Wiring/piping correction function
This unit has a wiring/piping correction function which corrects wiring and piping
combination. When there is possibility of incorrect wiring and piping combination,
and
confirming
the combination is
difficult,
use this function to detect and correct
the combination by following the procedures below.
Make sure that the following is done.
• Power is supplied to the unit.
• Stop valves are open.
Note:
During detection, the operation of the indoor unit is controlled by the outdoor
unit. During detection, the indoor unit automatically stops operation. This is not a
malfunction.
Procedure
Press the piping/wiring correction switch (SW871) 1 minute or more after turning
on the power supply.
• Correction completes in 10 to 15 minutes. When the correction is completed,
its result is shown by LED indication. Details are described in the following
table.
• To cancel this function during its operation, press the piping/wiring correction
switch (SW871) again.
• When the correction completed without error, do not press the piping/wiring
correction switch (SW871) again.
When the result was “cannot be corrected”, press the piping/wiring correction
switch (SW871) again to cancel this function. Then,
confir
m the wiring and piping
combination in a conventional manner by operating the indoor units one by one.
• The operation is done while the power is supplied. Make sure not to contact
parts other than the switch, including the P.C. board. This may cause electric
shock or burn by hot parts and live parts around the switch. Contacting the
live parts may cause P.C. board damage.
• To prevent electronic control P.C. board damage, make sure to perform static
elimination before operating this function.
• This function does not operate when the outside temperature is 0°C or be-
low.
LED indication during detection:
LED
1 (Red)
2 (Yellow)
3 (Green)
Lighted
Lighted
Blinking
Result of piping/wiring correction function
LED
Result
1 (Red)
2 (Yellow) 3 (Green)
Lighted Not lighted Lighted Completed
(Corrected successfully)
Blinking
Blinking
Blinking Cannot be corrected
Other indications
Refer to “SAFETY PRE-
CAUTIONS WHEN LED
FLASHES” located behind
the service panel.
Summary of Contents for M-SERIES
Page 6: ...M series C WALL MOUNTED ...
Page 38: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 36 MUH GD80VB OUTDOOR UNIT ...
Page 40: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 38 OUTDOOR UNIT MUZ FD50VA ...
Page 42: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 40 OUTDOOR UNIT MUZ FD50VABH ...
Page 45: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 43 MUZ GE42VA OUTDOOR UNIT ...
Page 46: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 44 MUZ GE42VAH OUTDOOR UNIT ...
Page 47: ...WALL MOUNTED Outdoot Unit M series WIRING DIAGRAM WALL MOUNTED C 45 MUZ GE50VA OUTDOOR UNIT ...
Page 48: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 46 MUZ GE50VAH OUTDOOR UNIT ...
Page 50: ...WALL MOUNTED Outdoor Unit M series WIRING DIAGRAM WALL MOUNTED C 48 MUZ HC25VA OUTDOOR UNIT ...
Page 192: ...WALL MOUNTED Inverter Heat Pump M series INSTALLATION PROCEDURE WALL MOUNTED C 190 ...
Page 271: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 269 ...
Page 272: ...FLOOR STANDING MFZ KA VA Series M series OPERATION FLOOR STANDING C 270 f i save OPERATION ...
Page 289: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 287 ...
Page 290: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 288 ...
Page 292: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 290 ...
Page 293: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 291 ...
Page 294: ...CEILING CASSETTE Inverter Heat Pump M series INSTALLATION PROCEDURE CEILING CASSETTE C 292 ...
Page 300: ...CEILING CASSETTE M series CEILING CASSETTE C 298 ...