154
«
After supplying power to the sys-
tem, HO blinks for a maximum of
about 10 minutes.
(This is not an error.)
«
Make the group setting (registra-
tion). If using a system with a cen-
tralised controller, register at the
centralised controller. If there is only
the Lossnay remote controller, reg-
ister at the remote controller. (refer
to “15. Appendix” or page 179)
«
Check the group setting at the
MELANS. (refer to “15. Appendix”)
«
Check the power supply to the
Lossnay. (refer to page 161)
«
Check the power supply.
«
Check the transmission cable
connection (connected to
A
,
B
of terminal unit TB5 on the Loss-
nay board). (refer to page 165)
«
Check the Lossnay address.
(refer to page 166)
«
If the board has been replaced,
reset the group settings. (refer to
“15. Appendix”)
«
Check the length of the trans-
mission cable wiring.
2
No.
Displays “HO” and does
not start.
«
It is less than 10 minutes since the power was
supplied to the system.
«
Group setting (registration) has not been
made.
«
Remote control address has not been registered
in the group setting by the centralised controller.
«
Power supply to the Lossnay is not turned on.
«
Lossnay is connected to a power supply with a
rating outside specification.
«
Lossnay transmission cable connection termi-
nal is wrong.
«
Lossnay address was changed.
«
Lossnay board was changed.
«
The length of wiring of the transmission cable is longer
than specifications (longer than maximum 200 m from
the power supply unit, longer than 500 m between ends).
3
Cannot register the Loss-
nay from the remote con-
troller or the controller.
«
Power supply to the Lossnay is not turned on.
«
Lossnay is connected to a power supply with a
rating outside specification.
«
Transmission cable to the Lossnay is not con-
nected.
«
Lossnay transmission cable connection termi-
nal is wrong.
«
Lossnay address is wrong.
«
The length of wiring of the transmission cable is longer
than specifications (longer than maximum 200 m from
the power supply unit, longer than 500 m between ends).
«
Check the power supply to the
Lossnay. (refer to page 161)
«
Check the power supply.
«
Check the transmission cable
connection. (refer to page 165)
«
Check the transmission cable
connection (connected to
A
,
B
of terminal unit TB5 on the Loss-
nay table). (refer to page 165)
«
Check the Lossnay address.
(refer to page 166)
«
Check the length of the trans-
mission cable wiring.
4
Starts or stops, or the dis-
play changes, by itself.
«
Set for interlocked operation with City Multi.
«
Cancel interlocked operation
setting. (refer to “15. Appendix” )
5
Displays a error code that
is not in the checklist.
«
Letters on the remote controller LCD are dim.
«
Replace the remote controller.
6
Cannot stop the Lossnay
with the remote controller
(display shows “Central”).
«
“Cancel Operation” setting is made from the
MELANS.
«
External priority ON/OFF setting is made.
«
Remote/nearby switch input (CN32) is set to
“Remote.”
«
Check the settings of the
MELANS.
«
Check the interlocked operation
mode setting. (refer to page 168)
«
Check the remote/nearby
change input (CN32).
Symptom
Cause
Corrective action
Summary of Contents for Lossnay PZ-41SLB-E
Page 4: ...CHAPTER 1 Ventilation for Healthy Living Lossnay Unit ...
Page 17: ......
Page 18: ...CHAPTER 2 Lossnay Construction and Principle ...
Page 24: ...CHAPTER 3 General Technical Considerations ...
Page 41: ......
Page 42: ...CHAPTER 4 Characteristics ...
Page 56: ...53 CHAPTER 4 Characteristics ...
Page 57: ...54 CHAPTER 4 Characteristics ...
Page 59: ......
Page 60: ...CHAPTER 5 System Design Recommendations ...
Page 68: ...CHAPTER 6 Examples of Lossnay Applications ...
Page 83: ......
Page 84: ...CHAPTER 7 Installation Considerations ...
Page 88: ...CHAPTER 8 Filtering for Freshness ...
Page 96: ...CHAPTER 9 Service Life and Maintenance ...
Page 98: ...CHAPTER 10 Ventilation Standards in Each Country ...
Page 101: ......
Page 102: ...CHAPTER 11 Lossnay Q and A ...
Page 108: ...Lossnay Remote Controller ...
Page 109: ......
Page 197: ...MEMO ...
Page 198: ...Y04 002 Jul 2004 MEE ...