background image

12

INSTALLATION, RELOCATION AND INSPECTION

Installation place

Avoid installing the air conditioner in the following places.

Where flammable gas could leak.

 Caution:

Do not install the unit where flammable gas could leak.
If gas leaks and collects around the unit, it may cause an
explosion.

Where there is much machine oil.

Salty place such as the seaside.

Where sulfide gas is generated such as a hot spring.

Where oil is splashed or where the area is filled with
oily smoke.

Electrical work

Provide an exclusive circuit for power supply of the air conditioner.

Be sure to observe the breaker capacity.

 Warning:

The customer should not install this unit. If the unit is installed incorrectly, fire, electric shock, injury due to the unit
falling, water leakage, etc. may result.

 Caution:

Earth the unit.
Do not connect the earth to a gas pipe, water pipe, lightning rod or the earth of a telephone.
If the earthing is incorrect, it may cause an electric shock.

Install an earth leakage breaker depending on the place where the air conditioner is to be installed (humid place,
etc.).
If the earth leakage breaker is not installed, it may cause an electric shock.

Inspection and maintenance

When the air conditioner is used for several seasons, the capacity may be lowered due to dirt inside the unit.

Depending upon the conditions of use, an odor may be generated or dirt, dust, etc. may prevent proper drainage.

It is recommended that the unit be inspected and maintained (charged) by specialist in addition to normal maintenance.
Consult your dealer.

Operating sound considerations

Do not put an object around the air outlet of the outdoor unit. It may cause lowering of capacity or increasing of operating
sound.

If abnormal sound is heard during operation, consult your dealer.

Relocation

When the air conditioner is to be removed or reinstalled because of rebuilding, moving, etc., special techniques and work
are required.

 Warning:

Repair or relocation should not be done by the customer.
If this is done incorrectly, it may cause a fire, electric shock, injury from the unit falling, water leakage, etc. Consult
your dealer.

Disposal

To dispose of this product, consult your dealer.

If you have any questions, consult your dealer.

SPECIFICATIONS

Model

Function
Power supply
Capacity

kW

Input

kW

Weight

Indoor

kg

Outdoor

kg

Refrigerant filling capacity (R-22)

kg

IP code

Indoor
Outdoor

Permissible excessive operating LP ps

MPa

pressure

HP ps

MPa

Noise level (Hi)

Indoor

dB(A)

Outdoor

dB(A)

MCFH-13NV

MCFH-18NV

MCFH-24NV

Cooling

Heating

Cooling

Heating

Cooling

Heating

~ /N, 220-240V, 50Hz

3.7

4.0

5.0

5.4

6.0

6.2

1.31-1.40

1.13-1.22

2.03-2.12

1.91-2.01

2.72-2.75

2.54-2.65

26

26

26

38

59

72

1.35

1.80

2.40

IP20

IP20

IP20

IP24

IP24

IP24

1.3

1.3

1.3

3.9

4.8

4.2

46-47

48

48

49

52

53

Notes:
1. Rating condition

Cooling —

Indoor:

27°C DB, 19°C WB

Outdoor: 35°C DB

Heating —

Indoor:

20°C DB

Outdoor: 7°C DB, 6°C WB

2. Guaranteed operating range

Indoor

Outdoor

Upper limit

32°C DB

43°C DB

Cooling

23°C WB

Lower limit

21°C DB

21°C DB

15°C WB

Upper limit

27°C DB

21°C DB

Heating

15°C WB

Lower limit

20°C DB

-8.5°C DB

-9.5°C WB

Inverter type fluo-
rescent lamp

To prevent the effect of
a fluorescent lamp, keep
it away as far apart  as
possible.

Keep a space to
prevent the pic-
ture distortion or
the noise.

100mm or
more

500mm or
more

Wall, etc.

Well-
ventilated
dry place

1m or more

Radio

Keep the outdoor unit 3 m or
more away from the antennas
of TV sets or radios.

3 m
or more

TV

Summary of Contents for MCFH-13NV

Page 1: ...RA O UTILIZADOR TIL BRUGER FÖR ANVÄNDAREN KULLANICI Ç N ДЛЯ ПОЛЬЗОВАТЕЛЯ OPERATION MANUAL BEDIENUNGSHANDBUCH MANUEL D UTILISATION BEDIENINGSHANDLEIDING MANUAL DE INSTRUCCIONES ISTRUZIONI DI FUNZIONAMENTO E XEIPI IO O H IøN XPH Eø MANUAL DE OPERAÇÃO DRIFTSMANUAL DRIFTSMANUAL IfiLETME ELK TABI РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ Floor And Ceiling Type Air Conditioners MCFH 13NV 18NV 24NV Русский ...

