36
CHAPTER 3
●
General Technical Considerations
9. Comparison of Heat Recovery Techniques
The methods by which heat recovery devices can be categorised may be considered as follows:
Basic methods of total heat exchangersa
9.1 Principle construction of rotary-type
●
The rotary-type heat recovery unit is composed of a rotor that
has a layered honeycomb structure made of kraft paper, drive
motor and housing.
A large quantity of moisture absorbent material (lithium chloride,
etc.) is applied onto the rotor, and humidity is transferred.
The rotor is rotated eight times a minute by the drive motor.
●
The principle of this rotary-type is for example when cooling, the
high temperature and high humidity fresh air passes through the
rotor, with the heat and humidity being absorbed by the rotor.
As the rotor is rotating, it moves into the exhaust air passage,
and the heat and humidity is discharged to outdoors because
the exhaust is cool and has a low humidity.
The rotor rotates and returns to the fresh air passage to absorb
the heat and humidity again.
●
Function of purge sector
There are two separation plates (purge sector) in the front and
back of the rotor to separate the flow of the air. As one of the
plates is slightly shifted, part of the fresh air always flows into the
exhaust air passage to prevent the exhaust air and fresh air from
mixing. (A balanced pressure difference is required.)
A
Vs
B
Vr
When a purge sector is mounted, the introduction of the exhaust
air in the rotor to the air on the supply side can be prevented.
Vr: Rotor speed, Vs: Air speed in relief section
Approx. 1.5 ø
Purge sector
Exhaust
Fresh air
Drive motor
Power supply
AC 200 V 50/60 Hz
Rotor
Bearing
Supply air
Fresh air
Return air
Exhaust
Drive motor
Room side
Purge sector
Fresh sir
Return air
Rotor rotation direction
Summary of Contents for Lossnay PZ-41SLB-E
Page 4: ...CHAPTER 1 Ventilation for Healthy Living Lossnay Unit ...
Page 17: ......
Page 18: ...CHAPTER 2 Lossnay Construction and Principle ...
Page 24: ...CHAPTER 3 General Technical Considerations ...
Page 41: ......
Page 42: ...CHAPTER 4 Characteristics ...
Page 56: ...53 CHAPTER 4 Characteristics ...
Page 57: ...54 CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 83: ......
Page 84: ...CHAPTER 7 Installation Considerations ...
Page 88: ...CHAPTER 8 Filtering for Freshness ...
Page 96: ...CHAPTER 9 Service Life and Maintenance ...
Page 98: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 101: ......
Page 102: ...CHAPTER 11 Lossnay Q and A ...
Page 108: ...Lossnay Remote Controller ...
Page 109: ......
Page 197: ...MEMO ...
Page 198: ...Y04 002 Jul 2004 MEE ...