6. Other
54
6.5.
Measurement Characteristic
■
Metering actions in other than operation mode
Status
Measurement
Display
Several seconds
just after turning on
the auxiliary power
supply
(Backlight is lit, and
LCD is not lit.)
No measurement
No display
Setting mode,
Set value
confirmation mode
Password protection
mode
Same actions as in
operation mode
No display of
measured value
During power failure
No measurement
No display
■
Metering actions in input status
Measurement
items
Actions
Current (A)
Current
demand (DA)
0A when the input current is less than 0.005A
When it is over the upper limit of the possible display
range (9999), the upper limit of the possible display
range (9999) is displayed.
Voltage (V)
0V when the input voltage (line voltage) is less than11V.
For 3-phase 4-wire, 0V when the line to neutral voltage
is less than 11V or the line to line voltage is less than
19V.
For 1-phase 3-wire, 0V when the voltage between
P1-P3 is less than 22V.
When it is over the upper limit of the possible display
range (9999), the upper limit of the possible display
range (9999) is displayed.
(Note 2)
Active power (W)
0W for total when the current and the voltage are 0A
and 0V for all 3 phases.
0W for each phase when the current of phase n is 0A or
the voltage of phase n is 0V.
(where n = 1,2 or 3)
When it is over the upper limit of the possible display
range (9999), the upper limit of the possible display
range (9999) is displayed.
Power factor (PF)
1.0 for total when the current and the voltage are 0A and 0V for all 3 phases.
1.0 for each phase when the current of phase n is 0A or the voltage of phase n is 0V. (where n = 1,2 or 3)
Frequency (Hz)
When the input voltage of phase1 is low voltage, ---- will
be displayed. Input 22V or more.
When the frequency is less than 44.5Hz or over
99.9Hz, ---- is displayed.
Harmonic current
(HI)
For effective value measurement
: When the current is 0A, 0A is displayed. (Each phase)
: When the voltage of phase1 is 0V or the frequency is
less than 44.5Hz, ---- is displayed for all phases.
For content factor measurement
: When the 1st current harmonic is 0A, 0% is
displayed. (Each phase)
: When the voltage of phase1 is 0V or the frequency is
less than 44.5Hz, ---- is displayed for all phases
Harmonic Voltage
(HV)
For effective value measurement
: When the current is 0V, 0V is displayed. (Each phase)
: When the voltage of phase1 is 0V or the frequency is
less than 44.5Hz, ---- is displayed for all phases.
For content factor measurement
: When the voltage is 0V, 0% is displayed. (Each
phase)
: When the voltage of phase1 is 0V or the frequency is
less than 44.5Hz, ---- is displayed for all phases
Operating Time
999999 hour is displayed if it is over 999999.
Note1: Input current and input voltage means the input to the instrument. They are not to primary sides of VT, CT.
Note2: For direct measurement, it does not input upper maximum scale value.