Page 2: ...d do not put anything on them Yellow Danger of electric shock Be careful Blue Be sure to shut off the power After reading this manual keep it together with the installation manual in a handy place for easy reference Warning mark position and Safety device Enclosure Enclosure Air outlet Air inlet Warning Do not expose your skin directly to cool air for a long time This could damage your health Do n...

Page 3: ...r more for a long time water condensed in the air conditioner may drop and wet or damage furniture etc Do not step onto an unstable bench when maintaining the unit etc This may cause an injury etc if you fall down For installation Caution Earth the unit Do not connect the earth to a gas pipe water pipe lightning rod or the earth of a telephone If the earthing is incorrect it may cause an electric ...

Page 4: ...Air filter Deodorizing filter Gray sponge type OPTION Remote controller When installed on the ceiling Operation section When the air inlet grille is pulled forward Emergency operation switch Air inlet back and side Piping Drain hose Air outlet Drain outlet MUCFH 24NV Remote controller RESET button Signal transmitting section Operation display section ON OFF operate stop button Operation select but...

Page 5: ...1 minute 5 Press the CLOCK set button again and close the front lid Press here using a thin stick Auto restart function These models are equipped with an auto restart function If you do not want to use this function please consult the service representative because the setting of the unit needs to be changed Auto restart function is When the indoor unit is controlled with the remote controller the...

Page 6: ...peration mode before the operation is stopped is selected The operation mode selected first is not changed even if the room tem perature changes If the operation mode does not match the room condition select the appropriate operation mode by pressing the MODE button Details of auto operation Note When both Operation Indicator lamps are lighting as the air conditioner is operating to reach the targ...

Page 7: ...ly available on the window Heat en tering the room is reduced 3 Block the outdoor unit from direct sunlight This saves energy CONVENIENT INFORMATION Description of AUTO RESTART FUNCTION Refer to page 6 HEAT Comfortable warmth depends on the temperature difference between the in door and the outdoor It is recommended that the set temperature in the heating operation does not differ from the externa...

Page 8: ...r the AIR FLOW direction is automatically set to position 1 to prevent condensed water from dropping Adjust the vertical AIR FLOW direction using the re mote controller If the horizontal vane is moved manu ally it may cause trouble In heating operation if the air flow temperature is too low or when defrosting is being done the horizontal vane position is set to position 1 1 2 3 4 5 COOL DRY HEAT F...

Page 9: ...led As these models are equipped with the auto restart function the air conditioner should start operating at the same time that a power has restored WHEN THE AIR CONDITIONER IS NOT GOING TO BE USED FOR A LONG TIME When it is not going to be used for a long time 1 Perform FAN operation for 3 or 4 hours to dry the inside of the air conditioner To perform FAN operation set to the highest tempera tur...

Page 10: ...he security Then install both of them to the body REPLACEMENTOFTHEDEODORIZINGFILTER OPTION AIR CLEANING FILTER OPTION When the capacity is lowered because of dirt etc it is necessary to replace the deodorizing filter air cleaning filter Deodorizing filter replacement about once a year 1 Remove the air filter and the deodorizing fil ter together 2 Separate the deodorizing filter Gray sponge type fr...

Page 11: ...nger This is the sound of the heat exchanger defrosting This sound is heard when the outside air is absorbed from the drain hose in turning on the range hood or the ventilation fan and that makes water flowing in the drain hose spout out This sound is also heard when the outside air blows into the drain hose in case the outside wind is strong When a ventilation fan or a gas cooker is used in a roo...

Page 12: ...utdoor unit It may cause lowering of capacity or increasing of operating sound If abnormal sound is heard during operation consult your dealer Relocation When the air conditioner is to be removed or reinstalled because of rebuilding moving etc special techniques and work are required Warning Repair or relocation should not be done by the customer If this is done incorrectly it may cause a fire ele...

Page 13: ...E MELCO TOKYO VN79A005H01 This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 73 23 EEC Electromagnetic Compatibility Directive 89 336 EEC ...

Reviews: