FX2N-64CL-M CC-Link/LT Master Block
Connection of Cables, Connectors and Terminating Resistors 6
6-5
6.2.2
Wiring check
Confirm the wiring between remote I/O units and external equipment.
Example of wiring check
The figure below shows an example in which the head I/O No. in the FX
2N
-64CL-M is X020/
Y020 and 4-point mode is selected.
Operating procedure
1) Connect the FX
2N
-64CL-M, power adapter and remote I/O units using the dedicated cables.
Set the transmission speed, point mode, station No., etc. using the DIP switches in the
FX
2N
-64CL-M and remote I/O units.
At this time, select the CONFIG mode in the FX
2N
-64CL-M (by setting bit 6 ON and setting
bit 7 OFF).
2) Supply power to the power adapter before the PLC unit.
3) When the acquisition of remote I/O unit information is completed in the CONFIG mode (that
is, when b4 of the BFM #28 (1Ch) turns ON), turn the power OFF.
4) Set the FX
2N
-64CL-M to ONLINE mode (by setting bit 6 OFF and bit 7 OFF). Supply power
to the power adapter before the FX
2N
-64CL-M. Then, execute step a) or b) below.
a) Checking the wiring between the input unit and external equipment
-
Turn ON the switch corresponding to "X020" of the external equipment connected to
the input unit with station No. is 1.
-
Monitor X020 from peripheral equipment.
-
If X020 is ON, connection between the input unit and external equipment is normal.
b) Check the wiring between the output unit and external equipment
-
Turn Y020 ON/OFF from peripheral equipment using the forced ON/OFF operation.
-
If the connection between the output unit and external equipment is normal, a lamp
corresponding to "Y020" in the external equipment will light.
FX
2N
-64CL-M
(X020/Y020, 4-point mode)
4-point input unit
CL1X4-D1B2
(station No. = 1,
number of occupied
stations = 1)
X020
ON
ON
Y020
Power
adapter
4-point output unit
CL1Y4-T1B2
(station No. = 2,
number of occupied
stations = 1)
PLC main
unit
Terminating
resistor
Terminating
resistor
Summary of Contents for MELSEC FX2N-64CL-M
Page 4: ...FX2N 64CL M CC Link LT Master Block ii ...
Page 6: ...FX2N 64CL M CC Link LT Master Block iv ...
Page 12: ...FX2N 64CL M CC Link LT Master Block Generic Names and Abbreviations 2 MEMO ...
Page 22: ...FX2N 64CL M CC Link LT Master Block System Startup Procedure 3 3 2 MEMO ...
Page 26: ...FX2N 64CL M CC Link LT Master Block System Configuration 4 4 4 MEMO ...
Page 36: ...FX2N 64CL M CC Link LT Master Block Various Modes 7 7 2 MEMO ...