66
Specifications
2. Applicable Standards
Electromagnetic Compatibility
Emissions
Radiated Emission
EN61326-1/CISPR 11
,
FCC Part15 Subpart B Class A
Conducted Emission
EN61326-1/CISPR 11
FCC Part15 Subpart B Class A
Harmonics Measurement
EN61000-3-2
Flicker Meter Measurement
EN61000-3-3
Immunity
Electrostatic discharge Immunity
EN61326-1/EN61000-4-2
Radio Frequency Electromagnetic field Immunity
EN61326-1/EN61000-4-3
Electrical Fast Transient/Burst Immunity
EN61326-1/EN61000-4-4
Surge Immunity
EN61326-1/EN61000-4-5
Conducted Disturbances, Induced By Radio Frequency Fields Immunity
EN61326-1/EN61000-4-6
Power Frequency Magnetic Field Immunity
EN61326-1/EN61000-4-8
Voltage Dips and Short Interruptions
EN61326-1/EN61000-4-11
Safety
Europe
CE, as per EN61010-1
U.S. and Canada
cRUus as per UL61010-1, IEC61010-1
Installation Category
Ⅲ
Measuring Category
Ⅲ
Pollution Degree
2
3. Specifications of MODBUS
®
RTU Communication
Item
Specifications
Physical interface
RS
-
485 2wires half duplex
Protocol
RTU (Binary data)
Synchronization method
Start-stop synchronization
Network topology
Daisy-chain
Baud rate
2400, 4800, 9600, 19200, 38400bps
Data bit
8
Stop bit
1, 2
Parity
Odd, Even, None
Slave address
1 to 255 (0
:
For broadcast)
Distance
1200m
Maximum Number
31
Response time
1s or less (time to a response after receiving a query)
Terminate
120Ω
1/2W
Recommended cable
Shielded twisted pair, AWG24 to 14 gauge
◼
About Programming
In addition to this manual, read the following documents too.
⚫
Electronic Multi-Measuring Instrument ME Series MODBUS® Interface specifications .................................... LSPM-0075