handling in the CONFIG mode
In the CONFIG mode, if the detailed remote station information [BFM #32 (20h) to #95 (5Fh)]
is edited, and if the detailed remote station information is inconsistent with remote stations
actually connected at the time of power ON as a result of the editing, there will be a data link
error.
While the detailed remote station information is being edited, the consistency with actually
connected stations is checked.
If the power is set to ON while all remote stations are unconnected or if remote stations are
disconnected after the power was set to ON, data link error is not detected, as far as the
detailed remote station information is not edited.
(For the details on editing the detailed remote station information, refer to "8.5 Editing the
detailed remote station information".)